Permit Information
Permit NumberFIR19-00060
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION SE
Site Address 9345 W CORY LN
Project NameAventura West Bldg C
Customer Number 
ePlanReviewYes
Description
Install new wet pipe fire sprinkler system beginning at one foot above the floor of the mechanical room
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/29/20198/29/20198/29/2019PPASS
DetailsTroy Cobbley
Permit finaled. Nick Phone #: ###-####
INSP-Final Inspection8/21/20198/22/20198/22/2019PFAIL
DetailsTroy Cobbley
Need insulation and cover inspection for the piping in the storage closets.


Nick Phone #: ###-#### (change inspection to this afternoon, 8-22, per kristin dolan)
INSP-Final Inspection8/12/20198/12/20198/12/2019PFAIL
DetailsJim Page
Last inspection request was on 21MAY2019 for cover, notes indicate cover was not approved due too no tenting being installed, cover material has been installed and according to the last entry, cover was not approved.

Kristin Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro5/21/20195/21/20195/21/2019PFAIL
DetailsTroy Cobbley
A tenting inspection was requested but no tenting has been installed.

Nick Phone #: ###-####
INSP-Sprinkler Rough-in5/6/20195/6/20195/6/2019PPART
DetailsTroy Cobbley
Rough-in passed but piping can not be covered until a tenting inspection has passed.

Nick Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro4/29/20194/30/20194/30/2019APASS
DetailsTroy Cobbley
The overhead hydro test witnessed with no visible loss on the guage. Todd Phone #: ###-####
INSP-Supply line flush4/25/20194/26/20194/26/2019APASS
DetailsTroy Cobbley
Underground flush witnessed


Nick Phone #: ###-####