Permit Information
Permit NumberBLD18-02407
StatusFinaled
Name TITAN TECHNOLOGIES INC
Site Address 1023 S CURTIS RD
Project NameBoise Love Inc Storage
Customer Number 
ePlanReviewYes
Description
(BOISE LOVE INC.) This building does not have a fire sprinkler system. Special inspections for concrete required per attached Form 310. To construct a new free standing 30'x65' storage building that totals 1,950 sq. ft. Work is to include concrete piers & footings, concrete foundation stem walls, concrete slab on grade, pre-engineered metal building frame, metal wall panels, metal roof panels, three sectional overhead doors, and a double side-hinged swinging exit door. This building will not be conditioned or insulated. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. This building is only approved for occupancy and use during the daytime since no mean of egress illumination is being provided. See letter submitted with this case by the applicant stating the storage building will only be accessed in day-light hours. Racking that exceeds 8 ft. in height requires a separate Building Permit. **JHB**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final7/24/20207/27/20207/27/2020APASS
DetailsMike Jordan
SCREENED // Kimbra Phone #: ###-####
DOC - Permit Finaled7/27/20207/27/20207/27/2020PPASS
DetailsMike Jordan
FIRE-Final Inspection7/23/20207/23/20207/23/2020PPASS
DetailsTroy Cobbley
Life safety passed.

call for access- Kimbra *screened* Phone #: ###-####
FIRE-Conference7/21/20207/21/20207/21/2020PDONE
DetailsTroy Cobbley
We went over life safety requirements.

Kimbra ###-####
BLD-Final7/17/20207/17/20207/17/2020PCANC
DetailsMike Jordan
Screened-Cliff Phone #: ###-####.
BLD-Conference12/2/201912/2/201912/2/2019PPASS
DetailsMike Jordan
aDAM Phone #: ###-####
BLD-Wall Bracing11/27/201911/27/201911/27/2019PPASS
DetailsMike Jordan
FIRE WALL // Adam Phone #: ###-####
BLD-Conference11/22/201911/22/201911/22/2019PDONE
DetailsMike Jordan
Adam Phone #: ###-####
BLD-Framing/Rough-in10/14/201910/15/201910/15/2019PPASS
DetailsMike Jordan
Kimbra Phone #: ###-####. Observed install of 3 1/2 inch all thread rods epoxied into concrete footing. All holes were blown clean and brushed. All work was done per the engineers RFI and manufactures instructions.
BLD-Conference9/18/20199/19/20199/19/2019ACANC
DetailsMike Jordan
BLD-Conference9/17/20199/18/20199/18/2019PDONE
DetailsMike Jordan
Call ahead 20 minutes - foundation poured in wrong spot - need advice // Kimbra Phone #: ###-####
BLD-Concrete8/20/20198/22/20198/22/2019PPASS
DetailsMike Jordan
after 2pm // Doug Phone #: ###-####. Welded wire mesh for slab on grade ok.
BLD-Concrete8/5/20198/6/20198/6/2019PPASS
DetailsMike Jordan
rebar- after 2:30pm please- Doug Phone #: ###-####. Ties replaced. ok.
BLD-Foundation8/6/20198/6/20198/6/2019PPASS
DetailsMike Jordan
rebar- after 2:30pm please- Doug Phone #: ###-####
BLD-Footing7/19/20197/23/20197/23/2019PCANC
DetailsMike Jordan
rebar - after 2 pm // Doug Phone #: ###-####
BLD-Foundation7/23/20197/23/20197/23/2019PFAIL
DetailsMike Jordan
rebar - after 2 pm // Doug Phone #: ###-####. Hairpins not installed around anchor bolts. #3 ties do not conform to ACI standards. Ties are not continous and missing hooks. Contractor noted that this rebar was donated. Noted to contractor that the ties still need to meet ACI.
BLD-Foundation7/10/20197/10/20197/10/2019PPASS
DetailsMike Jordan
Doug - after 2pm Phone #: ###-####. Footings ok. City approved plans on site. Noted that building pad appears to be built up 3/4 inch road mix. Footings appear to be on undisturb native soils. Called and have left message with owner, Micheal Moore, to call me back to discuss pad and if compaction testing was completed.
BLD-Concrete7/1/20197/3/20197/3/2019PNR
DetailsMike Jordan
late afternoon - rebar // Doug Phone #: ###-####. Needs to provide the city set of approved plans. Also noted to concrete contractor that special inspection is required.