Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR20-00125
StatusFinaled
Name JBL FIRE PROTECTION LLC
Site Address 8210 S BOGUS RIDGE AVE
Project NameRush Valley Tatom 8210
Customer Number 
ePlanReviewYes
Description
Single Family Dwelling per NFPA 13D
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/12/20206/12/20206/12/2020PPASS
DetailsJim Page
Previously noted items have been corrected, final fire sprinkler inspection is complete, irrigation shutdown on flow switch activation witnessed.
INSP-Final Inspection6/5/20206/9/20206/9/2020AFAIL
DetailsJim Page
Hole was cut into ceiling in master bathroom, tenting has been removed from over top of pipe, area notated had no insulation on top of piping. Provide 175 degree head in master closet, head is within 24 inches of heat register.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
INSP-Sprinkler Rough-in/Hydro6/5/20206/9/20206/9/2020ADONE
DetailsJim Page
Hydrostatic test for overhead fire srpinkler piping witnessed at city pressure, no pressure loss onserved at riser provided gauge.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
INSP-Sprinkler Rough-in4/13/20204/14/20204/14/2020APASS
DetailsJim Page
All tenting in place at time of inspection, cover is approved. Sticker has been placed for cover approval.

tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
INSP-Sprinkler Rough-in4/1/20204/3/20204/3/2020PPART
DetailsJim Page
Rough in inspection complete, no tenting installed at time of inspection, cover is not approved.

Phone #: ###-#### Inspection requested via web by Jonathan Lee
Issue and Print Permit  2/25/2020 DONE
Intake Approval  2/21/2020 PASS
DetailsMark Stumbaugh
Plan assigned to (Stumbaugh)2/21/2020 2/21/2020 DONE
DetailsMark Stumbaugh
Sprinkler Plan Check2/21/2020 2/21/2020 PASS
DetailsMark Stumbaugh
1st review completed  2/21/2020 PASS
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  2/21/2020 DONE
DetailsMark Stumbaugh
Permit Ready to Issue  2/21/2020 DONE
met
Application received  2/19/2020 DONE
Application submitted via PDS Online on Feb 19 2020 5:02PM