Final | 2/19/2020 | 2/20/2020 | 2/20/2020 | A | PASS |
Tom Saunders
|
|
|
Corbin Metcalf ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg...corrections made...ok to final
|
Final | 2/17/2020 | 2/18/2020 | 2/18/2020 | A | FAIL |
Tom Saunders
|
|
|
Corbin Metcalf ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg... 1) exterior outlet needs heavy duty inuse cover..406.9(A)
2) panel in shed needs main breaker installed...discussed at rough in...abillity to have more then 6 swipes of hand...225.33 3) exterior lights need rated for damp location...keylesses not rated
|
Final | 2/12/2020 | 2/13/2020 | 2/13/2020 | A | FAIL |
Eric Story
|
|
|
Justin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg 1) Tamper resistant receptacles required in shop 2) WR needed for outdoor recept 3) service recept required for mini split unit 4) GFCI trips free in shed
|
Permanent Service | 2/3/2020 | 2/3/2020 | 2/3/2020 | P | PASS |
Tom Saunders
|
|
|
Corbin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg...p/s u/g reconnect ok
|
Electrical Rough-In | 1/6/2020 | 1/6/2020 | 1/6/2020 | P | PASS |
Tom Saunders
|
|
|
Corbin Metcalf ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg... out building rough-in ok to cover...panel needs addressed-main breaker or panel with no more than 6 swipes of hand
|
Electrical Rough-In | 12/19/2019 | 12/19/2019 | 12/19/2019 | P | PASS |
Tom Saunders
|
|
|
Justin Metcalf ###-#### Rough in inspection for addition. Phone #: ###-#### Inspection requested via web by Samatha Solberg...rough-in of addition complete...outbuilding scheduled later once rough-in done
|
Electrical Rough-In | 12/10/2019 | 12/10/2019 | 12/10/2019 | P | PASS |
Tom Saunders
|
|
|
Partial wall rough in inspection. The existing wall will have to be called in for a separate inspection. Call Justin Metcalf for details ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg...ok to cover exterior walls only of new addition...ceiling and removed wall area rough scheduled later time
|
Electrical Rough-In | 12/5/2019 | 12/6/2019 | 12/6/2019 | A | PASS |
Tom Saunders
|
|
|
Justin Metcalf ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg...underground to shed ok to cover
|
Electrical Rough-In | 12/3/2019 | 12/4/2019 | 12/4/2019 | A | NR |
Tom Saunders
|
|
|
Justin Metcalf ###-#### This inspection is just for the underground conduit ran from the house to the shed. Phone #: ###-#### Inspection requested via web by Samatha Solberg...trench not complete and pipe install not complete
|
Issue PAID IN FULL permit | | | 12/3/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/3/2019 | | DONE |
|
|
|
This permit was created on the web by Samatha Solberg
|