Information based on query as of Thursday, May 9, 2024.
Permit Information
Permit NumberFIR18-00644
StatusFinaled
Name PROTEX
Site Address 3722 W ANDERSON ST
Project NameTaft Elementary Update
Customer Number 
ePlanReviewYes
Description
Upgrade existing fire alarm control panel to a voice system. This work is associated with building permit BLD18-00945.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/29/20193/29/20193/29/2019PPASS
DetailsJim Page
Previously noted items have been corrected, final fire alarm inspection complete.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection3/27/20193/28/20193/28/2019AFAIL
DetailsJim Page
Fire panel that was installed does not match what was submitted. Communicator showing trouble at time of inspection. In-duct detectors report to panel as a trouble with no RTU shutdown on both HVAC units. Provide a different type of notification appliance in horn location, horns do not sync with speaker strobes as well as overpowering the sound of the surrounding speaker strobes. Signals were not verified at time of inspection.

Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection3/22/20193/25/20193/25/2019PFAIL
DetailsJim Page
Two speaker strobes in gym area are blocked by ducting. Need to test in-ducts for HVAC unit shutdown. Wire hanging out of communicator to fire panel.



Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection3/14/20193/14/20193/14/2019PPART
DetailsJim Page
Fire alarm audible device now meets the required NFPA 72 sound level requirements in the new kitchen area..

Final is for Kitchen Only. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection3/12/20193/13/20193/13/2019PFAIL
DetailsJim Page
Audible level was not met in kitchen area.

This final is only for the kitchen portion. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten