Permit NumberFIR18-00858
StatusIssued
Name STATEFIRE DC SPECIALTIES
Site Address 1221 W IDAHO ST
Project NameIDAHO POWER CHQ FIRE ALARM UPG
Customer Number 
ePlanReviewYes
Description
COMPLETE REPLACEMENT & UPGRADE OF THE EXISTING SIMPLEX FIRE ALARM/VOICE EVAC SYSTEM WITH A NEW SILENT KNIGHT SYSTEM. This work is not associated with a building permit. ALL FIRE SMOKE DAMPERS ARE REQUIRED TO HAVE AN IN DUCT SMOKE DETECTOR LOCATED WITHIN FIVE FEET OF EACH FIRE SMOKE DAMPER UNLESS OPEN AREA DETECTION HAS BEEN PROVIDED IN AN APPROVED MANNER. Plan Mod 10-11-19. Includes added smoke detectors above and below the ceiling for plenum coverage, in duct detection, a smoke control panel and fire smoke damper control. Since this is a direct replacement of the original designed / approved smoke control system, it is a 1 for 1 replacement and not subject to prescriptive code requirements. This smoke control will require a third party inspection per 2015 IFC 909.18.8.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/14/20201/15/20201/15/2020PPART
DetailsJim Page
No noted items for level 1 walkthrough.

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
INSP-Final Inspection12/27/201912/30/201912/30/2019PPART
DetailsJim Page
Walkthrough completed for remaining level 2 and basment level. Walkthrough not performed on level 1, base of A/V devices were masked for painting, could not see candella setting.

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
INSP-Final Inspection12/12/201912/12/201912/12/2019PPART
DetailsJim Page
Northside of level 2 walkthrough complete, approved plans are notated for areas of correction.
INSP-Final Inspection12/10/201912/12/201912/12/2019PFAIL
DetailsJim Page
Level 3 floor plan does not match what was provided to the fire alarm designer, corrections need to be made for proper coverage..

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
INSP-Final Inspection12/4/201912/6/201912/6/2019APART
DetailsJim Page
Walk through complete for levels 4, 5 and 6, notated city approved plans with red ink for corrections.

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
INSP-Final Inspection12/2/201912/3/201912/3/2019PPART
DetailsJim Page
Walk through complete for levels 7 and 8, notated city approved plans with red ink for corrections.

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa
INSP-Final Inspection11/25/201911/27/201911/27/2019APART
DetailsJim Page
Walk through complete for penthouse and level 9, notated city approved plans with red ink for corrections, level 9 has a room that is a telephone room, not a telecom room, provide notification in telephone room. Conference room on level 9 is in a different location tahn the drawings, A/V device is overspaced due to wall location. Will verify correction on a future inspection.

Call prior to going Phone #: 2086810381 >> Inspection requested via mobile web by Doug Lessa