INSP-Final Inspection | 9/27/2019 | 9/27/2019 | 9/27/2019 | A | PASS |
Jim Page
|
|
|
Plan mods have been approved and verified, final fire alarm inspection is complete
|
INSP-Sprinkler Rough-in/Hydro | 9/27/2019 | 9/27/2019 | 9/27/2019 | P | CANC |
Jim Page
|
|
|
Wrong inspection type for inspection request, this request is cancelled.
.
David Phone #: ###-####
|
INSP-Final Inspection | 9/12/2019 | 9/13/2019 | 9/13/2019 | P | PART |
Jim Page
|
|
|
Initiating devices in common areas tested. Audio visual notification has been tested. Fire sprinkler initiating devices has been tested. Notification to be added in trash rooms on each floor, will verify before final C of O. Monitoring has been verified.
David Phone #: ###-####
|
INSP-Final Inspection | 9/11/2019 | 9/12/2019 | 9/12/2019 | P | FAIL |
Jim Page
|
|
|
Panel shows ground fault trouble, needs to be corrected. FDC bell only rings with level 1 stair 2 riser, no other flow switches are hooked to bell, FDC bell needs to ring during all water flow events.
Trey Phone #: ###-####
|
INSP-Final Inspection | 9/6/2019 | 9/9/2019 | 9/9/2019 | A | FAIL |
Jim Page
|
|
|
Audio intelligibility not met in numerous areas. Smoke detector in ADA room on level 1 overspaced, detector is more than 21 foot from corner of room. A/V device in level 1 elevator lobby is overspaced. Notated city approved draiwngs other areas requiring correction. Inspection was stopped on level 2 due to deficiencies noted, all fire sprinkler and initiating devices still and audio visual coverage still need inspected. Monitoring account has been verified, have not checked signals with monitoring as of this entry.
David Phone #: ###-####
|
INSP-Final Inspection | 9/5/2019 | 9/6/2019 | 9/6/2019 | P | FAIL |
Jim Page
|
|
|
Walkthrough on level 1 performed, notated city approved drawings with red ink areas requiring correction, inspection stopped on level 1 due to amount of items marked. No sprinkler monitoring devices or initiating devices tested.
David Phone #: ###-####
|
INSP-Final Inspection | 8/30/2019 | 8/30/2019 | 8/30/2019 | P | CANC |
Jim Page
|
|
|
Cancelled per conversation with point of contact, will be rescheduled for a later date.
Tre Phone #: ###-####
|