Permit Information
Permit NumberELE18-02369
StatusFinaled
Name QUALITY ELECTRIC INC
Site Address 1290 W MYRTLE ST
Project Name 
Customer Number 
ePlanReviewNo
Description
New:
(PIONEER CROSSING OFFICE BUILDING) Permit for the buildout of the core and shell with work to include, restrooms, elevators, entry lobby, electrical, mechanical and fire sprinkler systems per the approved plans.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/3/20196/4/20196/4/2019PPASS
DetailsRock A. Hudson
Call Joey C. prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
Final ok
Final6/3/20196/3/20196/3/2019PFAIL
DetailsRock A. Hudson
Call Joey Campbell prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
110.22- Each roof top unit shall be identified as per which disconnecting means operates it.
314.20= Boxes that are not flush with combustible materials shall be extented to be flush. All receptacles in electrical room on all floors.
Final5/20/20195/21/20195/21/2019PFAIL
DetailsRock A. Hudson
Call Joey C. prior to arrival Phone #: ###-#### Inspection requested via web by Scott Campbell
300.15- All wiring shall terminate in a box. Switch leg for accent LED tape light hanging at misc locations. 120 volt dampers not complete.
314.25- All boxes shall have covers. Misc found on level 1.
Electrical Rough-In5/14/20195/16/20195/16/2019PPASS
DetailsRock A. Hudson
Exterior trenching and conduit on west and south sides of building. Call Joey C. prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
Areas noted underground rough in ok cover
Conference5/10/20195/13/20195/13/2019ADONE
DetailsRock A. Hudson
Request for consultation to meet requirements for building temporary occupancy. Phone #: ###-#### Inspection requested via web by Scott Campbell
Discussed requirements for TCO of core and shell. All emergency lighting, interior and exterior egress lighting, gererator shall be operational and commissioning reports complete. All unfinished wiring shall terminate in a box.
Electrical Rough-In5/10/20195/13/20195/13/2019APASS
DetailsRock A. Hudson
3rd and 4th Floor Ceiling Inspection for cover. Phone #: ###-#### Inspection requested via web by Scott Campbell
Levels 3 and 4 grid rough in ok cover
Electrical Rough-In4/29/20194/30/20194/30/2019PPASS
DetailsRock A. Hudson
1st ; 2nd Floor Ceilings. Generator Grounding Electrode. Call Joey C. prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
Generator GES and level 1 and 2 corridor grid rough in ok cover
Electrical Rough-In4/25/20194/26/20194/26/2019APASS
DetailsRock A. Hudson
1st floor vestibules. Call Joey C, prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
HVAC to be installed after cover. Rough in ok cover.
Electrical Rough-In4/23/20194/24/20194/24/2019PPASS
DetailsRock A. Hudson
Bank Canopy hardlid, two vestibule hardlid, 1st ceiling t-grid inspection. Call Joey C prior to arrival Phone #: ###-#### Inspection requested via web by Scott Campbell
Vestibules and grid not ready,
Bank canopy hard lid rough in ok cover
Electrical Rough-In4/22/20194/22/20194/22/2019PPART
DetailsRock A. Hudson
Two exterior canopies and 5th Floor elevator lobby. Call Joey C. prior to arrival. If no answer, call Ben M. at ###-####. Phone #: ###-#### Inspection requested via web by Scott Campbell
300.11- Ceiling support system shall not support raceways or cable unless manufacturers instructions state system has been tested for support of such cables and raceways. Contractor is checking instructions.
Level 5 elevator lobby wall and south lobby hardlid rough in ok cover
Electrical Rough-In4/16/20194/17/20194/17/2019APASS
DetailsRock A. Hudson
1st through 4th floor elevator lobby wall inspection. Call Joey Campbell prior to arrival. If no answer call Ben MacDonagh at ###-####. Phone #: ###-#### Inspection requested via web by Scott Campbell
Verified main bonding jumper installed at generator.
Elevator lobby walls levels 1 thru 4 rough in ok cover
Electrical Rough-In4/16/20194/16/20194/16/2019PNH
DetailsRock A. Hudson
1st through 4th Floor elevator lobby wall rough-in. Call Joey Campbell prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
Called twice unable to leave message, mail obx full. Recall when available.
Permanent Service4/10/20194/12/20194/12/2019PCANC
DetailsRock A. Hudson
Call Joey Campbell prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
Needed rough in inspection.
Electrical Rough-In4/12/20194/12/20194/12/2019PPASS
DetailsRock A. Hudson
Call Joey Campbell prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
Discussed the work depth for HVAC unit on roof disconnecting means at 480 volt.
As per 110.26(A)(1) a minimum depth of 3'6" shall be present. Disconnects will have to be moved to another location.
Energize sub gear on all floors rough in ok.
Permanent Service4/8/20194/8/20194/8/2019PPASS
DetailsRock A. Hudson
Joey ###-#### p/s u/g n ok
Permanent Service4/1/20194/8/20194/8/2019ANR
DetailsRock A. Hudson
Joey Phone #: ###-####
Field testing being performed at time of inspection as per 230.95(C).
110.24- Available fault current shall be posted prior to permanent service inspection
Electrical Rough-In4/8/20194/8/20194/8/2019PPASS
DetailsRock A. Hudson
Joey Phone #: ###-####
Bollard bases east end and pole bases north side rough in ok cover
Electrical Rough-In3/21/20193/21/20193/21/2019PPASS
DetailsRock A. Hudson
Underground conduit install rough-in for cover. Call Joey Campbell prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
N.E. 3 post bases and underground rough in ok cover
Electrical Rough-In3/5/20193/6/20193/6/2019PPASS
DetailsRock A. Hudson
Call Joey Campbell prior to arrival. Fifth floor hardlids. Phone #: ###-#### Inspection requested via web by Scott Campbell
Level 5 hardlids in bathrooms and elevator lobby rough in ok cover
Electrical Rough-In2/22/20192/25/20192/25/2019PPASS
DetailsRock A. Hudson
Call Joey C prior to arrival. North and South Stairwell hardlid inspection Phone #: ###-#### Inspection requested via web by Scott Campbell
Level 1 north and south stair hardlid as noted on contractor print rough in ok cover
Electrical Rough-In2/12/20192/14/20192/14/2019PPASS
DetailsRock A. Hudson
Call Joey C prior to arrival. Rough in for hardlids floors 2-4. Phone #: ###-#### Inspection requested via web by Scott Campbell
Levels 2,3,4 elevator lobbies and tape lighting wiring and level 5 tape wiring only as noted on contractor print rough in ok cover
Electrical Rough-In2/6/20192/7/20192/7/2019PPASS
DetailsRock A. Hudson
3rd and 4th floor restroom ceiling rough-in. 5th floor wall rough-in. Call Joey Campbell prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
Areas as noted and marked on contractor print rough in ok cover.
Electrical Rough-In1/29/20191/30/20191/30/2019PPASS
DetailsRock A. Hudson
Rough in for North stairwell 2nd floor. Phone #: ###-#### Inspection requested via web by Scott Campbell
All of north stair walls and level 2 bathroom hardlids as noted on contractor print rough in ok cover
Electrical Rough-In1/22/20191/23/20191/23/2019APASS
DetailsRock A. Hudson
Call Joey C at 208 ###-#### prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
South stairway walls complete 1 thru 5 rough in ok cover
Electrical Rough-In1/21/20191/22/20191/22/2019ACANC
DetailsJames Ady
Call Joey C at ###-#### prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell will recall for AM inspection
Electrical Rough-In1/14/20191/16/20191/16/2019PPASS
DetailsRock A. Hudson
1st Floor hardlid areas. Call Joey C. prior to arrival. ###-####. Phone #: ###-#### Inspection requested via web by Scott Campbell Level 1 elevator lobby, clouds, bathrooms hardlids and south stair levels1 to 2 1/2 wall rough in ok cover
Electrical Rough-In1/14/20191/17/20191/14/2019PCANC
DetailsRock A. Hudson
1st Floor hardlid areas. Call Joey C. prior to arrival. ###-####. Phone #: ###-#### >> Inspection requested via web by Scott Campbell Inspection cancelled from web by: Scott Campbell
Conference1/10/20191/10/20191/10/2019PPASS
DetailsRock A. Hudson
Discussed with Ben temporary power requirements for job site. Having issues with tripping circuit taking out multiple floors. As long as temporary power complies with 590.6(B)(1)(2)(3) ok to make changes to reduce tripping issues.
Electrical Rough-In1/7/20191/9/20191/9/2019APASS
DetailsRock A. Hudson
WALL ROUGH-IN INSPECTION FOR FIRST AND FOURTH FLOOR. CALL JOEY C AT ###-#### PRIOR TO ARRIVAL. Phone #: ###-#### Inspection requested via web by Scott Campbell
Informed seperate electrical permit required for elevators.
Level 1 mail room, demizing wall, east exterior wall only. No stairway walls.
Level 4 bathrooms and corridor as noted on contractor print wall rough in ok cover
Electrical Rough-In12/21/201812/21/201812/21/2018PPASS
DetailsRock A. Hudson
Contractor called and asked if ok to 1-side electrical rooms only. OK to cover 1 side of 2 electrical rooms only rough in ok cover
Electrical Rough-In11/19/201811/20/201811/20/2018APASS
DetailsRock A. Hudson
Wall rough-in inspection on floors 2 and 3. Contact is Joey Campbell Phone #: ###-#### Inspection requested via web by Scott Campbell Walls- level 1 from center to west exterior lighting, level 2 corridors, bathrooms, electrical rm, level 3 bathrooms and electrical room.
All marked and dated in blue on contractor print rough in ok cover
Electrical Rough-In10/31/201811/2/201811/2/2018APASS
DetailsRock A. Hudson
Please call Joey Campbell at ###-#### prior to arrival. 1st floor wall inspection. Phone #: ###-#### Inspection requested via web by Scott Campbell
Fire riser room, bathrooms, corridors and noted in orange on contractor print wall rough in ok cover
Temporary Service8/8/20188/8/20188/8/2018PCANC
DetailsRock A. Hudson
Please call Joey Campbell @ ###-#### 30 minutes prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell needed temp service. seperate permit required.
Electrical Rough-In8/3/20188/6/20188/6/2018APASS
DetailsRock A. Hudson
If possible, please see if this inspection can be the first inspection of the day.
Call Joey Campbell at ###-#### prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
Service entrance conduits rough in ok cover
Electrical Rough-In7/23/20187/23/20187/23/2018PPASS
DetailsRock A. Hudson
Joey Phone #: ###-####
Note: If an inspection is needed time shall be provided to complete and inspect before cover. Concrete encased electrode rough in ok cover
Electrical Rough-In7/18/20187/23/20187/23/2018APASS
DetailsRock A. Hudson
Please call Joey Campbell @ ###-#### 20 minutes prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
Underslab conduits to east of electrical room rough in ok cover