Permit NumberFIR19-00783
StatusIssued
Name ALPINE FIRE SPRINKLERS NC
Site Address 11910 W FAIRVIEW AVE
Project NameVillage East Apartments Bldg A
Customer Number 
ePlanReviewYes
Description
Building A 3 stories - New 13R fire sprinkler system. Dedicated fire line installed under FIR19-00773
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in6/23/20206/23/20206/23/2020PPASS
DetailsTroy Cobbley
Piping in first floor soffits is ok for cover.

Screened- Tanner Phone #: ###-####
INSP-Sprinkler Rough-in6/22/20206/22/20206/22/2020PPASS
DetailsTroy Cobbley
Piping in the second floor soffits is ok for cover.

screened // MIke Phone #: ###-####
INSP-Sprinkler Rough-in6/9/20206/10/20206/10/2020APASS
DetailsTroy Cobbley
Piping in the third floor soffits is ok for cover.

Screened- Tanner Phone #: ###-####
INSP-Supply line flush6/5/20206/5/20206/5/2020PCANC
DetailsTroy Cobbley
Tanner Phone #: ###-####
INSP-Sprinkler Rough-in5/13/20205/14/20205/14/2020APASS
DetailsTroy Cobbley
Heat taped piping is ok for cover. Tanner Phone #: ###-####
INSP-Sprinkler Rough-in5/11/20205/11/20205/11/2020PCANC
DetailsTroy Cobbley
Tanner Phone #: ###-####
INSP-Sprinkler Rough-in5/6/20205/6/20205/7/2020PPASS
DetailsTroy Cobbley
Tenting passed, heat tape/insulation complete. All piping can be covered. Screened- Tanner Phone #: ###-####
INSP-Sprinkler Rough-in5/5/20205/5/20205/5/2020PFAIL
DetailsTroy Cobbley
Need as-builts showing the pipe routing changes and pipe size changes, repair the tenting in two spots, relocate one overspaced pendant in the breezeway and repir two hangers on the first floor.

screened // Tanner Phone #: ###-####
INSP-Sprinkler Rough-in4/27/20204/27/20204/27/2020PCANC
DetailsTroy Cobbley
Cancel per Tanner Phone #: ###-####
INSP-Sprinkler Rough-in4/22/20204/23/20204/23/2020ACANC
DetailsTroy Cobbley
Cancel per point of contact. Tanner **Cleared** Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro1/6/20201/6/20201/6/2020PCANC
DetailsTroy Cobbley
Wrong permit number scheduled. Bill Phone #: ###-####