Permit Information
Permit NumberFIR18-00565
StatusFinaled
Name JBL FIRE PROTECTION LLC
Site Address 503 S ASH ST
Project NameASH STREET TOWNHOMES WEST BLDG
Customer Number 
ePlanReviewYes
Description
[Ash Street Townhomes - West Building]
The fire sprinkler scope of work consists of protecting a three level apartment building. The bottom level is a side feed design; the middle and top level are gridded. The project utilizes residential sprinklers and CPVC piping. There are floor control valves for each level.
[BLD17-04465]
There are three building permits under this Eplan (BLD17-04464, BLD17-04465 and BLD18-00248). Permit to build the West Building, a 19,230 sq ft multi-family R2 apartment building. This project consists of two 3-story, multi-family residential buildings and one single-story detached carport, and related site work. The two multi-family buildings are of Type VB construction and fully sprinklered with an NFPA 13 system for building area increase. Separate fire sprinkler and fire alarm permits are required as regulated by Boise Fire Department. **JAR**

Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or building life safety systems. Please review the supplemental documents attached to this building permit case for details. Fire protection “shop drawings” shall include approved code alternate design.

• There are no AMM at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/10/20195/13/20195/13/2019PPASS
DetailsJim Page
Final fire sprinkler inspection complete.

Johnathon Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro3/29/20194/1/20194/1/2019ADONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed, hydrostatic testing for this building is complete.

overhead // Jonathan Phone #: ###-####
INSP-Sprinkler Rough-in3/26/20193/29/20193/29/2019PPASS
DetailsJim Page
Tenting/insulation inspection for fire sprinklers in remaining units complete, approved for cover. Rough to ocver ispection complete for all units in this building.



insulation inspection for units 128, 130, and 132 // Jonathan Phone #: ###-####
INSP-Sprinkler Rough-in3/18/20193/19/20193/19/2019APART
DetailsJim Page
Tenting inspection for units 112, 114, 116, 118 and 120 complete, piping is approved for cover.

overhead- Verfiy insullation in units 114, 116, 118 and 120- John. Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro3/13/20193/14/20193/14/2019ADONE
DetailsJim Page
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.

Johnathon Phone #: ###-####
INSP-Supply line flush3/8/20193/11/20193/11/2019PDONE
DetailsJim Page
Underground main line flush complete.

Jonathan Phone #: ###-####
INSP-Sprinkler Rough-in2/1/20192/1/20192/1/2019PCANC
DetailsTroy Cobbley
No city approved plans on site. No inspection. Johnathon Phone #: ###-####
INSP-Sprinkler Rough-in1/2/20191/3/20191/3/2019APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping/insulation for remaining building complete, approved for cover.

John Phone #: ###-####
INSP-Sprinkler Rough-in12/11/201812/12/201812/12/2018APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping/insulation for unti 119 complete, approved for cover.

Nate Phone #: ###-####
INSP-Sprinkler Rough-in12/7/201812/10/201812/10/2018PPART
DetailsJim Page
Rough to cover inspection for units, 111, 113, 115 and 117 complete, approved for cover.

Johnathon Phone #: ###-####
INSP-Sprinkler Rough-in11/28/201811/29/201811/29/2018APART
DetailsJim Page
Previously noted items have been corrected, rough to cover inspection complete for overhead fire sprinkler piping in west building, units 101, 105, 107, 109, 201 and 203. Inspected units approved for cover.

John Phone #: ###-####
INSP-Sprinkler Rough-in11/26/201811/27/201811/27/2018PFAIL
DetailsJim Page
Correct overspaced attic heads as discussed. Insulation needs to be pulled tight and not hanging below deflectors is attic spaces. Make corrections to heads that are to close to deck, heads need to be 1 inch to 3 inches below the top cord per manufacture specs. Combustible concealed space under stairs that do not have insulation will need to have fire sprinkler protection added or cobustible material is covered with sheetrock or fill the space with non-combustible insulation.

Jonathon Phone #: ###-####
INSP-Sprinkler Rough-in10/24/201810/24/201810/24/2018PDONE
DetailsJim Page
Hydrostatic test for both underground mains witnessed, no pressure loss observed.

Johnathon-hydro underground east and west bldg Phone #: ###-####
INSP-Sprinkler Rough-in10/16/201810/16/201810/16/2018PPASS
DetailsJim Page
Rough to cover inspection for underground supply complete, approved for cover

Supply line cover-Jon Phone #: ###-####
INSP-Sprinkler Rough-in10/4/201810/4/201810/4/2018PPASS
DetailsJim Page
Rough to cover inspection for underground supply complete, approved for cover.

underground cover-John Phone #: ###-####