Information based on query as of Tuesday, July 23, 2024.
Permit Information
Permit NumberBLD19-03981
StatusFinaled
Name STEWART CONSTRUCTION SERVICES LLC
Site Address 1021 S BROADWAY AVE
Project NameUptown Cheapskate
Customer Number 
ePlanReviewYes
Description
(UPTOWN CHEEPSKATE – TENANT IMPROVEMENT – RETAIL SALES) (11-25-19 PLAN MODIFICATION TO CHANGE THE LOCATION OF THE “HIGH” AND THE “LOW” DRINKING FOUNTAINS. A CANE APRON IS REQUIRED AT THE “HIGH” DRINKING FOUNTAIN.) This building does not have a fire sprinkler system. To remodel an existing 6,369 square foot tenant space (4,748 square feet at grade and 1,621 square feet on upper level) for a new retail sales tenant. The upper level will be reduced in size by at least 312 square feet by creating an un-occupiable “attic” so that the area of the upper level complies as a mezzanine. The “attic” area will be completely enclosed by full height walls with the only access being a 22” x 30” attic access opening. A sign will be posted at the opening stating, “This area is not approved for any occupancy or for any use, including storage” or words to that effect. The usable portion of the mezzanine is allowed to have a maximum floor area of about 1,318 square feet. The usable portion of the mezzanine will continue to be used for storage, as an employee break room, and as an office. Work is to include interior nonbearing walls, 7 dressing rooms with one accessible to the disabled, display shelving, millwork, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final4/8/20204/9/20204/9/2020APASS
DetailsJim Storey
Christian **cleared** Phone #: ###-####
FIRE-Final Inspection4/7/20204/8/20204/8/2020PPASS
DetailsJim Page
Previously noted item has been corrected, no fire sprinklers, duct detection is complete (FIR20-00245) with no other fire alarm items, fire extinguishers are placed with current inspection tags. Final life fire safety inspection is complete, signature card not presented at time of inspection.

*screened* - Christian Phone #: ###-####
FIRE-Final Inspection3/25/20203/27/20203/27/2020AFAIL
DetailsTroy Cobbley
Items on correction list have been addressed except for the duct smoke detectors. They will require a FIR permit as discussed. They will need to be tested for function. I noted that the incorrect remote annunciators have been installed and the duct smoke detectors are mounted on the supply side not the return side.. I let the store owner/employee take a picture of a cut sheet I had for the correct annunciator. I left a message for the contact listed below but he was not on site. I spoke to the tenant as stated.

Christian Phone #: ###-####
BLD-Final3/25/20203/27/20203/27/2020PCANC
DetailsJim Storey
cancel per christian 3-27-2020 Christian Phone #: ###-####
FIRE-Final Inspection3/6/20203/9/20203/9/2020PFAIL
DetailsJim Page
Provide fire exitinguisher on upper mezzanine, provide fire extingiushers throughout level 1, 2 extinguishers for tenant space and last annual inspection was 2014. Emergency light at top of stairs was inoperable at time of inspection. Wireless smoke detectors still placed in 3 areas, will need to be removed or permitted. Need to verify CFM for HVAC units, HVAC units over 2000 CFM will require HVAC fan shutdown on in-duct smoke detection activation. Provide emergency lighting in changing room corridor. Provide code compliant door hardware on south entry/exit door.

Christian Phone #: ###-####
BLD-Final2/24/20202/24/20202/24/2020PCANC
DetailsJim Storey
Christian Phone #: ###-####
BLD-Final2/10/20202/12/20202/12/2020PNR
DetailsJim Storey
Christian Phone #: ###-#### pending fire c./n
FIRE-Final Inspection2/10/20202/11/20202/11/2020PFAIL
DetailsJim Page
Fire alarm/smoke detector system has been installed without an FIR permit, non required fire alarm/smoke detection system must comply with 2015 IFC, section 901.4.2, FIR permit has not been issued for fire alarm system, a FIR permit is required for all commercial fire alarm system installs. Door hardware on south door is not code compliant, no other items inspected.

Christian Phone #: ###-####
BLD-Final2/7/20202/10/20202/10/2020PFAIL
DetailsJim Storey
Christian Phone #: ###-#### door singage remain unlocked/ ada signage latch side of doors/ under sink protection/ fire sign off.
FIRE-Final Inspection2/7/20202/10/20202/10/2020AFAIL
DetailsJim Page
Called point of contact provided, was instructed that space was not open. Drove to tenant space, door was locked. Space was occupied before inspection process has been completed.
GR
Christian Phone #: ###-####
BLD-Framing/Rough-in11/20/201911/21/201911/21/2019APART
DetailsJim Storey
Mychal Phone #: ###-#### pending ele