INSP-Final Inspection | 6/22/2020 | 6/22/2020 | 6/22/2020 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, final fire sprinkler inspection is complete.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Final Inspection | 6/17/2020 | 6/18/2020 | 6/18/2020 | P | FAIL |
Jim Page
|
|
|
Replace 155 degree heads in washer/dryer closets to the 175 degree heads as shown on city approved drawings. Relocate overspaced head as discussed.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Supply line flush | 5/29/2020 | 6/1/2020 | 5/29/2020 | A | CANC |
Jim Page
|
|
|
Scheduled for 9am with Stacy at Suez. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
INSP-Sprinkler Rough-in/Hydro | 5/27/2020 | 5/27/2020 | 5/27/2020 | P | CANC |
Jim Page
|
|
|
Underground hydro. Ready any time, call James before heading out. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
INSP-Sprinkler Rough-in/Hydro | 4/8/2020 | 4/9/2020 | 4/9/2020 | P | DONE |
Jim Page
|
|
|
Hydrostaic test for overhead fire sprinkler piping has been witnessed, no pressure loss observed at riser provided gauge.
Hydrostatic test Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 3/11/2020 | 3/12/2020 | 3/12/2020 | A | PASS |
Jim Page
|
|
|
All tenting in place at time of inspection, cover is approved, cover sticker placed on window.
Tenting inspection, call James with any concerns, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 3/11/2020 | 3/11/2020 | 3/11/2020 | P | PART |
Jim Page
|
|
|
Rough in inspection complete, piping between conditioned spaces approved for cover. No tenting installed at time of inspection, piping requiring tenting not approved for cover.
Tenting and overhead rough, call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|