Permit Information
Permit NumberBLD18-04294
StatusFinaled
Name KIER CONSTRUCTION CORPORATION
Site Address 10577 W FAIRVIEW AVE
Project NameMaverik
Customer Number 
ePlanReviewYes
Description
(MAVERIK) Permit to construct a new 4,224 sq. ft. retail convenience store building, a 2,843 sq. ft. fuel canopy and related site improvements. Approval is contingent upon adhering to the approved plans on file, DRH18-00416, plan review report and attached engineering. Scope of work includes: construction of foundation, concrete slab on grade, construction of fuel canopy, construction of steel stud framed exterior building envelope walls, roof construction, construction of interior non-bearing walls to create a retail area, an office, men’s and women’s accessible restrooms, kitchen area, storage areas, a pump room, (3) coolers and a freezer, new windows and doors, new electrical, new mechanical, new plumbing, site work, and interior finishes to be in compliance with Ch. 8 of the 2015 IBC. The building is not fire sprinklered. Note: Special Inspections Required see form 310. **JG**
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Telephone call  5/21/2020 DONE
spoke with Ben project manager about the electrical value provided and he said there was only one electrical contractor- called electrical contractor and left message to get final value cleared up. 5/27/2020 JCA//working n the Final valule- need to do trait permits
Third Notice 4/8/20205/7/2020 DONE
mailed 5-8-2020
Second Notice 3/15/20204/3/2020 DONE
mailed 4-6-2020
First Notice 2/20/20203/5/2020 DONE
mailed 3-6-20
PubWorks Occupancy Approval2/10/20202/10/20202/10/2020 DONE
DetailsTiffany Lowery
Permanent Occupancy  2/10/2020 DONE
BLD-Final2/7/20202/7/20202/7/2020PPASS
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Roger Graves. Ok for perm occ.
BLD-Final2/6/20202/10/20202/7/2020ACANC
DetailsMike Jordan
Phone #: ###-#### >> Inspection requested via web by Roger Graves Inspection cancelled from web by: Roger Graves
Zoning Approval2/7/20202/7/20202/7/2020 PASS
DetailsJosh Wilson
FIRE-Final Inspection2/5/20202/6/20202/6/2020PPASS
DetailsTroy Cobbley
Life safety passed.

Phone #: ###-#### Inspection requested via web by Roger Graves
FIRE-Final Inspection1/27/20201/29/20201/29/2020PFAIL
DetailsTroy Cobbley
See the Fire life safety review comments for items marked in red that need addressed. It includes testing of the three emergency off switches, duct smoke detectors, adding exit discharge lighting at the Store Room exit, removing the dead bolt at the Beer Cooler, removing the thumb turn dead bolts at both main exit doors, providing an operational permit for the tank storage/exchange, 6" island's....ect.

Phone #: ###-#### Inspection requested via web by Roger Graves
Print Occupancy Form  1/23/2020 DONE
BLD-Ceiling Grid Inspection1/21/20201/22/20201/22/2020APASS
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Roger Graves
BLD-Ceiling Grid Inspection1/20/20201/21/20201/21/2020APART
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Roger Graves
BLD-Energy code compliance12/6/201912/6/201912/6/2019PPASS
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Roger Graves. Remaining walls ok to cover.
BLD-Framing/Rough-in12/5/201912/5/201912/5/2019PPASS
DetailsMike Jordan
Soffits and hardlids ok.
BLD-Energy code compliance12/5/201912/5/201912/5/2019PPART
DetailsMike Jordan
exterior walls except at cooler ares.
BLD-Energy code compliance12/4/201912/5/201912/5/2019ACANC
DetailsMike Jordan
Requesting a mid morning inspection if possible. thank you Phone #: ###-#### Inspection requested via web by Roger Graves
BLD-Framing/Rough-in12/2/201912/3/201912/3/2019APASS
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Roger Graves. walls only. Ok to insulate.
BLD-Wall Bracing12/2/201912/3/201912/3/2019APASS
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Roger Graves
BLD-Wall Bracing11/25/201911/25/201911/25/2019PFAIL
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Roger Graves. Not all blocking or screws installed.
BLD-Wall Bracing11/14/201911/14/201911/14/2019AFAIL
DetailsMike Jordan
Install all blocking as shown on plans and additional strapping on interior side of building with the required additional screws.
BLD-Wall Bracing11/14/201911/14/201911/14/2019ACANC
DetailsMike Jordan
BLD-Wall cover11/12/201911/13/201911/14/2019PCANC
DetailsMike Jordan
Requesting a partial wall cover for house keeping walls. Phone #: ###-#### Inspection requested via web by Roger Graves
BLD-Wall Bracing11/12/201911/13/201911/14/2019PCANC
DetailsMike Jordan
Requesting a later PM inspection Phone #: ###-#### Inspection requested via web by Roger Graves
BLD-Foundation10/16/201910/17/201910/17/2019PDEFR
DetailsMike Jordan
Concrete is scheduled for 1:00 pm Phone #: ###-#### Inspection requested via web by Roger Graves. ok pending special inspection.
BLD-Footing10/11/201910/14/201910/14/2019PPASS
DetailsMike Jordan
Concrete is scheduled for 2:00 pm Phone #: ###-#### Inspection requested via web by Roger Graves
BLD-Foundation5/20/20195/21/20195/22/2019PDEFR
DetailsMike Jordan
Trash enclosure foundation inspection. Concrete is scheduled for 3 pm. Phone #: ###-#### Inspection requested via web by Roger Graves. Will have special inspection.
BLD-Footing5/17/20195/20/20195/20/2019APASS
DetailsMike Jordan
Trash enclosure footing inspection. Concrete is scheduled for 11:00 am. Phone #: ###-#### Inspection requested via web by Roger Graves. Will hace special inspections as well for project as noted.
BLD-Foundation5/16/20195/17/20195/17/2019ACANC
DetailsMike Jordan
Trash enclosure footing inspection. Have an 11:00 am concrete pour scheduled. Phone #: ###-#### >> Inspection requested via web by Roger Graves Inspection cancelled from web by: Roger Graves
BLD-Footing5/15/20195/17/20195/16/2019ACANC
DetailsMike Jordan
Trash enclosure footing inspection Phone #: ###-#### >> Inspection requested via web by Roger Graves Inspection cancelled from web by: Roger Graves
Issue PAID IN FULL permit  4/11/2019 DONE
Print Occupancy Form  4/11/2019 DONE
OVERRIDE  3/29/2019  
Plan assigned to (JG)12/6/201812/6/20183/29/2019 PASS
DetailsJavier Guzman
4th rev, 1/09 New Maverik ePlan, pend ng
Routing Off Site - STRUCTURAL3/20/2019 3/29/2019 PASS
DetailsJavier Guzman
signed off in ePlan by AHJ Engineers Chris Holladay
PLANS/APPL TAKEN TO FRONT DESK  3/29/2019 DONE
Permit Ready to Issue  3/29/2019 DONE
Met-
need RP


MET-
Need GC
Need Rev cert of val
Routing - PLAN CHECK3/20/2019 3/28/2019 PASS
DetailsJavier Guzman
Routing PW Drainage3/20/2019 3/26/2019 PASS
DetailsBrian Murphy
Routing - PLAN CHECK2/21/2019 3/12/2019 PASS
DetailsJavier Guzman
Routing Off Site - STRUCTURAL2/21/2019 3/12/2019 FAIL
DetailsJavier Guzman
Failed in ePlan by AHJ Engineers Chris Holladay
Routing PW Drainage2/21/2019 3/4/2019 FAIL
DetailsBrian Murphy
NEED APDX J NO CONNECTION TO ACHD NO10 /HR PERC
Routing - PUBLIC WORKS2/21/2019 2/26/2019 PASS
DetailsMorgan Webb
Routing - PLUMBING2/21/2019 2/22/2019 PASS
DetailsDaryl Spivey
Install approved backflow on Yard hydrant.
Routing - PLAN CHECK2/6/2019 2/14/2019 FAIL
DetailsJavier Guzman
Routing Off Site - STRUCTURAL2/6/2019 2/14/2019 FAIL
DetailsJavier Guzman
Failed in ePlan by AHJ Engineers Chris Holladay
Routing PW Drainage2/6/2019 2/13/2019 FAIL
DetailsBrian Murphy
not 3 inch rock4.5 feet deep into clay? need original noterized and sign appenx j ACHD OK SEEPAGE BEDS ON PLAN MUST BE DIMEN.
Routing PW Sewer Design2/6/2019 2/7/2019 PASS
DetailsDeAnn Brown
Routing PW Solid Waste2/6/2019 2/7/2019 PASS
DetailsEvan Carpenter
Routing - PLUMBING2/6/2019 2/6/2019 FAIL
DetailsDan Ediger
Design per Idaho State Plumbing Code
See change-marks
Route to Impact Fee Review1/23/20191/26/20191/24/2019 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
1st review completed  1/23/2019 FAIL
DetailsJavier Guzman
Routing - FIRE12/6/201812/6/20181/22/2019 PASS
DetailsErika Akin
Attached comments to case
Routing - PLAN CHECK12/6/2018 1/7/2019 FAIL
DetailsJavier Guzman
Routing Off Site - STRUCTURAL12/6/2018 1/4/2019 FAIL
DetailsJavier Guzman
Failed in ePlan by AHJ Engineers Chris Holladay

Routing PW Sewer Design12/7/2018 12/11/2018 FAIL
DetailsDeAnn Brown
Refer to changemarks on sheet C.7. If there are any questions, please contact DeAnn Brown at ###-####.
Routing PW Solid Waste12/7/2018 12/11/2018 FAIL
DetailsEvan Carpenter
Solid waste enclosures with separate gate openings for each dumpster must have at least 12 feet of unobstructed clearance between gate posts. The center gate post will need to be removed, or each separate gate opening will need to have 12 feet of clearance.
Routing - Design Review12/6/2018 12/11/2018 PASS
DetailsJosh Wilson
Ok per DRH18-00416
Routing - MECHANICAL12/6/2018 12/10/2018 PASS
DetailsTroy James
Routing PW Environmental12/7/2018 12/10/2018 PASS
DetailsRick Christenson
1500 Gallon Exterior Grease Interceptor shown.
Routing - Addressing12/6/2018 12/10/2018 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS12/6/2018 12/7/2018 PASS
DetailsMorgan Webb
Routing - PLUMBING12/6/2018 12/7/2018 PASS
DetailsDaryl Spivey
Per plan and ISPC.
Routing PW Street Lights12/7/2018 12/7/2018 PASS
DetailsTom Marshall
Routing - PLANNING12/6/2018 12/6/2018 PASS
DetailsDavid Moser
See DRH18-00416
Routing - Erosion and Sediment12/6/2018 12/6/2018 PASS
DetailsMichael Zawacki
Valid Boise RP needed. If RP has Utah Certification they will need to get a ESC con#, class will not be needed.
Site prep inspection required.
Plan Reviewer's activity  12/5/2018 PASS
The plan intake review was approved
Intake Approval  11/29/2018 FAIL
11-29-18 Refer to the circled items in the plan intake checklist. Resolve each item as directed. CJW
Application received  11/27/2018 DONE
Application submitted via PDS Online on Nov 27 2018 2:17PM
Routing PW Drainage12/7/2018   FAIL
NO OVERFLOW TO ACHD PERC RATE 9' NOT 10'APDX J BED MUST GO THRU CLAY TO FREE DRAING