BLD-Final | 7/27/2020 | 7/28/2020 | 7/28/2020 | A | PASS |
Tony Young
|
|
|
Phone #: ###-#### Inspection requested via web by tracey Garrett// ok for perm. occupancy pending others
|
BLD-Grading Inspection | 7/27/2020 | 7/27/2020 | 7/27/2020 | P | DONE |
Tony Young
|
|
|
Phone #: ###-#### Inspection requested via web by tracey Garrett
|
BLD-Final | 7/16/2020 | 7/17/2020 | 7/17/2020 | A | PART |
Jim Storey
|
|
|
Phone #: ###-#### Inspection requested via web by tracey Garrett need others signed off no card for occ issued per bill.
|
FIRE-Final Inspection | 7/16/2020 | 7/16/2020 | 7/16/2020 | A | PASS |
Jim Page
|
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags, knox box is located by fire sprinkler riser room. Main entry and rear exit have mag locks installed as required by NFPA101 as well as state requirements for the type of use for this building. Mag locks do release on fire alarm activation and remain unlocked until fire panel is reset. Final life fire safety inspection is complete, signature card not available at time of inspection.
|
BLD-Footing | 7/13/2020 | 7/13/2020 | 7/13/2020 | P | PASS |
Tony Young
|
|
|
Inspect footings for deck at rear of residence; prior to cover. Phone #: ###-#### Inspection requested via web by tracey Garrett
|
BLD-Other | 5/28/2020 | 5/29/2020 | 5/29/2020 | A | PEND |
Tony Young
|
|
|
request DRAINAGE INSPECTOR from Public Works to come to job for consult with contractor. Thank you. Bill''s cell ###-####. or Tracey at office ###-#### Phone #: ###-#### Inspection requested via web by tracey Garrett
|
BLD-Wall cover | 5/8/2020 | 5/11/2020 | 5/11/2020 | A | PASS |
Tony Young
|
|
|
Please inspect prior to sheetrock cover. Thank you. Phone #: ###-#### Inspection requested via web by tracey Garrett,, double drywall ok
|
BLD-Energy code compliance | 4/28/2020 | 4/30/2020 | 4/30/2020 | A | PASS |
Tony Young
|
|
|
Inspection needed for energy code, ; wall cover. Thank you. Phone #: ###-#### Inspection requested via web by tracey Garrett
|
BLD-Framing/Rough-in | 4/27/2020 | 4/28/2020 | 4/28/2020 | A | PART |
Tony Young
|
|
|
Inspection needed for framing, energy code, ; wall cover. Thank you. Phone #: ###-#### Inspection requested via web by tracey Garrett frame ok pending sprinkler pass
|
FIRE-Conference | 4/13/2020 | 4/13/2020 | 4/13/2020 | P | DONE |
Jim Page
|
|
|
Fire confernce is complete, atic heat detection will need to be revised before final inspection for acceptance, current drawing does not cover attic space correctly as discussed with Lee Meridith, Fire Alarm Plan Reviewer.
Tracey- conference Phone #: ###-####
|
BLD-Framing/Rough-in | 4/7/2020 | 4/7/2020 | 4/8/2020 | P | PART |
Tony Young
|
|
|
Request a "partial" framing inspection: Soffits to be inspected per Inspector. Phone #: ###-#### Inspection requested via web by tracey Garrett// soffit ok to cover
|
BLD-Conference | 4/1/2020 | 4/2/2020 | 4/3/2020 | P | PART |
Tony Young
|
|
|
on site conf with all trades,, call 415 if ?s,, on site meeting with all.. code ?s
|
BLD-Conference | 3/27/2020 | 4/2/2020 | 4/3/2020 | P | PART |
Tony Young
|
|
|
Tracey Phone #: 208 ###-####// on site conf with all parties,, owner, builder, trades, etc. to go over code requirements
|
BLD-Wall cover | 3/2/2020 | 3/2/2020 | 3/2/2020 | P | PART |
Tony Young
|
|
|
Bill Phone #: ###-####,, girders ok to apply draft stop on,, exterior shear panels ok to cover
|
BLD-Conference | 2/13/2020 | 2/13/2020 | 2/13/2020 | P | PASS |
Tony Young
|
|
|
?s on firewalls,, take plan reviewer,, went over fire wall/ceiling, draft stops,, R4 requirements
|
BLD-Conference | 2/12/2020 | 2/13/2020 | 2/13/2020 | A | PASS |
Tony Young
|
|
|
?s on firewalls,, take plan reviewer
|