Permit Information
Permit NumberBLD19-01444
StatusFinaled
Name VANTAGE HOMES
Site Address 8642 W OVERLAND RD
Project NameMattress Today Boise
Customer Number 
ePlanReviewYes
Description
(MATTRESS TODAY BOISE) The fire sprinkler system is used for building area increase and for fire area. To remodel and existing tenant space that is 1,355 square foot retail mattress store with an accessory storage area. Work is to include a single user restroom accessible to the disabled and interior finishes. The work is required to comply with the approved drawings, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. Separate fire sprinkler permits shall be obtained prior to beginning any modification or installation work on such system. **JHB**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final7/2/20197/3/20197/3/2019PPASS
DetailsMike Jordan
Access to unit via lockbox located in Mailbox near door. Code is 2805. Please call Chad @208.994.2805 prior to inspection. Phone #: ###-#### Inspection requested via web by Chad Aland. All issues have been resolved. ok for perm occ.
BLD-Final6/28/20196/28/20196/28/2019PFAIL
DetailsMike Jordan
Key to unit in lock box located in mailbox near door. Code is 2805 Phone #: ###-#### Inspection requested via web by Chad Aland. A mech. permit is required for the ventalation fan that has been installed. noted no framing inspection has been conducted on new framing for restroom. Miiror and grab bars mounted in correctly to walls. A correction notice has been issued.
FIRE-Final Inspection6/26/20196/27/20196/27/2019PPASS
DetailsJim Page
Previously noted items have been corrected. Fire sprinkler inspection is complete, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work comlpete.

Access is through a lock box located in the mailbox beside the door. Code is 2805 Phone #: ###-#### Inspection requested via web by Chad Aland
FIRE-Final Inspection6/22/20196/24/20196/24/2019AFAIL
DetailsJim Page
Provide addressing for tenant space. Provide fire extinguisher with a current inspection tag, cuurent inspection on extinguisher was completed in 2009. Exit sign/emergency lighting needs serviced, all exit/emergency lighting did not operate when A/C power was isolated. Provide sign at front door reading "Door to remain unlocked while building is occupied", signage currently reads "Door to remain unlocked during business hours". Rear exit is partially blocked by mattress storage.

Fire, Life and Safety inspection to be completed at the same time as fire sprinkler if possible-please call chad for access 208.994.2805 Phone #: ###-#### Inspection requested via web by Chad Aland
FIRE-Final Inspection6/17/20196/18/20196/18/2019AFAIL
DetailsTroy Cobbley
Storage Room sprinkler heads are overspaced for Ordinary Hazard, add sprinkler coverage for new restroom, tag and mount the fire extinguisher, test the exit signs/emergency lights, provide annual inspection for the sprinkler system

Please Call Chad for access to building-he will meet on site. Phone #: ###-#### Inspection requested via web by Chad Aland