Information based on query as of Friday, May 17, 2024.
Permit Information
Permit NumberFIR19-00661
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 4100 W LIBBY LN
Project NameSUITE OCCUPANCY SEPERATION
Customer Number 
ePlanReviewYes
Description
AMERICAN WILL INSTALL A NEW 12.1 GALLON ANTIFREEZE SYSTEM USING THE NEW UL LISTING LFP ANTIFREEZE. MOST PIPE AND HEADS WILL BE UNDER THE CEILING EXPOSED. THE ATTIC SPACE IS LESS THEN 2" TALL AND USE CCS HEADS.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/5/20206/11/20206/12/2020PPASS
DetailsTroy Cobbley
Permit finaled.

Phone #: ###-#### Inspection requested via web by Michelle Cooper
INSP-Final Inspection5/18/20205/21/20205/21/2020AFAIL
DetailsTroy Cobbley
Provide a one hour rated riser room, provide heat for the riser room as discussed, provide ball drip for the FDC, provide forward flush testing, provide walk through to verify final sprinkler head placement. All interconnections with the FACP tested ok. Inspection requested via web by Connie Danes
Telephone call  5/21/2020 DONE
DetailsJoe Bruce
Given the size of the small size (<600 SF) of the building and that this is a non-required fire sprinkler system, acceptable to omit the 1-hour fire rating requirement per conversation with assistant Fire Marshal. I also spoke with Tim (General Contractor) and the exterior door for this fire riser room is insulated and the temperature of the past winter allows enough residual heat in this room to keep it above 40 degrees. Owner required to keep temperature in this room above 40F. **JHB**
INSP-Final Inspection4/9/20204/14/20204/14/2020AFAIL
DetailsJim Page
Fire sprinkler system is required to be supervised per the 2015 IFC, section 903.4.

Josh Danes Cell Number: ###-#### Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in1/30/20201/30/20201/30/2020PPASS
DetailsJim Page
Previously noted items have been corrected.

Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in1/23/20201/24/20201/24/2020PFAIL
DetailsTroy Cobbley
Need city approved plans that match the layout of the installed piping. Need through bolts for the earthquake attachments at the roof structure.

Rough in for Cover - Jim will attend Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in1/22/20201/23/20201/24/2020PCANC
DetailsTroy Cobbley
Cover Inspection, Jim will attend Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in/Hydro1/8/20201/9/20201/9/2020APASS
DetailsTroy Cobbley
Overhead Hydro test witnessed with no pressure loss.

, Barry will attend. Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in12/10/201912/12/201912/12/2019PCANC
DetailsTroy Cobbley
Cancel per Barry Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Supply line flush12/9/201912/9/201912/9/2019PPASS
DetailsTroy Cobbley
Underground flush witnessed.

Barry Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in/Hydro12/6/201912/6/201912/6/2019PPASS
DetailsTroy Cobbley
Underground hydro test witnessed.

Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in11/26/201911/27/201911/27/2019APASS
DetailsTroy Cobbley
The underground tie-in piping is ok for cover.
Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in11/11/201911/12/201911/12/2019PPASS
DetailsTroy Cobbley
Underground supply piping is ok for cover.

Phone #: ###-#### Inspection requested via web by Connie Danes
INSP-Sprinkler Rough-in11/7/201911/8/201911/8/2019PCANC
DetailsTroy Cobbley
Phone #: ###-#### Inspection requested via web by Connie Danes
Issue and Print Permit  9/16/2019 DONE
Plan resubmittals received  9/6/2019 DONE
DetailsMark Stumbaugh
Sprinkler Plan Check9/6/2019 9/6/2019 PASS
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  9/6/2019 DONE
DetailsMark Stumbaugh
Permit Ready to Issue  9/6/2019 DONE
Intake Approval  9/5/2019 PASS
DetailsMark Stumbaugh
Plan assigned to (Stumbaugh)9/5/2019 9/5/2019 DONE
DetailsMark Stumbaugh
Sprinkler Plan Check9/5/2019 9/5/2019 FAIL
DetailsMark Stumbaugh
Application received  9/4/2019 DONE
Application submitted via PDS Online on Sep 4 2019 2:29PM