Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR19-00761
StatusIssued
Name WEBSTER FIRE PROTECTION
Site Address 502 W FRONT ST
Project NameHome 2 Suites
Customer Number 
ePlanReviewYes
Description
New fire alarm system in a new 7 story hotel with attached parking structure. Not classified as a high story. This work is associated with building permit BLD18-03143.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/5/20203/6/20203/6/2020APART
DetailsJim Page
Elevator recall complete, initiating devices in pump room, garbage room, mech room next too fire pump room and fire panel heat have been tested. Level 1 garage dry system and level 6 dry system alarm pressure switches reported to panel, all other monitoring devices will need to be tested after trip times are corrected on dry systems, no other fire alarm associated devices for fire sprinkler monitoring have been tested. Monitoring has been verified.

Coordinated with Sprinkler contractor for 9AM inspection, Buck Phone #: ###-####
INSP-Final Inspection3/4/20203/5/20203/5/2020ACANC
DetailsJim Page
Rescheduled for 9AM, 06MAR2020, this request is cancelled.

Buck Phone #: ###-####
Plan resubmittals received  2/26/2020 DONE
Alarm Plan Check2/26/2020 2/26/2020 PASS
DetailsLee G Meredith
Design is passed as noted and will require a plan modification or as built submittal prior to final acceptance testing. Any changes to this design (as noted) will require resubmittal. This passed design is required to be sent to the engineer of record for review and approval. Any changes required by the engineer of record will required resubmittal for city review.
PLANS TAKEN FRONT DESK ALARM  2/26/2020 PASS
Review is passed as noted with review comments and requirements.

4th review requires review at $65 per hour. Total 4th review time is 2.5 hours for a total of $162.50, plus the original base fee of $150.00, plus total amount for 129 alarm devices. Installation has begun prior to a permit being issued so permit fee is to be doubled.
Permit Ready to Issue  2/26/2020 DONE
met
Issue and Print Permit  2/26/2020 DONE
Plan resubmittals received  2/25/2020 DONE
1st review completed  2/25/2020 FAIL
Detection coverage corrections still have note been made. Returned to Ken to have drawing notes / requirements met.
Plan resubmittals received  2/18/2020 DONE
1st review completed  2/18/2020 FAIL
See 2nd review comments. Updated review comments were emailed to Rita.
Plan assigned to (Lee)10/9/2019 10/9/2019 DONE
DetailsLee G Meredith
Intake Approval  10/9/2019 PASS
1st review completed  10/9/2019 FAIL
See 1st review comments.
Application received  10/8/2019 DONE
Application submitted via PDS Online on Oct 8 2019 11:22AM