Permit Information
Permit NumberBLD18-04519
StatusIssued
Name WRIGHT BROTHERS THE BLDG CO EAGLE
Site Address 974 N MAPLE GROVE RD
Project NameRosewood Apartments Bldg 10
Customer Number 
ePlanReviewYes
Description
(ROSEWOOD APARTMENTS) (BUILDING #10) //08/01/19 PLAN MOD TO UTILITY LINE LOCATIONS AND LANDSCAPE PLANS. JAR// Permit for the construction of a new 15,774 sq ft, 3-story, 12 unit apartment building (identified as Type VI on plans). Work to include general site work and the construction of the new building per the approved plans. Special inspections required per attached Form 310. Carports to be constructed under separate building permit. All buildings are to be fully fire sprinklered with an NFPA 13-R system as required for residential occupancy and story increase. Exterior decks and breezeways to be protected. **JAR**
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Framing/Rough-in4/29/20204/30/20204/30/2020APASS
DetailsMike Jordan
Ceiling drops for cover, Building 10 (12 units). Phone #: ###-#### Inspection requested via web by Bob Goodwin
BLD-Framing/Rough-in4/29/20204/29/20204/29/2020ANR
DetailsMike Jordan
Ceiling drops for cover in Building 10 (12 units), late as possible this morning. Phone #: ###-#### Inspection requested via web by Bob Goodwin. Stiil needs mech. rough in inspection. electrical rough in inspection has failed for all units.
BLD-Framing/Rough-in4/27/20204/28/20204/28/2020PNR
DetailsMike Jordan
Ceiling drops framing inspection for cover, Building 10 (12 Units). Phone #: ###-#### Inspection requested via web by Bob Goodwin
BLD-Energy code compliance4/13/20204/15/20204/15/2020APASS
DetailsTell Riley
Building 10 Insulation, Vapor Barrier ; RC Channel for cover Phone #: ###-#### Inspection requested via web by Bob Goodwin
BLD-Energy code compliance4/13/20204/14/20204/13/2020ACANC
DetailsMike Jordan
Building 10 Insulation, Vapor Barrier & RC Channel for cover Phone #: ###-#### >> Inspection requested via web by Bob Goodwin Inspection cancelled from web by: Bob Goodwin
BLD-Framing/Rough-in4/10/20204/13/20204/13/2020APASS
DetailsMike Jordan
Building 10 Framing Inspection, C3 truss bearing point truss-manufacturer "No Repair Needed", drawing confirmation. Phone #: ###-#### Inspection requested via web by Bob Goodwin. Per the truss engineer, no repair is required for the missed C3 truss bearing location.
BLD-Framing/Rough-in4/8/20204/9/20204/9/2020PFAIL
DetailsMike Jordan
Building 10 Energy Seal, Fire Caulking ; Framing for Cover Phone #: ###-#### Inspection requested via web by Bob Goodwin. Complete fire caulking, fireblock fur out walls. Provide approved fix for missed bearing points on C3 trusses.
BLD-Framing/Rough-in2/26/20202/27/20202/27/2020ACANC
DetailsMike Jordan
Re-inspect shear Phone #: ###-#### Inspection requested via web by Kris Linnell
BLD-Wall Bracing2/27/20202/27/20202/27/2020APASS
DetailsMike Jordan
Re-inspect shear Phone #: ###-#### Inspection requested via web by Kris Linnell. Exterior shear only.
BLD-Framing/Rough-in2/26/20202/26/20202/26/2020PNR
DetailsMike Jordan
Shear re-inspection Phone #: ###-#### Inspection requested via web by Kris Linnell
BLD-Framing/Rough-in2/25/20202/25/20202/25/2020PFAIL
DetailsMike Jordan
Inspection on Exterior shear Phone #: ###-#### Inspection requested via web by Kris Linnell
BLD-Framing/Rough-in2/20/20202/21/20202/21/2020APART
DetailsMike Jordan
Exterior Shear and Wall Framing on East Exterior Walls for Plumbing wall pre-rock. Phone #: ###-#### Inspection requested via web by Kris Linnell. Ok to pre rock at tubs only.
BLD-Concrete10/9/201910/10/201910/13/2019PPASS
DetailsDave Hannah
Building 10 Thickend footing and slab reinforcement inspeciton Phone #: ###-#### Inspection requested via web by Kris Linnell
BLD-Energy code compliance9/20/20199/23/20199/23/2019PPASS
DetailsMike Jordan
Stem Wall insulation Phone #: ###-#### Inspection requested via web by Kris Linnell
BLD-Foundation9/17/20199/18/20199/18/2019APASS
DetailsMike Jordan
Stem Walls for Building 10. Pour scheduled for 2P.M. Phone #: ###-#### Inspection requested via web by Kris Linnell
BLD-Footing9/6/20199/9/20199/9/2019APART
DetailsMike Jordan
Rebar inspection for footings. Pour is scheduled for 1130 Phone #: ###-#### Inspection requested via web by Kris Linnell. Work in progress on installing the remaing verts. Ok to place concrete pending special inspection.
BLD-Footing9/5/20199/6/20199/6/2019PCANC
DetailsMike Jordan
Chris Phone #: ###-#### Inspection cancelled from web by: Kris Linnell
CHANGE STATUS TO (ISS)  9/5/2019 DONE
plan mod
OVERRIDE  8/6/2019  
Plan assigned to (JAR)7/24/20197/24/20198/6/2019 DONE
DetailsJulie Romig
1st Rev Comp - Plan Mod - Rosewood Bldg 10
PLANS/APPL TAKEN TO FRONT DESK  8/6/2019 DONE
Permit Ready to Issue  8/6/2019 DONE
PLAN MOD - DO NOT REISSUE UNTIL PLAN MOD FEES FOR BLD19-04520 HAVE BEEN PAID
Routing - Design Review8/5/2019 8/5/2019 PASS
DetailsAndrea Tuning
Routing - Design Review7/30/2019 8/1/2019 FAIL
DetailsAndrea Tuning
Remove trash enclosure from adjacent to Susan Drive
Routing - PLAN CHECK7/30/2019 8/1/2019 PASS
DetailsJulie Romig
Pending DR approval
Routing PW Drainage7/30/2019 7/31/2019 PASS
DetailsBrian Murphy
Routing PW Sewer Design7/30/2019 7/31/2019 PASS
DetailsDeAnn Brown
Routing - PLUMBING7/30/2019 7/30/2019 PASS
DetailsDaryl Spivey
Per plan and ISPC.
Routing - PUBLIC WORKS7/30/2019 7/30/2019 PASS
DetailsAngela Hardy
Plan Modification Accepted  7/24/2019 DONE
plan mod accepted in e plan for BLD18-04520, BLD18-04521 & BLD18-04519-updates to the utilities-PW, water lines ectC1.0,C2.0, C2.1, P2.1, A0.1, A2.2,A2.3,A4.3,A10.0, S2.2, S2.3, S2.4, S5.1-assigned to JAR-no valuations will change
Plan assigned to (JAR)1/2/20191/3/20197/23/2019 DONE
DetailsJulie Romig
1st Rev Comp - 4th Comp - 506 Rosewood Apts Bldg 10
Issue PAID IN FULL permit  7/12/2019 DONE
Print Occupancy Form  7/12/2019 DONE
Telephone call  7/10/2019 DONE
emailed the rest of the fees still due to tom and jade
OVERRIDE  7/9/2019  
Permit Ready to Issue  7/9/2019 DONE
MET- Need RP
Routing - PLAN CHECK7/2/2019 7/8/2019 PASS
DetailsJulie Romig
Routing - Design Review7/2/2019 7/2/2019 FAIL
DetailsAndrea Tuning
Routing - PLAN CHECK6/25/2019 6/25/2019 PASS
DetailsJulie Romig
All IBC Plan Review items passed. Corrections required per DR.
Routing PW Sewer Design6/25/2019 6/25/2019 PASS
DetailsDeAnn Brown
Routing - Design Review6/25/2019 6/25/2019 FAIL
DetailsAndrea Tuning
Replace the street trees on Susan Drive that were removed from this version of the landscape plan.

Remove the trash enclosure from the setback.
Routing - PLANNING6/25/2019 6/25/2019 PASS
DetailsKarla Nelson
Recorded CCR's from April 25 cover the parking cross access agreement.
Routing - PLAN CHECK4/24/2019 5/2/2019 FAIL
DetailsJulie Romig
All IBC Plan Review items passed. Corrections required per DR, Planning, PW Sewer Design: easements/agreements required.
Routing PW Sewer Design4/24/2019 5/2/2019 FAIL
DetailsDeAnn Brown
Sewer service pipeline under proposed building 10 must be relocated prior to approval of building permit.
Routing - PLAN CHECK4/10/2019 4/22/2019 FAIL
DetailsJulie Romig
Routing PW Drainage4/10/2019 4/18/2019 PASS
DetailsBrian Murphy
Routing PW Sewer Design4/10/2019 4/11/2019 FAIL
DetailsDeAnn Brown
Notes on sheet C2.0 still call out an existing 18" sewer main, when it is a 15" sewer main. Notes also use slopes for 6-inch services that match the service invert to the mainline invert. Services should tap mainline at or above 80% full level. Please revise.
Routing - Design Review4/10/2019 4/10/2019 FAIL
DetailsAndrea Tuning
Submit a recorded cross access agreement.
Routing - PLANNING4/10/2019 4/10/2019 FAIL
DetailsNicolette Womack
Need to consolidate the parcels or provide a cross access/share parking agreement
Routing PW Sewer Design3/21/2019 3/27/2019 FAIL
DetailsDeAnn Brown
Changemarks from the first two review sessions have not been addressing. Revise and resubmit.
Routing - PLAN CHECK3/21/2019 3/26/2019 FAIL
DetailsJulie Romig
Routing - PLANNING3/21/2019 3/21/2019 FAIL
DetailsDavid Moser
need cross access / shared parking agreement
Routing - Design Review3/21/2019 3/21/2019 FAIL
DetailsAndrea Tuning
The applicant should consolidate the parcels into one large parcel or enter into a cross access/shared parking agreement in regard to parking, pedestrian networks and trash collection.
Provide a minimum of 66 bicycle parking spaces on the site with 17 of these spaces being covered. To provide a safe, covered and efficient location for the bicycles, the applicant will be required to design the spaces to be a minimum of 6 feet long and 2.5 feet wide and have an overhead clearance of 7-feet if covered. A 4-foot wide aisle is required between rows of bicycle parking or nearby walls. Stationary racks shall be located on improved non-permeable surfaces and anchored to the ground.
All light poles and fixtures shall be located outside of the required setbacks and landscape planters which contain trees as required by the landscape ordinance. All lighting shall also be designed and located so as to prevent glare or direct light from falling onto adjoining properties or streets. The illumination of all light fixtures shall not exceed two foot candles as measured 1-foot above the ground at property lines shared with residentially zoned or used parcels. All new pole lighting shall feature 100 percent cut-off light fixtures and all new wall lighting shall have full cut-off shields.
Routing - PLAN CHECK3/6/2019 3/19/2019 FAIL
DetailsJulie Romig
Routing PW Sewer Design3/6/2019 3/13/2019 FAIL
DetailsDeAnn Brown
Corrections noted in last review were not included in new set. Please see changemarks for noted corrections/changes.
Routing Off Site - STRUCTURAL3/6/2019 3/12/2019 PASS
DetailsJulie Romig
KPFF 2nd Review
Routing PW Street Lights3/6/2019 3/8/2019 PASS
DetailsTom Marshall
Routing - Design Review3/6/2019 3/6/2019 FAIL
DetailsAndrea Tuning
The applicant should consolidate the parcels into one large parcel or enter into a cross access/shared parking agreement in regard to parking, pedestrian networks and trash collection.
Provide a minimum of 66 bicycle parking spaces on the site with 17 of these spaces being covered. To provide a safe, covered and efficient location for the bicycles, the applicant will be required to design the spaces to be a minimum of 6 feet long and 2.5 feet wide and have an overhead clearance of 7-feet if covered. A 4-foot wide aisle is required between rows of bicycle parking or nearby walls. Stationary racks shall be located on improved non-permeable surfaces and anchored to the ground.
Replace the street trees on Susan Drive that were removed from this version of the landscape plan.
All light poles and fixtures shall be located outside of the required setbacks and landscape planters which contain trees as required by the landscape ordinance. All lighting shall also be designed and located so as to prevent glare or direct light from falling onto adjoining properties or streets. The illumination of all light fixtures shall not exceed two foot candles as measured 1-foot above the ground at property lines shared with residentially zoned or used parcels. All new pole lighting shall feature 100 percent cut-off light fixtures and all new wall lighting shall have full cut-off shields.
Routing - PLANNING3/6/2019 3/6/2019 FAIL
DetailsDavid Moser
need a cross access and parking agreement and 48 bike parking are shown and 66 required, need more information on bike parking spaces.
Route to Impact Fee Review2/13/20192/16/20192/14/2019 PASS
DetailsShannon Cade
Review requested for Commercial Permit
1st review completed  2/12/2019 FAIL
DetailsJulie Romig
Routing - PLAN CHECK1/3/2019 2/12/2019 FAIL
DetailsJulie Romig
Routing - FIRE1/2/20191/3/20192/5/2019 PASS
DetailsMark Scharfen
IFC Fire Code review uploaded and complete.
Routing Off Site - STRUCTURAL1/3/2019 1/16/2019 FAIL
DetailsJulie Romig
KPFF
Routing PW Drainage1/4/2019 1/14/2019 PASS
DetailsBrian Murphy
Routing PW Sewer Design1/4/2019 1/14/2019 FAIL
DetailsDeAnn Brown
See changemarks in eplanreview. Contact DeAnn Brown ###-#### for record drawings.
Routing - Addressing1/3/2019 1/10/2019 PASS
DetailsDoug Chausow
New address: 974 N Maple Grove Rd
Routing - PUBLIC WORKS1/3/2019 1/10/2019 PASS
DetailsMorgan Webb
Routing - Erosion and Sediment1/3/2019 1/9/2019 PASS
DetailsAndy J. Long
ESC site map and SWPPP approved. RP tbd, must be provided before permit may be issued . Site preparation inspection is REQUIRED
Routing - MECHANICAL1/3/2019 1/9/2019 PASS
DetailsTroy James
Routing PW Solid Waste1/4/2019 1/4/2019 PASS
DetailsEvan Carpenter
Routing PW Street Lights1/4/2019 1/4/2019 PASS
DetailsTom Marshall
Routing - PLUMBING1/3/2019 1/3/2019 PASS
DetailsDaryl Spivey
Per plan and ISPC.
Routing - Design Review1/3/2019 1/3/2019 FAIL
DetailsAndrea Tuning
The applicant should consolidate the parcels into one large parcel or enter into a cross access/shared parking agreement in regard to parking, pedestrian networks and trash collection.
Provide a minimum of 66 bicycle parking spaces on the site with 17 of these spaces being covered. To provide a safe, covered and efficient location for the bicycles, the applicant will be required to design the spaces to be a minimum of 6 feet long and 2.5 feet wide and have an overhead clearance of 7-feet if covered. A 4-foot wide aisle is required between rows of bicycle parking or nearby walls. Stationary racks shall be located on improved non-permeable surfaces and anchored to the ground.
All light poles and fixtures shall be located outside of the required setbacks and landscape planters which contain trees as required by the landscape ordinance. All lighting shall also be designed and located so as to prevent glare or direct light from falling onto adjoining properties or streets. The illumination of all light fixtures shall not exceed two foot candles as measured 1-foot above the ground at property lines shared with residentially zoned or used parcels. All new pole lighting shall feature 100 percent cut-off light fixtures and all new wall lighting shall have full cut-off shields.
Intake Approval  1/2/2019 PASS
DetailsJoe Bruce
Prescreen approval by JHB
Intake Approval  12/26/2018 FAIL
DetailsJoe Bruce
1) The Verification of Legal Lot or Parcel is required to be signed by out planning and zoning staff prior to being submitted for a permit. Please contact Sue Cummings for more info: ###-####, scummings@cityofboise.org
2) Plan sheets do not have the required space reserved for City approval stamps as specified in the Electronic Plans Submittal Standards. Revise sheets with a blank 4” x 2” (4"x4" on cover) space located 3” off the right sheet edge to allow for the title block. Verify ALL plan sheets have the required space for city approval stamp.
3) Sheet A1.0, A1.1, and A1.2 could not be located. Upload these drawings or revise sheet index on cover page to exclude these sheets.
Application received  12/20/2018 DONE
Application submitted via PDS Online on Dec 20 2018 3:07PM
Routing - PLANNING1/3/2019   FAIL
The applicant should consolidate the parcels into one large parcel or enter into a cross access/shared parking agreement. Provide 66 bicycle parking spaces on the site with 17 of the spaces covered.