BLD-Final | 3/28/2018 | 3/29/2018 | 3/29/2018 | A | PASS |
Dave Hannah
|
|
|
Victoria Phone #: ###-####
|
FIRE-Final Inspection | 3/28/2018 | 3/28/2018 | 3/28/2018 | P | PASS |
Jim Page
|
|
|
Final life fire safety inspection complete.
|
BLD-Final | 10/23/2017 | 10/24/2017 | 10/24/2017 | A | NR |
Dave Hannah
|
|
|
Victoria-please call Victoria she has questions about this permit and the camopies permit Phone #: ###-####
|
BLD-Conference | 4/28/2016 | 4/29/2016 | 4/29/2016 | A | PASS |
Dave Hannah
|
|
|
would like call ahead; Walter Phone #: ###-#### ok to remove exit signs on 6th floor patio cover
|
BLD-Conference | 11/23/2015 | 11/23/2015 | 11/23/2015 | P | PASS |
Dave Hannah
|
|
|
Conf requested by Victoria via voicemail, not sure on exact area Phone #: ###-####
|
BLD-Final | 11/23/2015 | 11/23/2015 | 11/23/2015 | P | PART |
Dave Hannah
|
|
|
ok for temp occ ok for perm occ after other buildings are finaled and under ground parking garage can be openned
|
BLD-Conference | 11/10/2015 | 11/12/2015 | 11/12/2015 | A | PART |
Dave Hannah
|
|
|
Victoria Phone #: ###-#### ok to have simplot employees tour site
|
BLD-Conference | 10/22/2015 | 10/23/2015 | 10/23/2015 | A | DONE |
Dave Hannah
|
|
|
Victoria Phone #: ###-####
|
BLD-Conference | 9/17/2015 | 9/18/2015 | 9/18/2015 | A | PASS |
Jim Storey
|
|
|
CJ Phone #: ###-####
|
BLD-Final | 8/27/2015 | 8/28/2015 | 8/28/2015 | A | PART |
Dave Hannah
|
|
|
CJ Phone #: ###-#### ok for temp occ staff only still not ready for general public.
|
FIRE-Final Inspection | 8/27/2015 | 8/28/2015 | 8/28/2015 | P | PART |
Thomas Walsh
|
|
|
Fire and Life-Safety inspection of the JUMP bldg, for TCO of a small amount (10-15) of staff personnel to access the building for start-up purposes - No public access at this time. Followup inspection from this morning, including covering up some exit signs for exit stairs that are not in service at this time. Fire protection systems and fire alarm systems are fully operational and shall be kept in service at all times. There may be times when systems have to be taken off line for maint. purposes, however these systems shall always be put back into service at the end of shift. Exit gates have been identified, and fitted with panic hardware. Egress paths are in place, however some of these walkways from the JUMP structure to the public way may be temporary. Temp. exit signs were also posted to aid staff to the nearest exit gate at grade level. Fire is OK with TCO for this small amount of staff while the building is being completed.
|
FIRE-Final Inspection | 8/27/2015 | 8/28/2015 | 8/28/2015 | A | PART |
Thomas Walsh
|
|
|
Retest of the exit signs and emergency lighting system for the JUMP bldg, on generator - above ground only - underground parking garage not tested, addressing corrections made from the previous test on 8/21. All previous items deqautely addressed, The following items should be addressed prior to TCO of office staff; 1. Cover all exit signs (approx. 6) for the northwest exits on the second floor office suite. This exit, and exterior exit stair, will not be used for this partial TCO. 2. Install EM lighting fixture on pole at exit gate, located on 9th street exit. 3. Cover exit signs for parking garage far west stair, that will not be utilized for this partial TCO of office staff only. NOTE: Pathways from exit stairs, and the pedestrian walkways are currently being poured, and will be inspected later today. East exit gates will also be fitted with panic hardware devices.
|
FIRE-Final Inspection | 8/27/2015 | 8/27/2015 | 8/27/2015 | P | PART |
Thomas Walsh
|
|
|
Preliminary walk through of JUMP structure to see changes made to egress signs, walking surfaces, etc. from last inspection. An early morning retest of the EM lighting and exit signage off the generator is scheduled for 8/28 am. Some of the exit stairs (parking garage) are not completed yet, but are scheduled to be done also by 8/28. TCO for a small group of emplyees for use of the JUMP building is being proposed next week, pending successful completion of the EM light retest.
|
FIRE-Final Inspection | 8/18/2015 | 8/21/2015 | 8/21/2015 | A | PART |
Thomas Walsh
|
|
|
Exit sigage and emergency egress lighting for JUMP building, including A/G parking structure, Helix, and associated rooms that make up the JUMP bldg. Test was performed off of generator. All areas tested OK, except as follows; 1. Install exit signs at center stairs (2) in parking structure to clarify exit stairs 2. parking structure level 1 - west side lights not working. 3. Exit signs and EM lights nt working for level 2 office area.' 4.Stair A03B not lit - still under construction. 5. 5th floor kitchen area not lighted. 6.restrooms at multipurpose room not lit. 7. 4th floor frieght elevator lobby not lit. 8. Mech. mezzanine at Inspiration room not lighted. 9. Temp exit signs needed at grade level to direct personnel to exit gates, that are still not present. 10. Egress lighting along east exits not complete yet.
|
FIRE-Final Inspection | 8/18/2015 | 8/20/2015 | 8/20/2015 | P | PART |
Thomas Walsh
|
|
|
Meeting to review egress plan prior to tomorrow'smeans of egress inspection with exit sigange and emergency lights off the generator.
|
FIRE-Conference | 8/12/2015 | 8/14/2015 | 8/14/2015 | A | DONE |
Thomas Walsh
|
|
|
Meeting with GC and electrical contractors to review upcoming exit signage and emergency lighting test, which will be scheduled for early morning (5am) to get an accuarte assessment of EMs under dusk conditions, since most of the egress from the building is outside, or open to the outside.
|
FIRE-Conference | 8/11/2015 | 8/12/2015 | 8/12/2015 | A | DONE |
Thomas Walsh
|
|
|
Meeting with Bldg. Dept. (Dave) and Hoffman (ZAC) to review areas of the building that they are looking for TCO for use by staff personnel only (approx. 10-12 persons), to get things setup in the building. No public use at this time. They are shooting for temp. TCO status by next Friday (8/21). A review and inspection of the temp. egress systems will be conducted before next Friday. Fire alarm systems are still being tested, so it is the goal to get fire sprinklers, fire alarm and egress (signs and lighting) completed by then. No use of the U/G parking area is being proposed at this time.
|
BLD-Conference | 8/11/2015 | 8/12/2015 | 8/12/2015 | A | DONE |
Dave Hannah
|
|
|
CJ Phone #: ###-####
|
BLD-Final | 8/4/2015 | 8/7/2015 | 8/7/2015 | A | PEND |
Dave Hannah
|
|
|
part 2; CJ Phone #: ###-####
|
BLD-Final | 8/4/2015 | 8/6/2015 | 8/6/2015 | A | PEND |
Dave Hannah
|
|
|
part 1; CJ Phone #: ###-####
|
BLD-Conference | 8/3/2015 | 8/4/2015 | 8/5/2015 | A | DONE |
Dave Hannah
|
|
|
TJ Phone #: ###-####
|
BLD-Conference | 7/30/2015 | 7/30/2015 | 7/31/2015 | P | PASS |
Dave Hannah
|
|
|
CJ Phone #: ###-####
|
BLD-Conference | 7/23/2015 | 7/24/2015 | 7/24/2015 | A | DONE |
Dave Hannah
|
|
|
Zach Phone #: ###-####
|
BLD-Conference | 7/20/2015 | 7/20/2015 | 7/20/2015 | A | PASS |
Dave Hannah
|
|
|
C.J. Phone #: ###-####
|
BLD-Conference | 7/13/2015 | 7/17/2015 | 7/20/2015 | A | CANC |
Dave Hannah
|
|
|
C.J. Phone #: ###-####
|
BLD-Wall cover | 7/15/2015 | 7/16/2015 | 7/16/2015 | A | PASS |
Dave Hannah
|
|
|
Requesting Sheathing inspection for Entry Portal. Please contact Rudy Phone #: ###-#### Inspection requested via web by Tim Pendleton
|
BLD-Framing/Rough-in | 7/15/2015 | 7/16/2015 | 7/15/2015 | P | CANC |
Dave Hannah
|
|
|
Requesting sheathing inspection for entry portal please contact RUDY Phone #: ###-#### >> Inspection requested via web by Tim Pendleton Inspection cancelled from web by: Tim Pendleton
|
BLD-Wall cover | 3/18/2015 | 3/18/2015 | 3/18/2015 | A | PASS |
Dave Hannah
|
|
|
Requesting sheathing inspection for tractor box 02c03, 04c02 and 03d03. Phone #: ###-#### Inspection requested via web by Tim Pendleton
|
BLD-Framing/Rough-in | 3/3/2015 | 3/4/2015 | 3/4/2015 | A | PASS |
Dave Hannah
|
|
|
Requesting Framing/Sheathing inspection for East Tractor Box. Please contact Rudy Phone #: ###-#### Inspection requested via web by Tim Pendleton
|
BLD-Framing/Rough-in | 2/17/2015 | 2/18/2015 | 2/19/2015 | A | PASS |
Dave Hannah
|
|
|
Requesting sheathing inspection for level 6 service core. outside sheathing inspection for all tractor boxes excluding east box Please call Rudy Phone #: ###-#### Inspection requested via web by Tim Pendleton
|
BLD-Framing/Rough-in | 6/11/2014 | 6/12/2014 | 6/12/2014 | A | PASS |
Dave Hannah
|
|
|
Requesting a sheathing inspection for Thursday AM. Multi-Purpose Studio on Level 5 - west and south elevations. Contact Rudy with NWI at ###-####. Phone #: ###-#### >> Inspection requested via web by Noelle Idehara
|
BLD-Other | 5/2/2014 | 5/2/2014 | 5/2/2014 | P | PASS |
Dave Hannah
|
|
|
kevin - fire proofing insp Phone #: ###-####
|
BLD-Framing/Rough-in | 5/1/2014 | 5/1/2014 | 5/2/2014 | A | PART |
Dave Hannah
|
|
|
fire calking rated assembly//###-#### Shane at rooflinekitchen ok
|
FIRE-Final Inspection | 5/1/2014 | 5/1/2014 | 5/1/2014 | P | DEFR |
Forrest France
|
|
|
shane - as late as possible please call 1/2 hr prior Phone #: ###-#### * Note- intended for a structural inspection of a rated assembly*
|
BLD-Conference | 4/17/2014 | 4/18/2014 | 4/18/2014 | A | PASS |
Dave Hannah
|
|
|
Call Joey JKB Construction with comments or questions ###-#### Phone #: ###-#### >> Inspection requested via web by Leonard Dooms
|
BLD-Framing/Rough-in | 4/14/2014 | 4/15/2014 | 4/15/2014 | A | PASS |
Dave Hannah
|
|
|
Requesting inspection for the following items. Please call Rudy with Northwest Interiors to coordinate inspection ###-####.
1. Exterior Framing Inspection - Inspiration Studio.
2. Exterior Framing Inspection - at grid G around the helix on Level 4 (east and west sides).
3. Sheathing Inspection at Service Core for Levels 1-4 (excluding west and south elevations at just the service elevator). Phone #: ###-#### >> Inspection requested via web by Noelle Idehara
|
BLD-Framing/Rough-in | 3/25/2014 | 3/25/2014 | 3/25/2014 | P | PART |
Dave Hannah
|
|
|
requesting exterior framing inspection at the lobby/kitchen. Grid lines 9.4-9.5 Phone #: ###-#### >> Inspection requested via web by Tim Pendleton ok to start ext sheeting
|
BLD-Framing/Rough-in | 3/20/2014 | 3/21/2014 | 3/21/2014 | A | PASS |
Dave Hannah
|
|
|
requesting exterior sheathing inspection at the kitchen. Grid lines 9.3-9.3a. Phone #: ###-#### >> Inspection requested via web by Tim Pendleton
|
BLD-Other | 3/18/2014 | 3/19/2014 | 3/20/2014 | P | DONE |
Dave Hannah
|
|
|
Field walk with special inspector and field superintendent Zac Ross. Zac''s cell is ###-####. Phone #: ###-#### >> Inspection requested via web by Noelle Idehara
|
BLD-Framing/Rough-in | 3/11/2014 | 3/12/2014 | 3/12/2014 | A | PART |
Jim Sly
|
|
|
Requesting an exterior framing inspection for the Lobby/Kitchen Studio. Phone #: ###-#### >> Inspection requested via web by Noelle Idehara Insp. of South wall Lobby/Kitch/studio....Rock, ice/water shield, flashing, Vertical aluminum screwed at 8" OC, and Horizontal purlins. OK to install finish product.
|
BLD-Framing/Rough-in | 2/17/2014 | 2/18/2014 | 2/19/2014 | A | PASS |
Dave Hannah
|
|
|
Need exterior steel stud framing inspection at the kitchen. Grid lines 9.3-9.3a. Phone #: ###-#### >> Inspection requested via web by Tim Pendleton
|