Information based on query as of Monday, May 20, 2024.
Permit Information
Permit NumberFIR18-00956
StatusFinaled
Name WEBSTER FIRE PROTECTION
Site Address 3290 E BARBER VALLEY DR
Project NameVeranda at Barber Station
Customer Number 
ePlanReviewYes
Description
Modification to Existing Fire Alarm Plan. Add temperature monitoring in previously unheated dog house spaces for sprinkler minimum temperature protection. This work is associated with building permit BLD18-00230 and project PRJ18-03042.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/13/20192/14/20192/14/2019APASS
DetailsJim Page
Overspaced smoke detection has been corrected, final fire alarm inspection complete.

Phone #: ###-#### Inspection requested via web by Ken Webster
Miscellaneous action  2/12/2019 DONE
As built drawings reviewed and approved.
INSP-Final Inspection1/30/20191/30/20191/30/2019PPART
DetailsJim Page
Final inspection for temperature sensors in dog house/over builds complete.
INSP-Final Inspection1/29/20191/30/20191/30/2019PPART
DetailsJim Page
Fire alarm inspection for initiating devices and notification complete, a follow up inspection will be required to verify possible spacing issues with smoke detector placement, as of these notes a 30 day TCO is authorized by Ron Johnson for occupancy. If smoke detectors space correctly on the install then the fire alarm permit can be finaled but as mentioned, a follow up inspection will be required.

Phone #: ###-#### Inspection requested via web by Ken Webster
CHANGE STATUS TO (ISS)  1/30/2019 DONE
per Jim Page-change status to ISS was finaled by mistake
INSP-Final Inspection1/28/20191/29/20191/29/2019ACANC
DetailsTroy Cobbley
The project related permit for the means of communication was not scheduled/inspected/passed. No inspection performed.

Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Final Inspection1/24/20191/25/20191/25/2019APART
DetailsJim Page
Fire alarm notification inspection complete, sprinkler monitoring complete, still need to test hood monitoring, in duct detectors and temperature sensors.

Phone #: ###-#### Inspection requested via web by Ken Webster
INSP-Conference1/15/20191/18/20191/18/2019ADONE
DetailsJim Page
Fire conference complete.

Phone #: ###-#### Inspection requested via web by Ken Webster
Issue and Print Permit  12/28/2018 DONE
Plan assigned to (Lee)12/27/2018 12/27/2018 DONE
DetailsLee G Meredith
Telephone call  12/27/2018 DONE
Purpose of the temperature monitoring was not indicated in the application. In a phone call to Ken, he explained that this was required by Jim Page and Ron Johnson to minimize the possibility of freezing temperatures in the previously unheated spaces that are protected by wet sprinklers. I called Jim to verify Kens explanation. Jim confirmed the requirement.
1st review completed  12/27/2018 PASS
Alarm Plan Check12/27/2018 12/27/2018 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  12/27/2018 DONE
Review passed. No review comments provided.
Permit Ready to Issue  12/27/2018 DONE
met
Application received  12/20/2018 DONE
Application submitted via PDS Online on Dec 20 2018 2:48PM