Permit Information
Permit NumberFIR20-00062
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 7485 N LUCY ROSE LN
Project NameEAGLE HAWK APTS. BLD 2
Customer Number 
ePlanReviewYes
Description
TFSS TO INSTALL A NEW NFPA 13R FIRE SPRINKLER SYSTEM IN THIS NEW APARTMENT BUILDING.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/23/20206/24/20206/24/2020APASS
DetailsJim Page
Final fire sprinkler inspection is complete.

James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in4/13/20204/13/20204/13/2020PFAIL
DetailsJim Page
Tenting has been altered by other trades in numerous areas, cover is not approved until tenting is corrected.

Tenting inspection, call James if issues. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro4/8/20204/9/20204/9/2020PDONE
DetailsJim Page
Hydrostaic test for overhead fire sprinkler piping has been witnessed, no pressure loss observed at riser provided gauge.

Overhead rough/hydro/tenting. Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in4/9/20204/9/20204/9/2020AFAIL
DetailsJim Page
Rough in inspection is complete, tenting has been removed by other trades in numerous areas, cover is not approved until tenting is corrected.