INSP-Final Inspection | 3/29/2019 | 3/29/2019 | 3/29/2019 | P | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, final fire alarm inspection complete.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 3/27/2019 | 3/28/2019 | 3/28/2019 | A | FAIL |
Jim Page
|
|
|
Fire panel that was installed does not match what was submitted. Communicator showing trouble at time of inspection. In-duct detectors report to panel as a trouble with no RTU shutdown on both HVAC units. Provide a different type of notification appliance in horn location, horns do not sync with speaker strobes as well as overpowering the sound of the surrounding speaker strobes. Signals were not verified at time of inspection.
Contact is Dan. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 3/22/2019 | 3/25/2019 | 3/25/2019 | P | FAIL |
Jim Page
|
|
|
Two speaker strobes in gym area are blocked by ducting. Need to test in-ducts for HVAC unit shutdown. Wire hanging out of communicator to fire panel.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 3/14/2019 | 3/14/2019 | 3/14/2019 | P | PART |
Jim Page
|
|
|
Fire alarm audible device now meets the required NFPA 72 sound level requirements in the new kitchen area..
Final is for Kitchen Only. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
INSP-Final Inspection | 3/12/2019 | 3/13/2019 | 3/13/2019 | P | FAIL |
Jim Page
|
|
|
Audible level was not met in kitchen area.
This final is only for the kitchen portion. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|