INSP-Sprinkler Rough-in | 8/11/2020 | 8/11/2020 | 8/11/2020 | A | FAIL |
Jim Page
|
|
|
Provide auxiliary drain for head under rool up door. Add two uprights in discussed locations due top block head from duct work. Provide correct size fittings for exterior pipe per NFPA13 6.4.7. Add sway braing in areas marked on city approved drawings.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Supply line flush | 7/14/2020 | 7/16/2020 | 7/16/2020 | A | DONE |
Jim Page
|
|
|
Main line flush is complete.
Scheduled for 8:30am with Jim Page and Stacy with SUEZ. Call James if anything comes up. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Supply line flush | 6/23/2020 | 6/24/2020 | 6/24/2020 | A | NR |
Jim Page
|
|
|
Flush was not performed due too the amount of wash-out that would happen from the jobsite to the public way, will area cleaned up for no wash out or provide means too flush without wash-out.
Coordinated with SUEZ and Jim for 10:30am, Gary or James will be on site ready to flush. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 1/15/2020 | 1/16/2020 | 1/16/2020 | A | PASS |
Jim Page
|
|
|
Remaining pipe for tie in inspection complete, approved for cover.
Call James before heading out, he will make sure the blanket is off and pipe is visible. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in | 1/14/2020 | 1/15/2020 | 1/15/2020 | A | CANC |
Jim Page
|
|
|
Piping was covered in snow and concrete blanket, piping/fitting could not be seen in the trench, inspection will need to be rescheduled when pipe is visible, this request is cancelled.
Underground rough to cover. Call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
INSP-Sprinkler Rough-in/Hydro | 12/26/2019 | 12/27/2019 | 12/27/2019 | P | PASS |
Jim Page
|
|
|
Rough to cover inspection for underground supply complete, approved for cover.
Underground fire line. Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
Issue and Print Permit | | | 12/18/2019 | | DONE |
|
|
|
|
Plan assigned to (Stumbaugh) | 12/5/2019 | | 12/5/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Intake Approval | | | 12/5/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 12/5/2019 | | 12/5/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
1st review completed | | | 12/5/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/5/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Permit Ready to Issue | | | 12/5/2019 | | DONE |
|
|
|
met
|
Intake Approval | | | 12/4/2019 | | FAIL |
Mark Stumbaugh
|
|
|
|
Application received | | | 12/3/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Dec 3 2019 3:05PM
|