Information based on query as of Thursday, May 2, 2024.
Permit Information
Permit NumberNAF19-00071
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 13902 N CURRANT CREEK LN
Project NameBOHL RESIDENCE
Customer Number 
ePlanReviewNo
Description
Installation of a 13D fire sprinkler system fed from private well. Total 28 heads.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final12/6/201912/9/201912/9/2019APASS
DetailsTroy Cobbley
***PASS Hydro papers uploaded to tidemark*MAS*** Gabe is the contact. Thanks for all you do! Phone #: ###-#### >> Inspection requested via web by Stan Beus
DOC - Permit Finaled  12/9/2019 DONE
DetailsMark Stumbaugh
INSP-Sprinkler Rough-in/Hydro12/5/201912/6/201912/6/2019APASS
DetailsTroy Cobbley
**PASS* Hydro passed. Heads that were blocked byfaux beams have been relocated.*MAS***
Gabe is the contact.Thanks for all you do! Phone #: ###-#### >> Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro11/25/201911/25/201911/25/2019PFAIL
DetailsTroy Cobbley
** Fail - Heads in great room need to be relocated due to newly installed faux beams* MAS**
Gabe is the field contact. Thanks for all you do! Phone #: ###-#### >> Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in8/20/20198/21/20198/21/2019APASS
DetailsTroy Cobbley
*** Pipe tenting passed. Ok to cover. Good work Gabe**MAS** Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in8/19/20198/20/20198/20/2019AFAIL
DetailsTroy Cobbley
***Piping in attic leading up to upper ceiling heads in family room, and entryway still need tenting/insulation corrected*** Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in8/14/20198/15/20198/15/2019PFAIL
DetailsTroy Cobbley
Tenting still needs modified in the bedroom with the soffit, insulation needs to be added at both sides of the two drops in this room to keep blow-in insulation out and heat in. Also the two 1" pipe risers that supply piping in the living room vaulted ceiling have been installed on the outside of the plywood. They have been insulated/tented vertically but when the owner insulates the wall it will effectively block off the transfer of heat. The pipe should be relocated to the inside of the wall and insulation placed behind the piping.

Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro8/13/20198/14/20198/14/2019AFAIL
DetailsTroy Cobbley
*Areas that need additional tenting marked in red on approved drawings. Hydro failed dropped from 210 to 182 psi. Underground piping not installed yet.**MAS**
Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### >> Inspection requested via web by Stan Beus