Permit Information
Permit NumberFIR19-00634
StatusFinaled
Name ALARMCO
Site Address 525 W JEFFERSON ST
Project NameIdaho State Bar
Customer Number 
ePlanReviewYes
Description
Replacement of existing Fire Alarm System. System will have sprinkler monitoring (basement only) Full smoke detection and notification in common areas. This work does not appear to be associated with a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/21/20201/23/20201/23/2020APASS
DetailsJim Page
Previously noted items have been corrected. Final fire alarm inspection is complete.

We would like this inspection for 8:00 am per the tenant''s request.
Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
INSP-Final Inspection1/14/20201/21/20201/21/2020ACANC
DetailsJim Page
We would like this inspection at 8:00 am per the tenant''s request.
Please call Nate at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
1st review completed  1/13/2020 DONE
Alarm Plan Check1/13/2020 1/13/2020 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  1/13/2020 DONE
As built - No Fee
Permit Ready to Issue  1/13/2020 DONE
as built met
CHANGE STATUS TO (ISS)  1/13/2020 DONE
Plan assigned to (Lee)1/3/2020 1/13/2020 DONE
DetailsLee G Meredith
as builts
Alarm Plan Check1/9/2020 1/9/2020 CANC
DetailsJoe Bruce
ePlan task sent back to Lori to upload corrections.
INSP-Final Inspection1/3/20201/6/20201/6/2020PCANC
DetailsJim Page
We would like this inspection at 1:00 pm. This is when the elevator company will be there along with the elevator inspector.
Please call Nate at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
Fees Due Hold12/19/2019 1/3/2020 DONE
Details
Plan resubmittals received  1/3/2020 DONE
lorie from Alarmco start as builts
INSP-Final Inspection12/12/201912/18/201912/18/2019AFAIL
DetailsJim Page
Elevator pit has fire sprinkler installed, provide smoke and heat detection in for shunt and recall as discussed. Notated city approved drawings where audio visual notification was overspaced. Verified monitoring, tested basement initiating devices, tested fire sprinkler tampers and flow switch, items tested all worked as required.

We would like this inspection to be done at 9:00 am.
Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
Plan assigned to (Lee)12/10/2019 12/12/2019 DONE
DetailsLee G Meredith
1st review completed  12/12/2019 DONE
Alarm Plan Check12/12/2019 12/12/2019 PASS
DetailsLee G Meredith
Plan Modification Accepted  12/12/2019 DONE
PLANS TAKEN FRONT DESK ALARM  12/12/2019 DONE
Plan mod passed. Minimum $65.00 review fee is due.
Permit Ready to Issue  12/12/2019 DONE
Plan Mod - Met
CHANGE STATUS TO (ISS)  12/12/2019 DONE
Plan resubmittals received  12/10/2019 DONE
as built
INSP-Final Inspection11/19/201911/21/201911/21/2019PFAIL
DetailsJim Page
Corridor spacing for smoke detection as well as audio visual notification for this project does not apply to most areas, numerous office walls shown on city approved drawings are half walls, smoke detection and audio visual notification will need to corrected, a plan mod will be required beofre next inspection. Notated city approved drawings with red ink areas where smoke detection is overspaced, a smoke detector is not installed that is city approved drawings as well as A/V notification that is overspaced, all areas of building fire alarm system were inspected. Inspection was stopped due to deficiencies noted. No initiating devices or A/V devices were tested.

We would like this inspection to be performed at 2:00 PM per the occupant''s request. Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
INSP-Final Inspection11/7/201911/12/201911/12/2019PCANC
DetailsJim Page
We would like this inspection performed after 1:30 pm per the occupant''s request. Please call Nate at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
INSP-Final Inspection11/5/201911/7/201911/7/2019ACANC
DetailsJim Page
We would like the inspection to be performed at 7:00 am per the request of the occupants. Please call Nate at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
INSP-Final Inspection10/30/201911/1/201911/1/2019ACANC
DetailsTroy Cobbley
Cancel per Nate since I could not be there at 7:00am die to another fire alarm inspection.

We would like the inspection to be performed at 7:00 am per the request of the occupants. Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
INSP-Final Inspection10/21/201910/23/201910/23/2019ACANC
DetailsJim Page
Could not perform inspection, request was cancelled per point of contact, will be rescheduled for a later date.

Please call Nate at ###-#### with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
INSP-Final Inspection10/17/201910/18/201910/18/2019PCANC
DetailsTroy Cobbley
I'm unable to perform the inspection when the contractor was ready. The site requested that the inspection start at 2:00 pm if possible since they have several meetings during the day. Please call Nate at ###-####
with inspection time. Phone #: ###-#### Inspection requested via web by Lori Brungardt
Alarm Plan Check10/8/2019 10/8/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  10/8/2019 DONE
As built - No fee.
Permit Ready to Issue  10/8/2019 DONE
as built approved
CHANGE STATUS TO (ISS)  10/8/2019 DONE
Plan assigned to (Lee)10/2/2019 10/3/2019 DONE
DetailsLee G Meredith
as built
1st review completed  10/3/2019 FAIL
Failed prescreen. Fl. 2 detector spacing is wrong. Returned to Lori.
Plan Modification Accepted  10/2/2019 DONE
as built to upload drawings request by Lori
INSP-Final Inspection9/27/20199/30/20199/30/2019ACANC
DetailsJim Page
Please call Nate at ###-#### with inspection time. Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
Permit Ready to Issue  8/29/2019 DONE
met
Issue and Print Permit  8/29/2019 DONE
Plan assigned to (Lee)8/28/2019 8/28/2019 DONE
DetailsLee G Meredith
1st review completed  8/28/2019 FAIL
Provide shut trip power monitoring per 2016 NFPA 72 21.4.4.
Plan resubmittals received  8/28/2019 DONE
Alarm Plan Check8/28/2019 8/28/2019 PASS
DetailsLee G Meredith
PLANS TAKEN FRONT DESK ALARM  8/28/2019 DONE
Passed with review comments. 8-28-19 pdf
Application received  8/27/2019 DONE
Application submitted via PDS Online on Aug 27 2019 10:58AM