Permit Information
Permit NumberFIR14-00531
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1011 S LA POINTE ST
Project NameBoise Heights
Customer Number 
ePlanReviewYes
Description
This submittal is for the portion of the Boise Heights project above the parking garage. This is a wood framed 4 story residential building. The system is designed per NFPA 13 using a wet pipe sprinkler system throughout. There is a semiautomatic wet class I standpipe with hose valve coverage on the roof and at the intermediate stair landings and in the garage at the floor level.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/26/20158/27/20158/27/2015APASS
DetailsThomas Walsh
Final inspection and signoff for this permit.
INSP-Final Inspection8/20/20158/21/20158/21/2015APART
DetailsThomas Walsh
Final inspection for Tower 3 section of the building for all floors. Noted a couple of sprinklers that needed finish trim installed, and these were corrected before end of inspection. Tower 3 final passed.
INSP-Sprinkler Rough-in/Hydro8/14/20158/17/20158/17/2015PPART
DetailsThomas Walsh
Hydrotest of new standpipe added in Tower 4 - 200 psi @ 2 hours - PASSED
INSP-Final Inspection8/14/20158/14/20158/14/2015PPART
DetailsThomas Walsh
Inspection of fire sprinklers for units 514 and 515 to add to TCO for the 5th floor of Tower 3. - OK to occupy these units.
INSP-Alarm Testing7/9/20157/10/20157/10/2015APART
DetailsThomas Walsh
Inspection of A/S for Towers 1 # 2 sections of the building - all floors. TCO is requested for this section of the building, so this was a pre-final inspection for the units in this area of the building. A few escutcheon were missing, but were installed before the end of the inspection. Fire sprinklers for this portion of the building are finaled.
INSP-Sprinkler Rough-in/Hydro7/6/20157/6/20157/6/2015PPART
DetailsThomas Walsh
Trip test of dry pipe valve supplying sprinklers in the fitness area, including the are below the pool/spa. Also tested fire alarm interface including water flow, tampers, and low-air test - All tested OK. Following these tests, the system was put on a 2 hour hydrotest, which also passed.
NOTE: This completes the tests to all of the systems for the entire building. Final inspections are pending completion of Towers 3 and 4 areas.
INSP-Sprinkler Rough-in/Hydro6/30/20157/2/20157/2/2015APART
DetailsThomas Walsh
Completion of the 24 hour air test of the the three dry pipe systems protecting the parking garage and fitness area. PASSED
Conducted a trip test of the two dry systems protecting the parking garage. The system to the north flowed at 90 seconds, while the system to the south flowed at 50 seconds.
Also hydrotested the wet system for the third floor and the wet system for the lobby area - 200 psi @ 2 hours - these both passed.
NOTE: Could not trip test the dry system for the fitness center as this area was not accessible.
INSP-Alarm Testing6/30/20157/1/20157/1/2015APART
DetailsThomas Walsh
Fire alarm interface tested, including all wet pipe waterflows (all floors), tampers, etc., including the exterior bell. All systems tested OK. Final inspection to follow.
INSP-Sprinkler Rough-in/Hydro6/30/20156/30/20156/30/2015PPASS
DetailsThomas Walsh
Hydrotests of floors 2 and 4 - 200 psi @ 2hrs, - PASSED.
NOTE: Floor 3 had a leak and floor 5 is not ready for test.
INSP-Sprinkler Rough-in/Hydro6/30/20156/30/20156/30/2015PPASS
DetailsThomas Walsh
Hydrotests of floors 2 and 4 wet pipe systems - 200 psi @ 2hrs - PASSED
NOTE: Floor 3 had a leak, and floor 5 is not ready for test.
INSP-Sprinkler Rough-in6/30/20156/30/20156/30/2015PPART
DetailsThomas Walsh
RTC inspection for under pool deck area - off of fitness room system.
OK to cover.
INSP-Sprinkler Rough-in6/24/20156/25/20156/25/2015APART
DetailsThomas Walsh
RTC inspection for elevator lobbies on the 4th and 5th floors for Tower4, and unit inspections for hard lid soffits on the 2nd floor Tower 4, including units 200, 201, 202, 203, 204 and 205.
OK to cover these areas.
INSP-Sprinkler Rough-in6/23/20156/24/20156/24/2015APART
DetailsThomas Walsh
RTC inspection for ist floor lobby rooms, including restrooms. Also fitness room sprinklers located above T-bar ceiling tilles. OK to cover the heads in these areas.
NOTE: Inspection actually ocurred on 6/23.
INSP-Sprinkler Rough-in6/12/20156/15/20156/15/2015APART
DetailsThomas Walsh
Rough to cover inspection for Tower 3 pod on the second floor, and the corridor for Tower 4 - also second floor.
INSP-Sprinkler Rough-in6/9/20156/10/20156/10/2015PPART
DetailsThomas Walsh
Rough to cover unit soffits for 3rd floor tower 4 section, including units 300 thru 305.
OK to cover the soffits in these units.
INSP-Sprinkler Rough-in6/3/20156/3/20156/3/2015PPART
DetailsThomas Walsh
Rough inspection of unit soffits for Tower #4, 4th and 5th floors, including units 400, 401, 402, 403, 404, 405, 500, 501, 502, 503, 504 and 505. All inspected OK - unit 502 needs sprinkler installed. Also soffits in trash rooms - Tower 2 floors 2 thru 5.
OK to cover pipe in these areas
INSP-Sprinkler Rough-in5/27/20155/28/20155/28/2015APART
DetailsThomas Walsh
Tower 4 cooridor rough inspection for floors 4 and 5. Also several hard lid areas/rooms on the first and second floors - see plans for locations.
PASSED - OK to cover.
INSP-Sprinkler Rough-in5/20/20155/21/20155/21/2015APART
DetailsThomas Walsh
Rough-in inspection of 1sr floor hard lids near stair #1. Also stair 1 levels 3 and 4, and 4th floor POD area.
INSP-Sprinkler Rough-in/Hydro5/19/20155/19/20155/19/2015PPASS
DetailsThomas Walsh
Rough-in of fitness room dry system, elevator loobies for elevator #1 (floors 2 thru 5), and 3rd floor pod soffits for Tower 3.
No discrpancies noted.
INSP-Sprinkler Rough-in5/18/20155/19/20155/19/2015ACANC
DetailsThomas Walsh
Rough-in inspection of fitness room dry system. Also elevator lobbies for elevator #1 (floors 2 thru 5) and 3rd fllor pod soffits located in tower 3.
No discrepancies noted.
INSP-Sprinkler Rough-in5/6/20155/8/20155/16/2015APASS
DetailsThomas Walsh
Rough-in inspection of Elevator lobiesy, all floors, tower 1.
INSP-Sprinkler Rough-in5/14/20155/15/20155/16/2015APASS
DetailsThomas Walsh
Rough in inspection for tower 3 pod units, floors 1 thru 4, including units 206-209, 306-309, 406-409, and 506 -509
INSP-Sprinkler Rough-in5/1/20155/4/20155/4/2015PPART
DetailsScott Arellano
Fire sprinkler rough inspection - Nate - Shilo FP 2nd floor corridors for towers 1 thru 3, and unit soffits sprinklers for all units in tower #3, floors 2 thru 5.
No discrepancies noted.
INSP-Sprinkler Rough-in4/27/20154/28/20154/28/2015APART
DetailsKatie Marron
3rd floor hallways OK to cover. See drawings for specific area of coverage.
INSP-Sprinkler Rough-in4/20/20154/20/20154/20/2015PPART
DetailsKatie Marron
5th and 4th Floor corridors, tower 3 to fire doors OK to cover. Noticed one area in pod with missing hangar.
INSP-Sprinkler Rough-in4/14/20154/15/20154/15/2015APART
DetailsKatie Marron
Floors 4, 3 and podium in tower 4 living quarters ok to cover, except room 204 with overspaced bedroom head and room 200 missing closet head. Soffits in tower 3 ok to cover.
INSP-Sprinkler Rough-in4/10/20154/14/20154/14/2015PFAIL
DetailsKatie Marron
Fail. Missing hangers at numerous locations and a branch line not connected to the main. Will verify corrections at next inspection scheduled for 4/15/15.
INSP-Sprinkler Rough-in4/8/20154/10/20154/10/2015ADEFR
DetailsForrest France
This is 4th fl. Please call 1/2 hr prior to inspection. Nate is the contact.
Thanks Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in4/6/20154/7/20154/7/2015PPART
DetailsScott Arellano
Approved for rough cover within in rooms and corridors at 5th floor.
INSP-Sprinkler Rough-in4/2/20154/3/20154/3/2015APART
DetailsForrest France
4th and 5th floor tower 2 sprinkler coverage at soffits units only okayed- need to provide missing fire stop at some locations. Field modifications at the first floor lobby to be reflected on plan mod.
INSP-Sprinkler Rough-in3/31/20154/1/20154/1/2015APART
DetailsForrest France
Inspection completed for connection of trash chute sprinkler heads at towers one and three- floor levels 5th, 3rd and podium.
INSP-Sprinkler Rough-in3/13/20153/16/20153/16/2015PPART
DetailsForrest France
Verified C/N item at the 5th floor unit 511 tower 2. Rough-in for coverage at soffits 1st floor tower 1.
INSP-Sprinkler Rough-in2/27/20153/2/20153/6/2015APART
DetailsForrest France
Requesting inspection on the 3rd ; 4th floor. Nate M is your contact on site. Please call 1/2 hour prior to inspection. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Sprinkler Rough-in2/26/20152/27/20153/6/2015APART
DetailsForrest France
INSP-Sprinkler Rough-in2/25/20152/26/20152/26/2015PCANC
DetailsForrest France
Overbooked
INSP-Sprinkler Rough-in2/18/20152/19/20152/19/2015APART
DetailsForrest France
Requesting RTC 3rd floor tower 2. Nate is your is your contact. Please Call 1/2 hour prior to inspection. Phone #: ###-#### Inspection requested via web by Stan Beus
INSP-Conference2/12/20152/13/20152/13/2015ADONE
DetailsForrest France
On site conferecne regarding NFPA 13 2013 sec. 8.5.5.4
INSP-Sprinkler Rough-in2/9/20152/9/20152/9/2015APART
DetailsForrest France
Verified added coverage at the 3rd and 4th floor tower two riser room concealed spaces.
INSP-Sprinkler Rough-in2/5/20152/6/20152/6/2015APART
DetailsForrest France
Rough-in inspection completed for living units only at tower 2 podium level. Install incomplete at the common area room 241. Also okayed prior C/N items at the 3rd and 4th floors tower 2. Note: * Damaged main and branchlines due to overheating by proximity to temporary jobsite heating appliances on the 2nd thru 5th floor corridors tower one to be replaced as discussed.*
INSP-Sprinkler Rough-in2/4/20152/4/20152/4/2015APART
DetailsForrest France
Completed rough-in inspection for the 5th floor tower 2 living units and common corridor. Also okayed for cover drops at lower soffits 4th floor tower 1.
INSP-Sprinkler Rough-in2/2/20152/3/20152/4/2015PPART
DetailsForrest France
Completed rough-in inspection of the 3rd and 4th floors tower 2 living units with the exception of NE end and corner rooms not yet piped. DSW heads at some units not yet installed, need to provide coverage at the riser room chases per plan, noted missing coverage at bedroom in unit 322. Rough-in inspections to be done prior to ceiling insulation, discussed distances to be maintained from light fixtures, ceiling fans, and heat sources per NFPA guidelines.
INSP-Sprinkler Rough-in1/26/20151/27/20151/27/2015APART
DetailsForrest France
Center pendent head and branch at the pods tower one podium level thru 4th floor okay for sheetrock ceiling cover.
INSP-Sprinkler Rough-in11/20/201411/21/201411/21/2014APART
DetailsForrest France
Rough-in inspection completed at "tower one" 5th floor room units 530,531,532,533,535,536, and 537, and common corridor including the elevator lobby. Noted items include; overspaced and obstructed head at unit 531 bedroom, relocate one sprinkler too close to a wall in unit 530, furnace rooms to be provided with intermediate temp heads, verify coverage at the elevator hoistway.
INSP-Conference10/17/201410/17/201410/17/2014APART
DetailsForrest France
INSP-Sprinkler Rough-in/Hydro9/15/20149/16/20149/16/2014APART
DetailsForrest France
Intended for an UG fire supply line hydrostatic test- Hydro passed.
INSP-Conference11/26/201411/26/2014 P 
DetailsForrest France
Nate is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus