Permit Information
Permit NumberFIR19-00103
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 11740 W KING ST
Project NameFairview Apartments 8-Plex #D2
Customer Number 
ePlanReviewYes
Description
Shilo will install a new fire sprinkler system into the new 8-Plex per NFPA 13R, 2016, and the City of Boise. Underground installed under FIR19-00032
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/3/20196/4/20196/4/2019APASS
DetailsTroy Cobbley
Permit finaled

Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection5/28/20195/29/20195/29/2019AFAIL
DetailsTroy Cobbley
Permit can be finaled when the test documents have been provided as discussed. Also the underground permit needs to be scheduled for a final inspection.

Gabe Phone #: ###-####
INSP-Final Inspection5/24/20195/28/20195/28/2019ACANC
DetailsTroy Cobbley
not ready per Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro5/21/20195/22/20195/22/2019APASS
DetailsTroy Cobbley
Overhead hydro tested witnessed with no visible loss on the guage.
INSP-Sprinkler Rough-in/Hydro5/14/20195/15/20195/15/2019AFAIL
DetailsTroy Cobbley
Overhead hydro tests failed again do to visible loss on the guages. A re-inspection fee has been applied.
INSP-Sprinkler Rough-in/Hydro5/13/20195/14/20195/14/2019AFAIL
DetailsTroy Cobbley
Overhead hydro tests failed due to visible loss on both guages. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro5/10/20195/13/20195/13/2019AFAIL
DetailsTroy Cobbley
Overhead hydro failed due to visible loss of pressure on the guages.

Gabe Garduno is the contact. This is for a hydro only inspection. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in3/7/20193/8/20193/8/2019APASS
DetailsTroy Cobbley
Rough-in passed. Tenting passed. Piping can be covered. Sprinkler protection for the second floor outside storage rooms may need to be modified. As-builts are needed showing the new sidewall coverage under the front entry gables.Rirers are not built yet.

Gabe Garduno is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in3/5/20193/5/20193/5/2019PFAIL
DetailsTroy Cobbley
Project is not ready yet for a complete rough-in inspection due to many missing heads in closets, balcony/storage closets, breezwway coverage, missing insulation for tenting. Also I noted that the breezeway has a soffit that may obstruct the sidewall sprinkler coverage.

Gabe Garduno is the contact. Thank you for all the help you give! Phone #: ###-#### Inspection requested via web by Stan Beus