Permit Information
Permit NumberFIR19-00418
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 5992 E BARBER DR
Project NameHARRIS RANCH LOT 98
Customer Number 
ePlanReviewYes
Description
TFSS TO INSTALL A NEW NFPA 13D FIRE SPRINKLER SYSTEM IN THIS NEW SINGLE FAMILY DWELLING.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/24/201910/25/201910/25/2019APASS
DetailsJim Page
Previously noted items have benn corrected, final fire sprinkler inspection complete.

Backflow replaced with a double check valve as designed. Please call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Final Inspection10/21/201910/22/201910/22/2019PFAIL
DetailsJim Page
Backflow installed for fire sprinklers is a RPBA (reduce pressure backflow assembly), calculations for sprinkler system were designed with a double check, not and RP. System will need to be re-calculated for water flow demand or install double check as shown on city approved drawings.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Final Inspection10/21/201910/21/201910/21/2019ACANC
DetailsTroy Cobbley
Canceled due to time constraints.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
Fees Due Hold10/17/2019 10/21/2019 DONE
Details
INSP-Final Inspection10/16/201910/16/201910/16/2019AFAIL
DetailsTroy Cobbley
***Failed - None of the items on the last inspection have been corrected. MAS***
Call James before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello
INSP-Final Inspection9/17/20199/18/20199/18/2019PFAIL
DetailsJim Page
Sprinkler escutcheon does not cover entire hole in 3 areas, master closet, master bedroom and sidewall under stairs. Sprinkler timer is sitting on garage floor, sprinkler timer must be in place and permanent wiring installed before final inspection.

Call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in6/19/20196/20/20196/20/2019APASS
DetailsJim Page
All tenting in place at time of inspection, cover approved for all overhead fire sprinkler piping.

Tenting Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in6/18/20196/19/20196/19/2019PFAIL
DetailsJim Page
Tenting had not been started at time of inspection, request will need to be rescheduled.

Tenting Inspection, should be ready by afternoon. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
INSP-Sprinkler Rough-in6/14/20196/14/20196/14/2019PPART
DetailsJim Page
Partial rough to cover inspection for overhead fire sprinkler piping complete, piping between conditioned spaces approved for cover, tenting inspection to be completed at a later date, areas requiring tenting not approved for cover.
INSP-Sprinkler Rough-in/Hydro6/13/20196/14/20196/14/2019ADONE
DetailsJim Page
Hydrostatic test witnessed at 150psi instead of static city pressure, no pressure loss observed.

Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
Issue and Print Permit  6/12/2019 DONE
Application received  6/10/2019 DONE
Application submitted via PDS Online on Jun 10 2019 10:18AM
Intake Approval  6/10/2019 PASS
DetailsMark Stumbaugh
Plan assigned to (Stumbaugh)6/10/2019 6/10/2019 DONE
DetailsMark Stumbaugh
Sprinkler Plan Check6/10/2019 6/10/2019 PASS
DetailsMark Stumbaugh
PLANS/APPL TAKEN TO FRONT DESK  6/10/2019 DONE
DetailsMark Stumbaugh
Permit Ready to Issue  6/10/2019 DONE
met