INSP-Final Inspection | 8/26/2015 | 8/27/2015 | 8/27/2015 | A | PASS |
Thomas Walsh
|
|
|
Final inspection/test of fire alarm system for Tower 4 area - all floors, including elevator 2 recal/alt. recall functions, area SD for elevator lobbies, unit smoke detection, etc. All devices tested satisfactorily.. System is being monitored off site - correct address was confirmed.
|
INSP-Final Inspection | 8/27/2015 | 8/27/2015 | 8/27/2015 | P | PASS |
Thomas Walsh
|
|
|
Final inspection/test of fire alarm system for Tower 4 - all floors, including elevator# 2 recall/alt. recall functions, SDs for elevator lobbies, unit SDs, etc. All devices tested satisfactorily. Offsite monitoring and correct address confirmed.
|
INSP-Final Inspection | 8/26/2015 | 8/27/2015 | 8/26/2015 | A | CANC |
Jim Page
|
|
|
>> Inspection requested via mobile web by Nathan Proce Inspection cancelled via mobile web on Wednesday, August 26, 2015.
|
INSP-Alarm Testing | 8/19/2015 | 8/20/2015 | 8/20/2015 | P | PART |
Thomas Walsh
|
|
|
Fire alarm inspection/test for Towers 3 & 4 corridors only - no unit inspections were conducted. Test of MPs. SDs for FSDs, SDs for DH, etc, just within the corridors. Elevator for Tower 4 not ready for test. All devices tested satisfactorily within the corridors, and checked many units under general alarm.
|
INSP-Alarm Testing | 8/18/2015 | 8/18/2015 | 8/18/2015 | P | PART |
Thomas Walsh
|
|
|
Fire alarm testing is completed for the building up to and including the 4th floor (5th floor is not completed yet). All fire sprinkler systems are in service and all fire alarm devices are also in service. I did find some units on the 4th floor that still had their protective cap on their room SDs, and these should be removed before releasing the unit to the resident. The FACP is fully monitored and is being put into service at the end of each day.
|
INSP-Final Inspection | 8/13/2015 | 8/14/2015 | 8/14/2015 | A | PART |
Thomas Walsh
|
|
|
Fire alarm system testing of portions of Tower 3 5th floor (units 514 &515)) to add to TCO. Alarms for these units, and area of the corridor serving these units, are OK
|
INSP-Alarm Testing | 7/9/2015 | 7/10/2015 | 7/10/2015 | A | PART |
Thomas Walsh
|
|
|
Tower 2 fire alarm testing, including elevator # 1 recall functions, MP, SDs, unit smoke detection, SFDs, general notification and rooftop HVAC units serving tower 2. All devices staisfactorily. GC is requesting TCO of Tower 1 and 2 (all floors). Fire alarm system has been tested and is functonal for these areas.
|
INSP-Alarm Testing | 7/1/2015 | 7/2/2015 | 7/2/2015 | A | PART |
Thomas Walsh
|
|
|
Testing of fire alarm system for the 5th floor (Tower 1) and the rooftop HVAC units for shutdown. Also confirmed test of fire sprinkler dry pipe systems with FACP. NOTE: Many of the descriptions and locations of the various devices will have to be updated to clarify the device locations and purpose/function. Will retest some of the devices alraedy tested to confirm proper addressing. NOTE: Tower 3 and Tower 4 areas - all floors not tested todate.
|
INSP-Alarm Testing | 6/30/2015 | 7/1/2015 | 7/1/2015 | A | PART |
Thomas Walsh
|
|
|
Partial fire alarm test for the entire apartment building, including all fire sprinkler interface devices, including waterflows, tampers, etc., and then all fire alarm devices, including SDs, FSDs, MPs, elevator recall functions (Elevator # 1 only). More testing is required to complete the process, mostly on the upper floors. NOTE: Fire alarm installation work is still on-going in Towers 3 & 4, while they are looking for partial TCO for Towers 1 and possible 2. Therfore, this is just a partial test of the system that is completed today.
|
Permit Ready to Issue | | | 12/19/2014 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/19/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/19/2014 | | 12/19/2014 | | DONE |
Kristal Soland
|
|
|
|
Plan resubmittals received | | | 12/18/2014 | | DONE |
|
|
|
|
1st review completed | | | 12/18/2014 | | PASS |
|
|
|
|
Alarm Plan Check | 12/18/2014 | | 12/18/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 12/18/2014 | | DONE |
|
|
|
Plans approved with review comments. Projectdox updated.
|
Telephone call | | | 12/16/2014 | | DONE |
|
|
|
Mike, of Eidam & Associates called regarding my review comment to move a couple of manual alarm stations from the outside to the inside to minimize false activation of alarms. He agreed and will direct Simplex to make the change.
|
Plan assigned to (Lee) | 12/8/2014 | | 12/8/2014 | | DONE |
Lee G Meredith
|
|
|
|
Miscellaneous action | | | 12/8/2014 | | DONE |
|
|
|
Design failed prescreen review. Applicant was emailed a list of corrections and deficiencies.
|
Application received | | | 12/3/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Dec 3 2014 4:12PM
|