Permit Information
Permit NumberFIR18-00901
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1701 S RAYMOND ST
Project NameICCU Overland Storage Bldg
Customer Number 
ePlanReviewYes
Description
[ICCU Overland Storage Building]
The fire sprinkler scope of work consists of replacing and existing fire sprinkler system with a new system starting at an underground connection. New 6”x60’± C-900 underground piping with associated fittings and thrust blocks. The underground supplies a new 4” backflow preventer and riser to a new grid type layout with 4”x4”x 1½” piping. The storage is furniture less than 12’ high.

[BLD18-03251]
Permit is to convert an existing 19,760 sq. ft. retail store into a storage warehouse building for furniture, promotional products, and office supplies. The prior tenant was Regency Carpet Barn under permit BLD08-01632. A northern portion of the building will be demolished to reduce the total tenant area of the warehouse to 14,460 sq. ft. This building is fully Fire Sprinklered with an approved Fire Alarm system. Work to include: new asphalt parking lot, site work, new exterior finishes/roof, exterior doors, electrical work, plumbing work, mechanical work and interior finishes in compliance with Ch. 8 of the current IBC. A reduction to the occupant load for plumbing fixture counts has been approved by the building official. An occupant load of 15 shall be posted at the front entrance. Racking that exceeds 8 ft. in height requires a separate Building Permit. Any alterations or modifications to the building’s Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT as regulated by the Boise Fire Department. **JHB**

Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.

• There are no AMM at this time that pertain to the fire sprinklers.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/19/20194/19/20194/19/2019PPASS
DetailsJim Page
Final fire sprinkker inspection complete.
INSP-Final Inspection4/11/20194/16/20194/16/2019AFAIL
DetailsTroy Cobbley
Need forward flush test and the fire alarm permit scheduled to test interconnection with fire riser devices.


Please call Jeff with time frame this will include alarm testing and our remaining items. Phone #: ###-#### Inspection requested via web by Jeff Packham
INSP-Conference4/2/20194/2/20194/2/2019PDONE
DetailsJim Page
A second curb valve was installed after SUEZ valve to accomplish underground hydrostatic test, underground held 200psi for 2 hours as required by NFPA 13.

This is inspection to confirm our isolation of the underground from the Suez service and hydro test of UG. It can be completed during hydro test for overhead. We will be on site. Phone #: ###-#### Inspection requested via web by Jeff Packham
INSP-Sprinkler Rough-in/Hydro4/2/20194/2/20194/2/2019PDONE
DetailsJim Page
Hydrostatic test for underground supply and overhead fire sprinkler piping witnessed, no pressure loss observed.

Tom Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro4/1/20194/1/20194/1/2019PFAIL
DetailsTroy Cobbley
The underground supply piping was not pressurized when I arrived at job site. Per Tom a letter from Suez will be provided since the underground piping will not hold pressure. underground // Tom Phone #: ###-####
INSP-Supply line flush3/14/20193/14/20193/14/2019PPASS
DetailsTroy Cobbley
Underground flush passed
INSP-Sprinkler Rough-in2/26/20192/27/20192/27/2019APASS
DetailsTroy Cobbley
Bury depth has been corrected. Underground supply piping is ok for cover.

Phone #: ###-#### Inspection requested via web by Jeff Packham
INSP-Supply line flush2/25/20192/26/20192/26/2019APART
DetailsTroy Cobbley
The portion of the supply piping near the Suez connection point is not buried deep enough and will need to be modified and re-inspected. After the second 45 degree elbow the piping is deep enough and can be buried.


Note:Pouring Thrust Block by noon. P Lease see Troy Nelsen Phone #: ###-#### Inspection requested via web by Daniel Buccino
INSP-Sprinkler Rough-in2/11/20192/11/20192/11/2019PPASS
DetailsTroy Cobbley
General overhead rough-in passed. Still need earthquake bracing installed and verified.

Mike Phone #: ###-####
INSP-Sprinkler Rough-in1/24/20191/24/20191/24/2019PPASS
DetailsTroy Cobbley
Hanger attachments are ok for cover.

Mike Phone #: ###-####
INSP-Sprinkler Rough-in12/20/201812/20/201812/20/2018PPASS
DetailsTroy Cobbley
Cover inspection for IBR Stub out passed. Piping/IBR can be covered.

Please call ROY, with time frame. Thanks and have a great day. Phone #: ###-#### Inspection requested via web by Jeff Packham