INSP-Final Inspection | 7/29/2019 | 7/29/2019 | 7/29/2019 | P | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, final fire sprinkler inspection for area of work complete.
Please call Clarence Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
INSP-Final Inspection | 7/2/2019 | 7/3/2019 | 7/3/2019 | A | FAIL |
Jim Page
|
|
|
Notated city approved drawings areas that need to be corrected. Submit plan modification to have sway bracing removed from city approved drawings.
Please call Dillion Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
INSP-Final Inspection | 6/25/2019 | 6/25/2019 | 6/25/2019 | P | CANC |
Jim Page
|
|
|
No inspection performed for this permit due to time constraints, this request is cancelled per conversation with point of contact.
Please call Dillion Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
INSP-Final Inspection | 6/18/2019 | 6/19/2019 | 6/19/2019 | A | CANC |
Jim Page
|
|
|
Inspection request cancelled per conversation with point of contact, city approved drawings/small documents could not be located, city approved drawings and small documents are required for inspection.
Dillion Phone #: ###-####
|
INSP-Final Inspection | 4/12/2019 | 4/12/2019 | 4/12/2019 | P | CANC |
Jim Page
|
|
|
Per conversation with my supervisor, Adele Schaffeld-Griffin, notes entered reading "Final fire sprinkler sign off of inspections for this permit will be completed at the same time as the life safety inspection is completed under the building permit." Please coordination with the general contractor to schedule the final inspections. Onsite inspection request for today will need to be rescheduled until coordinated inspections for the life safety can be scheduled.
Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
INSP-Final Inspection | 7/30/2018 | 7/31/2018 | 7/31/2018 | P | PART |
Jim Page
|
|
|
Final fire sprinkler inspection complete, fire sprinkler permit will remain in issued status until project is complete due to possible obstructions needing coverage.
Chris Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 6/15/2018 | 6/18/2018 | 6/18/2018 | P | DONE |
Jim Page
|
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge.
Chris Phone #: ###-####
|