INSP-Final | 10/8/2019 | 10/8/2019 | 10/8/2019 | P | DONE |
Troy Cobbley
|
|
|
Permit finaled.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
DOC - Permit Finaled | | | 10/8/2019 | | DONE |
|
|
|
Per Troy C, 10/8/19 Final inspection
|
INSP-Final | 9/18/2019 | 9/19/2019 | 9/19/2019 | A | FAIL |
Troy Cobbley
|
|
|
Can final when heat is provided and the plastic is attached to the trusses (repaired) and insulation is provided at these patched areas. Phone #: ###-#### Inspection requested via web by Sam Ball
|
INSP-Final | 8/21/2019 | 8/22/2019 | 8/22/2019 | P | PART |
Troy Cobbley
|
|
|
Sprinkler work is complete. Temporary per Boise Fire. Permit can be finaled when the shell/core permit is finaled.
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
|
INSP-Final | 8/20/2019 | 8/21/2019 | 8/21/2019 | A | FAIL |
Troy Cobbley
|
|
|
There were problems with the fire alarm system which prevented testing of the sprinkler system. No testing performed. Phone #: ###-#### Inspection requested via web by Sam Ball
|
INSP-Sprinkler Rough-in/Hydro | 8/6/2019 | 8/7/2019 | 8/7/2019 | A | PASS |
Troy Cobbley
|
|
|
24 hour air test on dry system and hydrostatic test on wet system witnessed with no pressure loss. Phone #: ###-#### Inspection requested via web by Sam Ball
|
INSP-Conference | 8/5/2019 | 8/6/2019 | 8/6/2019 | P | DONE |
Troy Cobbley
|
|
|
Myself, sam and the job superintendant spoke about a temporary occupancy for the two tenants until a third middle tenant is found with-in the next couple months. I deferred the request to the fire dept.
Call prior to going Phone #: 2085731293 >> Inspection requested via mobile web by Sam
|
INSP-Sprinkler Rough-in/Hydro | 8/5/2019 | 8/6/2019 | 8/6/2019 | P | PART |
Troy Cobbley
|
|
|
24 hour air test started on the dry system with 41psi on the guage.
Call prior to going Phone #: 2085731293 >> Inspection requested via mobile web by Sam
|
INSP-Sprinkler Rough-in | 7/11/2019 | 7/11/2019 | 7/11/2019 | P | PASS |
Troy Cobbley
|
|
|
Head added to the concealed area above fire place. Tenting passed. Piping for the west side tenant space can be covered. The center tenant space can not be covered until a tenting inspection has been completed.
|
INSP-Final | 7/11/2019 | 7/11/2019 | 7/11/2019 | P | CANC |
Troy Cobbley
|
|
|
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian Inspection cancelled via mobile web on Thursday, July 11, 2019.
|
INSP-Sprinkler Rough-in | 6/25/2019 | 6/25/2019 | 6/25/2019 | P | PART |
Jim Page
|
|
|
Tenting inspection for east side tenant space complete, all tenting in place for east side tenant at time of inspection, east side tenant space approved for cover.
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
|
INSP-Sprinkler Rough-in | 6/21/2019 | 6/24/2019 | 6/24/2019 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected.
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Bryan
|
INSP-Sprinkler Rough-in | 6/19/2019 | 6/20/2019 | 6/19/2019 | A | FAIL |
Troy Cobbley
|
|
|
EQ bracing on wet system main needs to be changed to what was approved. Dry system ok **MAS**
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
|
INSP-Sprinkler Rough-in/Hydro | 6/19/2019 | 6/19/2019 | 6/19/2019 | P | PASS |
Troy Cobbley
|
|
|
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
|
INSP-Supply line flush | 5/17/2019 | 5/20/2019 | 5/20/2019 | A | PASS |
Troy Cobbley
|
|
|
Underground supply line flush witnessed. Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
|
INSP-Sprinkler Rough-in/Hydro | 4/11/2019 | 4/12/2019 | 4/12/2019 | A | PASS |
Troy Cobbley
|
|
|
The underground hydro test was witnessed with no pressure loss. Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
|
INSP-Sprinkler Rough-in | 3/26/2019 | 3/27/2019 | 3/27/2019 | A | PASS |
Troy Cobbley
|
|
|
Underground supply line cover passed.
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
|
INSP-Sprinkler Rough-in | 3/26/2019 | 3/26/2019 | 3/26/2019 | P | CANC |
Troy Cobbley
|
|
|
Call prior to going Phone #: 2089148171 >> Inspection requested via mobile web by Brian
|
Staff review | 3/21/2019 | 3/21/2019 | 3/25/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Permit Ready to Issue | | | 3/25/2019 | | DONE |
|
|
|
|
Issue and Courier | | | 3/25/2019 | | DONE |
|
|
|
|
Issue and Courier | | | 3/25/2019 | | DONE |
|
|
|
didn't email Shelley because she emailed me that the customer was coming over to pick it up here-i did let hr know that there was a plan review fee since this is the 3rd resubmittal
|
Plan resubmittals received | | | 3/21/2019 | | DONE |
|
|
|
Resubmittals recieved 4 sets of the response letter & sheet FP3-took to MAS
|
Plan resubmittals received | | | 3/7/2019 | | DONE |
|
|
|
Resubmittals received 4 sets of drawings and 4 sets of calcs-took to MAS
|
Staff review | 3/1/2019 | 3/1/2019 | 3/5/2019 | | FAIL |
Mark Stumbaugh
|
|
|
See comments-3 hr plan review time
|
Plan resubmittals received | | | 3/1/2019 | | DONE |
|
|
|
resubmittals received-broke 1 permit into 3-resubmittals all the drawings for them-took to MAS
|
Miscellaneous action | | | 3/1/2019 | | DONE |
|
|
|
emailed Shelley Ste #'s and permits as well as the AF #er's
|
Staff review | 2/20/2019 | 2/20/2019 | 2/21/2019 | | FAIL |
Mark Stumbaugh
|
|
|
Review Time 1hr
|
Miscellaneous action | | | 2/21/2019 | | DONE |
|
|
|
emailed Shelley about the failed plan revied and the review time
|
Application received | | | 2/20/2019 | | |
|
|
|
|
Plan assigned to (Stumbaugh) | 2/20/2019 | | | | |
Mark Stumbaugh
|
|
|
|