Permit NumberFIR18-00503
StatusFinaled
Name PROTEX
Site Address 1300 S BIRD ST
Project NameIdaho Humane Society
Customer Number 
ePlanReviewYes
Description
Add code-compliant fire alarm control panel for the purposes of manual pull, smoke detection and annunciation. This work is associated with building permit BLD17-02871. Plan Mod 10-28-19. Change notification power supplies to resolve syncronization issues.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/30/201910/30/201910/30/2019PPASS
DetailsTroy Cobbley
Permit finaled

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection10/28/201910/29/201910/29/2019PFAIL
DetailsTroy Cobbley
Changes verified. Plan mods are needed showing the missing detector at first floor elevator lobby and the three NAC panels that are paired with the three other NAC panels. Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection10/24/201910/25/201910/25/2019PCANC
DetailsJim Page
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
INSP-Final Inspection10/24/201910/25/201910/24/2019ACANC
DetailsTroy Cobbley
Contact is Dirk. Phone #: ###-#### >> Inspection requested via web by Morgan Ahten Inspection cancelled from web by: Morgan Ahten
INSP-Alarm Testing10/9/201910/10/201910/10/2019PDONE
DetailsTroy Cobbley
Tested the remaining smoke detectors and elevator recall. Per Lee the volume of the horns has been verified by a third party and is ok. Items need prior to a final sign off are the sync issue with the horns and the previously noted changes need to be applied. Plan mods are needed showing all of the changes.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Alarm Testing10/9/201910/9/201910/9/2019PDONE
DetailsTroy Cobbley
Todays inspection we tested the smoke detectors in the first floor central area and the north wing. All tested ok. We set off the notification for the entire building and I noted that the visual devices have two patterns which is ok but the audible devices do not sync which is not ok as per NFPA 72.
Also the smoke detectors are reporting correctly.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Alarm Testing10/4/201910/4/201910/4/2019PFAIL
DetailsTroy Cobbley
The smoke detectors are not reporting to the facp. Inspection stopped. The receiver troubles have been cleared.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Alarm Testing10/1/201910/2/201910/2/2019PDONE
DetailsTroy Cobbley
Today we finished the building walk through for the notification appliances. See the city approved plans for locations of deficiencies. Approx. 30 items. The fire alarm panel currently has dial out issues and does not appear to be reporting signals. Plans need to be resubmitted showing the candella changes and that many of the smoke detectors have not been installed. No smoke detectors were tested due to the communication troubles on the fire alarm panel.

Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection9/30/201910/1/201910/1/2019AFAIL
DetailsTroy Cobbley
For todays inspection I was able to check spaqcing of the south wing and center section first floor. Several devices are overspaced and many more had the candellas set incorrectly. Plans do not match the install such as horns shown but horn/strobes installed (the horn/strobes are required) Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Final Inspection9/13/20199/16/20199/16/2019AFAIL
DetailsTroy Cobbley
Audibility levels tested. Most areas exceeded the maximum allowable volume of 110 dB and peaked between 112 and 116. All areas need to be reduced to below 110 dB. jonathan Phone #: ###-####.
INSP-Alarm Testing7/11/20197/12/20197/12/2019ADONE
DetailsTroy Cobbley
Todays inspection we verified phone lines, panel, duct detector/hvac unit shutdown, flow switches and tamper switches.
Plan modifications are needed showing all of the changes. Strobes are over spaced and need to be relocated or the candella adjusted. Smoke detectors are too close to diffusers. Strobes are missing in on location on the second floor as marked on the plans.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
INSP-Conference2/28/20193/4/20193/4/2019ADONE
DetailsTroy Cobbley
I went over smoke detector spacing with the electrical and fire alarm contractor. I deferred elevator recall requirement to state inspector.

Contact Morgan. Phone #: ###-#### Inspection requested via web by Morgan Ahten