Permit Information
Permit NumberBLD19-02464
StatusIssued
Name DAVE EVANS CONSTRUCTION
Site Address 101 S ALLUMBAUGH WAY
Project NameChildren's Therapy Place
Customer Number 
ePlanReviewYes
Description
(CHILDREN’S THERAPY PLACE – NEW TWO STORY BUILDING) (DRH19-00094) (12-31-19 PLAN MODIFICATION TO INSTALL AN ELECTRIC OVEN WITH A COOKTOP AND A STANDARD DOMESTIC HOOD WITHIN THE 1ST STORY BREAKROOM. COOKING OPERATIONS THAT CREATE GREASE LADEN VAPORS ARE NOT ALLOWED. A WORK SURFACE ACCESSIBLE TO THE DISABLED LOCATED NEXT TO THE RANGE WITH KNEE AND TOE CLEARANCE FOR A FRONT APPROACH WILL BE PROVIDED. KNEE AND TOE CLEARANCE FOR A FRONT APPROACH TO THE BREAKROOM SINK WILL ALSO BE PROVIDED. CLARIFICATION CHANGES WERE ALSO MADE TO THE DRAWINGS TO INCLUDE TEMPERED GLASS NEAR THE SWIMMING POOL, DECK DRAIN AT THE SWIMMING POOL, ETC.) The fire sprinkler system is used for fire flow and to substitute for 1-hr corridors. To construct a two story building having a total floor area of about 18,281 square feet (9,866 square feet 1st story and 8,415 square feet 2nd story). In addition, the 2nd story will have a 902 square foot occupied roof with a seasonal membrane shade structure above it. Work is to include concrete footings; concrete stem walls; a concrete elevator pit; a concrete pool pit; concrete slabs on grade with slabs thickened below interior bearing walls; wood stud bearing walls and shear walls; steel columns; steel beam; wood floor trusses with wood sheathing and gypcrete topping; wood roof trusses with wood structural panel decking, standing seam metal roofing, and/or single-ply membrane roof covering over R-35 continuous rigid insulation on top of the roof deck; adjustable pedestal concrete tile pavers above the roof covering at the occupied roof; exterior wood stud walls with wood structural panels and furred out sections with metal panel siding, or cement stucco, or manufactured stone finishes; exterior storefront windows; exterior storefront doors; steel awnings; interior walls; four multi-user toilet rooms accessible to the disabled; four single-user toilet rooms accessible to the disabled; two interior stairways; interior doors; interior windows; horizontal sliding partitions; a therapy pool; millwork; and finishes. Special Inspection is required for soils and for steel (including bolting and welding). Engineered trusses are a deferred submittal item. A masonry trash enclosure with steel gates will also be constructed on site. A 4 foot high non-climbable fence will be constructed around a playground. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. A separate permit is required for the therapy pool. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final8/13/20208/13/20208/13/2020PPART
DetailsMike Jordan
Ed *screened Phone #: ###-####. OK for temp occ. once mech. passes final.
FIRE-Final Inspection8/4/20208/6/20208/6/2020APART
DetailsTroy Cobbley
A temp for life safety until the project related fire alarm permit has been finaled.

Ed- */Screened*/ Phone #: ###-#### 7am inspection
FIRE-Final Inspection7/29/20207/30/20207/30/2020PFAIL
DetailsTroy Cobbley
Need the project related fire alarm permit finaled, need signs for fire dept access at the two entrances, need signage on electrical room door, need to test the door mags on main entrance.

Screened- ED Phone #: ###-####
BLD-Ceiling Grid Inspection6/18/20206/19/20206/19/2020APASS
DetailsMike Jordan
screened // Ed Phone #: ###-####. 1st. floor ok.
BLD-Ceiling Grid Inspection6/15/20206/15/20206/15/2020PPASS
DetailsMike Jordan
Ed Phone #: ###-####. 2nd. floor grid and east stairwell only.
BLD-Ceiling Grid Inspection5/15/20205/15/20205/15/2020PPASS
DetailsMike Jordan
Ed Phone #: ###-####. HArdlid in pool room ok.
BLD-Energy code compliance5/15/20205/15/20205/15/2020PPASS
DetailsMike Jordan
Ed Phone #: ###-####. 2nd floor above ceiling ok.
BLD-Energy code compliance5/12/20205/12/20205/12/2020PCANC
DetailsMike Jordan
Ed *screened* Phone #: ###-####
BLD-Energy code compliance5/6/20205/7/20205/7/2020PPASS
DetailsMike Jordan
Ed *screened* Phone #: ###-####. Pool room, north half of first floor.
BLD-Energy code compliance5/1/20205/4/20205/4/2020PCANC
DetailsMike Jordan
screened // Ed Phone #: ###-####
BLD-Energy code compliance5/4/20205/4/20205/4/2020PPASS
DetailsMike Jordan
screened // Ed Phone #: ###-####. 1st. floor south half.
BLD-Energy code compliance4/28/20204/29/20204/29/2020APASS
DetailsMike Jordan
Ed *cleared* Phone #: ###-####. 2nd. floor North half.
BLD-Energy code compliance4/23/20204/24/20204/24/2020APASS
DetailsMike Jordan
screened // Ed Phone #: ###-####. 2nd floor, south half. fire blocking, 1st and 2nd. floors.
BLD-Framing/Rough-in4/14/20204/14/20204/14/2020PPASS
DetailsMike Jordan
Ed **Cleared** Phone #: ###-####. 1st and 2nd. floor.
BLD-Framing/Rough-in4/9/20204/10/20204/10/2020APART
DetailsMike Jordan
screened // Ed Phone #: ###-####. Needs to complete airseal. ok to one side.2nd. floor.
BLD-Framing/Rough-in4/1/20204/2/20204/2/2020APASS
DetailsMike Jordan
Ed Phone #: ###-####. Ok to insulate roof deck and 2nd floor were discussed. All missing holdowns have been installed.
FIRE-Conference3/13/20203/13/20203/13/2020PDONE
DetailsTroy Cobbley
Ed and I discussed the combustible concealed pockets.

Ed Phone #: ###-####
BLD-Other3/10/20203/11/20203/11/2020APASS
DetailsMike Jordan
2 hour wall for elevator shaft inspection - Ed Phone #: ###-####. Per the architect, the 2hr. assembly on plans is in correct and has provided the correct assembly.
BLD-Wall Bracing3/10/20203/11/20203/11/2020APASS
DetailsMike Jordan
Ed Phone #: ###-####. All nailing on interior and exterior walls ok. All floor to floor straps ok except at pool area and at east interior stairs.
BLD-Framing/Rough-in3/6/20203/6/20203/6/2020PPART
DetailsMike Jordan
Ed Phone #: ###-####. @hr. shaft for elevator. Need to verify type of sheet rock being used. GA file notes 1/2" type C, contractor has used 5/8 type X.
BLD-Wall Bracing3/4/20203/5/20203/5/2020APART
DetailsMike Jordan
SHEAR // Ed Phone #: ###-####. Exterior and interior shear wall nailing. Needs to install all floor to floor straps, and fasten missed areas. Also received RFI ok an additional 7/16 OSB on high roof and noting 7/16 over pool area is ok due to 12" oc roof truss spacing.
BLD-Framing/Rough-in2/28/20203/2/20203/2/2020APASS
DetailsMike Jordan
roof nailing // Ed Phone #: ###-####. Main roof structure.
BLD-Wall Bracing2/20/20202/21/20202/21/2020APART
DetailsMike Jordan
Ed Phone #: ###-####. East exterior wall, 1st floor. Portion were meter pack is to be set only ok.
BLD-Foundation1/3/20201/3/20201/3/2020PPASS
DetailsMike Jordan
Ben Phone #: ###-####. remainder of interior thickend footings ok.
BLD-Foundation12/24/201912/26/201912/26/2019PPART
DetailsDave Hannah
Ben Phone #: ###-#### int ftgs ok to pour
BLD-Foundation12/23/201912/24/201912/24/2019AFAIL
DetailsMike Jordan
Ben Phone #: ###-####
BLD-Foundation12/20/201912/23/201912/23/2019ANR
DetailsMike Jordan
inspection not in plan mod location // Ben Phone #: ###-####
BLD-Foundation12/15/201912/16/201912/16/2019APASS
DetailsMike Jordan
Phone #: 2086971241 >> Inspection requested via mobile web by Heron. Elevator pit walls and walls around swimming pool ok.
BLD-Foundation12/9/201912/9/201912/9/2019PPASS
DetailsBrandon Shaw
Perimeter foundation...
BLD-Footing12/1/201912/2/201912/2/2019PPASS
DetailsMike Jordan
Phone #: 2089109404 >> Inspection requested via mobile web by Ricardo aggregate constru. Elevator pit, step footings and footings at pool ok.
BLD-Footing11/26/201911/27/201911/27/2019PPASS
DetailsMike Jordan
Phone #: 2086971241 >> Inspection requested via mobile web by Heron . Perimeter footings only, excluding step down areas by pool, pool footings and elevator pit.
BLD-Footing11/25/201911/26/201911/26/2019PNR
DetailsMike Jordan
Phone #: 2089109404 >> Inspection requested via mobile web by Ricardo aggregate constru
BLD-Footing11/24/201911/25/201911/25/2019PCANC
DetailsMike Jordan
Phone #: 2089109404 >> Inspection requested via mobile web by Ricardo aggregate constru. Cancelled by contractor via phone call.
BLD-Footing11/22/201911/22/201911/22/2019PCANC
DetailsMike Jordan
Phone #: 2089109404 >> Inspection requested via mobile web by Ricardo aggregate constru Inspection cancelled via mobile web on Friday, November 22, 2019.