Information based on query as of Thursday, May 2, 2024.
Permit Information
Permit NumberFIR19-00770
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 11457 W TIOGA CT
Project NameDegitz Residence
Customer Number 
ePlanReviewYes
Description
Shilo will install a new fire sprinkler system into the new Degitz Residence per NFPA 13D, 2016, and the City of Boise.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/25/20203/26/20203/26/2020APASS
DetailsTroy Cobbley
Permit finaled. Water meter changed per Suez. See the email attached in Documents for Boise Fire agreement on revised water flow.

Cam Phone #: ###-####
INSP-Final Inspection2/27/20202/28/20202/28/2020AFAIL
DetailsJim Page
Premit is under review as of these notes, final inspection cannot be performed until permit is back into issued status. According to SUEZ, water meter is a 5/8 water meter, not 1 inch as show on city approved documents.

Jon Beazer is the contact for this final inspection. Thank you for your help. Have a good day. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Final Inspection2/26/20202/27/20202/27/2020PCANC
DetailsTroy Cobbley
Cole Bierman is the contact for this final inspection. He is hoping for a PM appointment. He is needing an hour notice if possible as he will be working at another job site. Thank you for your help. Have a nice day. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Final Inspection2/26/20202/27/20202/27/2020ACANC
DetailsTroy Cobbley
Cole Bierman is the contact. Thanks for all you do! Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Final Inspection2/25/20202/26/20202/26/2020AFAIL
DetailsTroy Cobbley
Possible plan mods are needed due to the length of the actual underground supply, two houses fed off a single 1" supply and a 5/8" water meter. Repair the outside alarm bell and provide signage as discussed.
Cole will be the contact. Please give him an hours notice to meet you there. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in/Hydro2/25/20202/25/20202/25/2020PPASS
DetailsTroy Cobbley
Overhead hydro witnessed with no pressure loss.

Cole will be the contact. Please give him an hours notice to meet you there. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in12/6/201912/6/201912/6/2019PPASS
DetailsTroy Cobbley
Tenting passed. Piping can be covered.
INSP-Sprinkler Rough-in12/5/201912/5/201912/5/2019PFAIL
DetailsTroy Cobbley
Tenting needs repaired in the second floor bedroom and I need access to the area above the ceiling in the garage room.
INSP-Sprinkler Rough-in11/11/201911/12/201911/12/2019APASS
DetailsTroy Cobbley
Rough-in passed. Piping can not be covered until a tenting inspection has been passed. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus