Information based on query as of Thursday, May 9, 2024.
Permit Information
Permit NumberFIR19-00555
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION
Site Address 150 N 8TH ST
Project NameEvermore Prints TI
Customer Number 
ePlanReviewYes
Description
Provide new notification devices, relocate and demo existing notificaiton devices as shown on the drawings. This work is associated with BLD19-02376
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/29/20198/30/20198/30/2019APASS
DetailsJim Page
Final fire alarm inspection for area of work complete, other items noted are to be completed under FIR19-00642, this permit is finaled.

Per Ron Johnson this one will be given a TCO once permit FIR19-00642 was applied for. Phone #: ###-#### Inspection requested via web by Kristin Dolan
INSP-Final Inspection8/26/20198/27/20198/27/2019AFAIL
DetailsJim Page
Network interface between 8th street fire panel and Chase fire panel does not communicate on intial fire alarm, only time panels communicate on general fire is during a second fire alarm while 8th street fire panel is in alarm. Priority 2 alarm reports to chase panel but only have audio notification, no visual notification, troublshoot and repair to be code compliant.

firre alarmBrian Phone #: ###-####
INSP-Final Inspection8/22/20198/26/20198/26/2019ACANC
DetailsTroy Cobbley
Inspector for this project called in sick, contractor wanted 7am but did not corridinate with inspector. I tried to make phone contact with fire alarm tech but was only able to leave message at 7:39am. No inspection was performed.

This inspection needs to happen at 7 am, before the buildings open for business. Please coordinate with Damien @ ###-#### Phone #: ###-#### Inspection requested via web by Kristin Dolan
INSP-Final Inspection8/5/20198/6/20198/6/2019APART
DetailsJim Page
Partial final fire alarm inspection complete, TCO authorized for 30 days contingent on noted items being repaired. Notification works in tenant space, fire panel has ground fault that is being resloved and the network interface between fire panels needs to be resloved.

Clint Phone #: ###-####
INSP-Alarm Testing8/5/20198/6/20198/5/2019ACANC
DetailsJim Page
Damion Phone #: ###-####
INSP-Final Inspection8/2/20198/2/20198/2/2019AFAIL
DetailsJim Page
Fire alarm sounded for approximately half a second then went silent, this happened to the whole building, could not reset panel even after fire alarm was acknowledged.
INSP-Final Inspection8/1/20198/2/20198/2/2019ACANC
DetailsJim Page
Damin Phone #: ###-####