INSP-Final Inspection | 8/29/2019 | 8/30/2019 | 8/30/2019 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection for area of work complete, other items noted are to be completed under FIR19-00642, this permit is finaled.
Per Ron Johnson this one will be given a TCO once permit FIR19-00642 was applied for. Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
INSP-Final Inspection | 8/26/2019 | 8/27/2019 | 8/27/2019 | A | FAIL |
Jim Page
|
|
|
Network interface between 8th street fire panel and Chase fire panel does not communicate on intial fire alarm, only time panels communicate on general fire is during a second fire alarm while 8th street fire panel is in alarm. Priority 2 alarm reports to chase panel but only have audio notification, no visual notification, troublshoot and repair to be code compliant.
firre alarmBrian Phone #: ###-####
|
INSP-Final Inspection | 8/22/2019 | 8/26/2019 | 8/26/2019 | A | CANC |
Troy Cobbley
|
|
|
Inspector for this project called in sick, contractor wanted 7am but did not corridinate with inspector. I tried to make phone contact with fire alarm tech but was only able to leave message at 7:39am. No inspection was performed.
This inspection needs to happen at 7 am, before the buildings open for business. Please coordinate with Damien @ ###-#### Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
INSP-Final Inspection | 8/5/2019 | 8/6/2019 | 8/6/2019 | A | PART |
Jim Page
|
|
|
Partial final fire alarm inspection complete, TCO authorized for 30 days contingent on noted items being repaired. Notification works in tenant space, fire panel has ground fault that is being resloved and the network interface between fire panels needs to be resloved.
Clint Phone #: ###-####
|
INSP-Alarm Testing | 8/5/2019 | 8/6/2019 | 8/5/2019 | A | CANC |
Jim Page
|
|
|
Damion Phone #: ###-####
|
Fees Due Hold | 8/3/2019 | | 8/5/2019 | | DONE |
Brittany Hill
|
|
|
|
INSP-Final Inspection | 8/2/2019 | 8/2/2019 | 8/2/2019 | A | FAIL |
Jim Page
|
|
|
Fire alarm sounded for approximately half a second then went silent, this happened to the whole building, could not reset panel even after fire alarm was acknowledged.
|
INSP-Final Inspection | 8/1/2019 | 8/2/2019 | 8/2/2019 | A | CANC |
Jim Page
|
|
|
Damin Phone #: ###-####
|
Permit Ready to Issue | | | 8/2/2019 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 8/2/2019 | | DONE |
|
|
|
|
Plan Modification Accepted | | | 8/1/2019 | | |
|
|
|
request as built from Kristen- changed wall mount and ceiling device to different location and removed device in bathroom
|
Plan assigned to (Lee) | 8/1/2019 | | 8/1/2019 | | DONE |
Lee G Meredith
|
|
|
as built- changed wall mount and ceiling device to different location and removed device in bathroom
|
1st review completed | | | 8/1/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 8/1/2019 | | 8/1/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 8/1/2019 | | DONE |
|
|
|
As built - No fee.
|
Issue and Print Permit | | | 7/31/2019 | | DONE |
|
|
|
|
Plan assigned to (Lee) | 7/30/2019 | | 7/30/2019 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 7/30/2019 | | PASS |
|
|
|
|
Alarm Plan Check | 7/30/2019 | | 7/30/2019 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 7/30/2019 | | DONE |
|
|
|
Quick permit passed. No comments.
|
Permit Ready to Issue | | | 7/30/2019 | | DONE |
|
|
|
met
|
Application received | | | 7/29/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 29 2019 11:42AM
|