Permit NumberELE18-01608
StatusFinaled
Name MOUNTAIN POWER ELECT
Site Address 355 W JULIA DAVIS DR
Project Name 
Customer Number18-007
ePlanReviewNo
Description
New: Provide the electrical work associated with E.O. Wilson Building for the Zoo with a View project.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/28/20196/28/20196/28/2019APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Mike McCarrel Final ok
Conference5/9/20195/9/20195/9/2019PDONE
DetailsRock A. Hudson
Discussed work clearance for exterior pool equipment. Fence is planned to be installe limitting access to serviceable equipment for pools. All serviceable equipment shall have minimum work clearances as per 110.26 3' depth and 30" wide for 120/208 volt.
Final4/30/20195/1/20195/1/2019APART
DetailsRock A. Hudson
Inspection for baboon occupancy... Phone #: ###-#### Inspection requested via web by Mike McCarrel
No general public shall have access, only baboon keepers will have access to baboon areas only. Electrical contractor keeps each panel board locked.
TCO EO Wilson bldg baboon areas only ok
Electrical Rough-In4/25/20194/26/20194/26/2019APASS
DetailsRock A. Hudson
ceiling inspection at terrarium Phone #: ###-#### Inspection requested via web by Mike McCarrel
Area noted grid rough in ok cover.
Conference4/16/20194/16/20194/16/2019PDONE
DetailsRock A. Hudson
Questions regarding bonding in outdoor otter exhibit Phone #: ###-#### Inspection requested via web by Mike McCarrel
Questiion is for bonding of rebar located on interior of artificial rocks in contact with water.
No electrical equipment in or on otter pond, no metal likely to become energized as per 682.32. Equipotential plane will be needed for equipment disconnecting means as per 682.33.
Electrical Rough-In4/9/20194/10/20194/10/2019APASS
DetailsRock A. Hudson
Bathroom ceilings for cover Phone #: ###-#### Inspection requested via web by Mike McCarrel
Access shall be provided for emergency ballasts. Bathrooms and entrance. Rough in ok cover
Conference4/9/20194/9/20194/9/2019PDONE
DetailsRock A. Hudson
Discussed ceilings in bathrooms of EO Wilson building. Access shall be provided to fit a full body above ceiling to access emergency ballast of luminaires in bathroom and bathroom entrance. Ceiling support system shall not be used to support luminaires, cables, or conduits unless manufacturers instructions state other wise
Electrical Rough-In4/3/20194/4/20194/4/2019APART
DetailsRock A. Hudson
Underground fed from MDP to Zebra Barn, Ground Hornbill and Lion House Phone #: ###-#### Inspection requested via web by Mike McCarrel
At south end of dog enclosure due to existing underground unable to acheive required depth. Must either change to rigid or encase in concrete. Rest of noted underground rough in ok cover
Electrical Rough-In4/1/20194/2/20194/3/2019PPASS
DetailsMark Moncarr
Soffits in animal enclosures for cover Phone #: ###-#### Inspection requested via web by Mike McCarrel Ok cover soffits for crocodile, baboon and otter enclosures. Also ground work for exterior lighting from D7 panel. Check for recess can install in hardlid.
Electrical Rough-In3/26/20193/27/20193/27/2019APASS
DetailsRock A. Hudson
Bonding of re-bar on outside crocodile pool of E.O. Wilson.
Contact is Mike Hastings Phone #: ###-#### Inspection requested via web by Mike McCarrel
East gator pond shell bond rough in ok cover
Electrical Rough-In3/11/20193/12/20193/12/2019APASS
DetailsJames Ady
Overhead rough-in for EO Wilson building Phone #: ###-#### Inspection requested via web by Mike McCarrel ceilings in remaining hard lid areas ok to cover
Electrical Rough-In3/8/20193/11/20193/11/2019APASS
DetailsRock A. Hudson
Underground from main service to E.O. Wilson building Phone #: ###-#### Inspection requested via web by Mike McCarrel
EO wilson feeders and branch conduits rough in ok cover
Permanent Service2/20/20192/21/20192/21/2019PPASS
DetailsRock A. Hudson
Permanent service for Gorongosa site. if possible, would like inspection around noon Phone #: ###-#### Inspection requested via web by Mike McCarrel p/s u/g n ok
Electrical Rough-In2/19/20192/20/20192/20/2019APASS
DetailsRock A. Hudson
Common area ceiling inspection, Building D7 Phone #: ###-#### Inspection requested via web by Mike McCarrel
Service inspection to be requested for main distibution panel all sub- feeds to be installed as needed. D-7 ceiling rough in ok cover
Electrical Rough-In2/18/20192/19/20192/19/2019PPASS
DetailsRock A. Hudson
Underground for site and partial rough-in for EO Wilson building Phone #: ###-#### Inspection requested via web by Mike McCarrel
Discussed disconnect locations for interior body of water equipment. All shall have work space clearances and dedicated electrical space if a panel board or switch board as per 110.26.
North underground and E.O Wilsom building bathroom ceilings rough in ok cover.
Electrical Rough-In2/12/20192/13/20192/13/2019APASS
DetailsRock A. Hudson
underground inspection for cover Phone #: ###-#### Inspection requested via web by Mike McCarrel
Underground north side and all the way around west side of dog enclosure rough in ok cover
Conference2/13/20192/13/20192/13/2019PPASS
DetailsRock A. Hudson
underground inspection for cover Phone #: ###-#### Inspection requested via web by Mike McCarrel
Discussed animals being held in enclosures prior to final. As long as TCO has been granted for electrical associated with said encloure OK. Optional back up power will not be installed by this time however it is an option and transfer switch will be installed. In an emergency a portable could be used on temporary basis.
Electrical Rough-In2/7/20192/8/20192/8/2019PPASS
DetailsRock A. Hudson
Underground inspection Phone #: ###-#### Inspection requested via web by Mike McCarrel
Underground associated with service pad rough in ok cover
Electrical Rough-In1/15/20191/16/20191/16/2019APASS
DetailsRock A. Hudson
Inspect underground conduit for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud
West branch circuit underground rough in ok cover
Electrical Rough-In1/11/20191/14/20191/14/2019APASS
DetailsRock A. Hudson
Inspect underground conduit for cover Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Underground south and east of EO Wilaon bldg rough in ok cover
Electrical Rough-In1/8/20191/9/20191/9/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Central and western underground of west area as noted on contractor print rough in ok cover.
Electrical Rough-In1/3/20191/4/20191/4/2019APASS
DetailsRock A. Hudson
Inspect underground conduit for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud
OK to backfill underground in high traffic areas prior to inspection as long as contractor has photos and given the ok to cover.
Underground as noted on contractor print dated, rough in ok cover
Electrical Rough-In12/20/201812/21/201812/21/2018APASS
DetailsRock A. Hudson
Inspect underground conduit for cover Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Excavator asked for permission to cover roadways trying to keep accesses open. Told no cover with out the ok from electrical contractor.
Underground at east and west areas of west buildings as noted and dated on contractor print.
Electrical Rough-In12/19/201812/20/201812/20/2018APASS
DetailsRock A. Hudson
Inspect underground conduit on Centennial side for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud
This area will have several underground inspection, please mark contractor print in their trailer. Undergound as noted on contractor print rough in ok cover
Electrical Rough-In12/17/201812/18/201812/18/2018APASS
DetailsRock A. Hudson
Inspect underground at gift shop for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Allowed a photo of this install due to office missed inspection request and trench just inside entry gate in main walkway. Future underground inspections will be seen in person.
Underground east of gift shop under common pathways feeds to west new buildings rough in ok cover
Electrical Rough-In10/15/201810/16/201810/16/2018APASS
DetailsRock A. Hudson
Inspect pool bonding for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Discussed inspections required prior to cover. A concrete encased electrode installed for building 6 and covered. Contact took pictures. This will be only time pictures will be accepted.
Discussed 250.32 ex. Seperate buildings do not require a grounding electrode if fed by a single branch circuit or a multi-wire branch circuit that have a equipment grounding conductor.
Gator and otter ponds equipotential around each and interior equipment pad rough in ok cover.
Electrical Rough-In9/26/20189/27/20189/27/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Discussed equipotential bonding, How to bond window frames in contact with water and 3' around equipment and disconnects serving equipment. Uderground complete for E.O. Wilson bldg rough in ok cover
Electrical Rough-In9/20/20189/21/20189/21/2018APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Underground E.O. Wilson common area rough in ok cover
Electrical Rough-In9/14/20189/17/20189/17/2018PPART
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Misc underground with more to come. Discussed wiring methods, MC ok to terminate to PVC if equipment ground available at 1 end. Stubs up walls and through walls rough in ok cover.
Electrical Rough-In8/17/20188/20/20188/20/2018APASS
DetailsRock A. Hudson
Please Call Mike Phone #: ###-#### Inspection requested via web by Kevin Perez
EO wilson building base wall pour rough in ok cover
Temporary Service8/15/20188/15/20188/15/2018PFAIL
DetailsRock A. Hudson
please call Corey Phone #: ###-#### Inspection requested via web by Kevin Perez
Temp service requires seperate permit
Electrical Rough-In8/7/20188/8/20188/8/2018APASS
DetailsRock A. Hudson
Please call Mike McCarrel Phone #: ###-#### Inspection requested via web by Kevin Perez
Concrete encased electrode rough in ok cover