BLD-Final | 4/8/2020 | 4/9/2020 | 4/9/2020 | A | PASS |
Jim Storey
|
|
|
Christian **cleared** Phone #: ###-####
|
FIRE-Final Inspection | 4/7/2020 | 4/8/2020 | 4/8/2020 | P | PASS |
Jim Page
|
|
|
Previously noted item has been corrected, no fire sprinklers, duct detection is complete (FIR20-00245) with no other fire alarm items, fire extinguishers are placed with current inspection tags. Final life fire safety inspection is complete, signature card not presented at time of inspection.
*screened* - Christian Phone #: ###-####
|
FIRE-Final Inspection | 3/25/2020 | 3/27/2020 | 3/27/2020 | A | FAIL |
Troy Cobbley
|
|
|
Items on correction list have been addressed except for the duct smoke detectors. They will require a FIR permit as discussed. They will need to be tested for function. I noted that the incorrect remote annunciators have been installed and the duct smoke detectors are mounted on the supply side not the return side.. I let the store owner/employee take a picture of a cut sheet I had for the correct annunciator. I left a message for the contact listed below but he was not on site. I spoke to the tenant as stated.
Christian Phone #: ###-####
|
BLD-Final | 3/25/2020 | 3/27/2020 | 3/27/2020 | P | CANC |
Jim Storey
|
|
|
cancel per christian 3-27-2020 Christian Phone #: ###-####
|
FIRE-Final Inspection | 3/6/2020 | 3/9/2020 | 3/9/2020 | P | FAIL |
Jim Page
|
|
|
Provide fire exitinguisher on upper mezzanine, provide fire extingiushers throughout level 1, 2 extinguishers for tenant space and last annual inspection was 2014. Emergency light at top of stairs was inoperable at time of inspection. Wireless smoke detectors still placed in 3 areas, will need to be removed or permitted. Need to verify CFM for HVAC units, HVAC units over 2000 CFM will require HVAC fan shutdown on in-duct smoke detection activation. Provide emergency lighting in changing room corridor. Provide code compliant door hardware on south entry/exit door.
Christian Phone #: ###-####
|
BLD-Final | 2/24/2020 | 2/24/2020 | 2/24/2020 | P | CANC |
Jim Storey
|
|
|
Christian Phone #: ###-####
|
BLD-Final | 2/10/2020 | 2/12/2020 | 2/12/2020 | P | NR |
Jim Storey
|
|
|
Christian Phone #: ###-#### pending fire c./n
|
FIRE-Final Inspection | 2/10/2020 | 2/11/2020 | 2/11/2020 | P | FAIL |
Jim Page
|
|
|
Fire alarm/smoke detector system has been installed without an FIR permit, non required fire alarm/smoke detection system must comply with 2015 IFC, section 901.4.2, FIR permit has not been issued for fire alarm system, a FIR permit is required for all commercial fire alarm system installs. Door hardware on south door is not code compliant, no other items inspected.
Christian Phone #: ###-####
|
BLD-Final | 2/7/2020 | 2/10/2020 | 2/10/2020 | P | FAIL |
Jim Storey
|
|
|
Christian Phone #: ###-#### door singage remain unlocked/ ada signage latch side of doors/ under sink protection/ fire sign off.
|
FIRE-Final Inspection | 2/7/2020 | 2/10/2020 | 2/10/2020 | A | FAIL |
Jim Page
|
|
|
Called point of contact provided, was instructed that space was not open. Drove to tenant space, door was locked. Space was occupied before inspection process has been completed. GR Christian Phone #: ###-####
|
BLD-Framing/Rough-in | 11/20/2019 | 11/21/2019 | 11/21/2019 | A | PART |
Jim Storey
|
|
|
Mychal Phone #: ###-#### pending ele
|