INSP-Final | 8/16/2019 | 8/20/2019 | 8/20/2019 | A | PASS |
Troy Cobbley
|
|
|
*** Flow switch timed at 40 seconds*** Call prior to going Phone #: 2084212181 >> Inspection requested via mobile web by Brian
|
INSP-Final | 7/24/2019 | 7/30/2019 | 7/30/2019 | A | PASS |
Troy Cobbley
|
|
|
**Hydro passed at well pump pressure. Bell needs to be mounted in relocated location I marked on approved plans, Not at the location submitted. Some patching needs to be done around escutcheons, and all painting needs to be completed before final inspection. MAS***
Call prior to going Phone #: 2084212181 >> Inspection requested via mobile web by Brian
|
INSP-Final | 7/15/2019 | 7/17/2019 | 7/17/2019 | P | CANC |
Troy Cobbley
|
|
|
Cancel per contractor. Water connection not done yet.
Call prior to going Phone #: 2084212181 >> Inspection requested via mobile web by Brian Rumple
|
INSP-Sprinkler Rough-in | 2/4/2019 | 2/4/2019 | 2/4/2019 | P | PASS |
Troy Cobbley
|
|
|
The remaining sprinkler piping is ok for cover.
Call prior to going Phone #: 2086956553 >> Inspection requested via mobile web by John Venche
|
INSP-Sprinkler Rough-in | 1/28/2019 | 1/28/2019 | 1/28/2019 | P | PART |
Troy Cobbley
|
|
|
Rough-in passed. All piping, except as marked on the approved plans, can be covered. Tenting passed. Builder is going to add insulation in the garage area.
Call prior to going Phone #: 2086956553 >> Inspection requested via mobile web by John
|
INSP-Sprinkler Rough-in | 1/22/2019 | 1/22/2019 | 1/22/2019 | P | CANC |
Troy Cobbley
|
|
|
Call prior to going Phone #: 2086956553 >> Inspection requested via mobile web by John Inspection cancelled via mobile web on Tuesday, January 22, 2019.
|
INSP-Sprinkler Rough-in | 12/18/2018 | 12/20/2018 | 12/20/2018 | P | FAIL |
Troy Cobbley
|
|
|
Was only able to do a partial inspection due to numerous pipe routing changes. I also noted that alot of additional fittings have been added that might affect the hydraulic calculations. I also noted tenting issues in the garage area. Contractor will need to contact plan review and see if as-builts or plan modifications are required. This will need to be done prior to another inspection being scheduled. Per the general contractor blow-in insulation will be used above the ceilings in the garage.
Call prior to going Phone #: 2084212181 >> Inspection requested via mobile web by Brian
|