Permit Information
Permit NumberELE19-03174
StatusFinaled
Name MOUNTAIN POWER ELECT
Site Address 150 N 8TH ST Unit: 200
Project Name 
Customer Number19-031
ePlanReviewNo
Description
New: Provide the electrical work associated with the Tupelo Honey TI.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/5/201911/6/201911/6/2019PPASS
DetailsRock A. Hudson
Please call Mike Phone #: ###-#### Inspection requested via web by Kevin Perez
Final ok
Final10/31/201911/1/201911/1/2019APART
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
TCO for training purposes only. Exterior egress lighting not complete on balcony. TCO ok
Final10/30/201910/31/201910/31/2019PFAIL
DetailsRock A. Hudson
Inspect for TCO. Mike Hastings ###-#### Phone #: ###-#### Inspection requested via web by Jeremy Cloud
210.8(B)- All receptacles located in a commercial kitchen up to 50 amp single phase and 100 amp 3 phase 150 volts or less to ground shall have GFCI protection. 2-pole 20 for small oven.
408.4- Circuit directory shall be placed in each panel.
422.30- A disconnecting means shall be provided for all hard wired appliances. 9 ish needed.
Electrical Rough-In10/25/201910/25/201910/25/2019PPASS
DetailsRock A. Hudson
Inspect ceiling for cover Mike Hastings ###-#### Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Grid complete rough in ok cover
Electrical Rough-In10/23/201910/24/201910/24/2019PPART
DetailsRock A. Hudson
Inspect grid ceilings for cover. Mike Hastings ###-#### Phone #: ###-#### Inspection requested via web by Jeremy Cloud 400.12- Flexible cords shall not be installed above ceiling grid. Remove extension cords for emp lighting.
Grid boarders only rough in ok
Electrical Rough-In9/19/20199/19/20199/19/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
All full height walls complete, wall rough in ok cover
Conference9/16/20199/16/20199/16/2019PDONE
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Discussed if a GFCI device is allowed behind an appliance with wheels. If appliance is easily moved GFCI device is ok behind appliance.
Also width of work space required for a panel board. As per 110.26(A)(2) a minimum of 30" or width of equipment is required. Lighting control panel mounted of left wall does not affect work space width of panel in question.
Electrical Rough-In9/10/20199/10/20199/10/2019PPASS
DetailsRock A. Hudson
Please call Mike Phone #: ###-#### Inspection requested via web by Kevin Perez
Back kitchen wall, office and closet to right walls and hardlid, S.W. corner lid rough in ok cover.
Electrical Rough-In9/5/20199/6/20199/6/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Back kitchen wall changing. Walls and soffits and bathrooms as noted on contractor print rough in ok cover.
Electrical Rough-In8/27/20198/27/20198/27/2019PPART
DetailsRock A. Hudson
Please call Mike Inspection requested via web by Kevin Perez
Exterior of outer wall only, and more kitchen walls as noted on contractor print rough in ok cover.
Electrical Rough-In8/23/20198/26/20198/26/2019APART
DetailsRock A. Hudson
Please call Mike H. Phone #: ###-#### Inspection requested via web by Kevin Perez Discussed if equipment grounding conductors were required to switch bank where box fill tight. Electrical engineer has drawn in equipment grounding conductors on print so will be required to be installed.
kitchen walls and salad wall as noted on contractor print rough in ok cover