Permit Information
Permit NumberFIR19-00766
StatusIssued
Name PHOENIX FIRE PROTECTION
Site Address 2826 N 28TH ST
Project NameAbel Residence
Customer Number 
ePlanReviewYes
Description
,296 Sq Ft single level residence to be fully sprinklered per NFPA 13D 2016 and Local Code Occupancy Class r-1, Construction Type VB, point of connection to be at BFP.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/29/20207/31/20207/31/2020AFAIL
DetailsTroy Cobbley
I stopped the inspection when I found that the underground supply piping to the riser was 1" instead of the 2" shown on the plans. Also this 1" piping has alot of 1" 90's before it gets to the riser and none are shown on the plans. Also the plans indicate a rvs-1 residential valve but none is installed. Also there was no way to verify if the yard sprinklers are connected to the main supply and if so that they are shutting off upon activation of the sprinkler system. No other items looked at or tested.


Contact Perly Daniel ###-#### 30 min prior to Fire Final Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in12/16/201912/16/201912/16/2019PPASS
DetailsJim Page
All tenting/insualtion for fire sprinkler piping installed at time of inspection, cover is approved.

Contact Ken Orahood ###-#### 30 min prior to RTC Insp start please :)

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in12/11/201912/12/201912/12/2019PFAIL
DetailsJim Page
Insulation above fire sprinkler piping in walls not installed at time of inspection.

Contact Ken Orahood ###-#### 30 min prior to RTC Insp start please, Ken would like to schedule this for late, late afternoon if possible.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in12/10/201912/10/201912/10/2019PPART
DetailsJim Page
Previously noted items have been corrected, Ceiling cover for overhead fire sprinkler piping approved, all tenting in place for overhead fire sprinkler piping above ceiling at time of inspection. Numerous areas in house has vertical piping inside stub bays that are exposed to the attic space, only insualtion installed in these areas is behind the sprinkler piping not above, will need to verify insulation is installed in the complete stud bay above sprinkler piping before vertical sprinkler pipng can be covered. Sprinkler piping above ceilings is approved for cover, vertical sprinkler piping in walls exposed to the attic space not approved for cover.

Contact Ken Orahood ###-#### 30 min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in12/9/201912/9/201912/9/2019AFAIL
DetailsTroy Cobbley
Tenting inspection failed. I sent pictures of the three areas of concern to Ken and explained my concerns. Re-inspection fee applied.

Contact Ken Orahood ###-#### 30 minc prior to Insp start please. We''ve been told that they are ready and the Tenting has been taken care of hopefully for the last time.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Conference12/5/201912/6/201912/6/2019ADONE
DetailsJim Page
Fire conference is complete.

Contact Ken Orahood 08-###-#### 30 min prior to Conf Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in12/3/201912/5/201912/5/2019AFAIL
DetailsJim Page
Inspection performed not knowing fees were due for pemit, tenting still not installed correctly, another re-inspection fee will be added.

Contact ken Orahood ###-#### 30 min prior to RTC Insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in12/2/201912/3/201912/3/2019AFAIL
DetailsJim Page
Areas of concern for tenting were shown to the point of contact during 20NOV2019 conference, tenting still is not correct, no cover is approved. Pictures have been sent via text to the point of contact listed for this inspection.

Contact Trent Bice ###-#### 30 min prior to RTC insp Start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in11/25/201911/26/201911/26/2019ACANC
DetailsJim Page
Contact will be Chad Christensen ###-####, please contact him 30 min prior to RTC insp start please. he would like an 8:30 am insp. time.

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
INSP-Sprinkler Rough-in11/25/201911/25/201911/25/2019PFAIL
DetailsJim Page
Areas of concern for tenting were shown to the point of contact during last inspection, tenting still is not correct, no cover is approved.

Contact Perly Daniel ###-#### 30 min prior to RTC Insp start please,

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Conference11/19/201911/20/201911/20/2019ADONE
DetailsJim Page
Fire conference complete, discussed tenting requirements, adding sprinklers in level 2 storage area as well as addressing the vertical sprinkler piping location.

Contact Perly Daniel - ###-#### 30 min prior to Insp Conference start time please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in11/18/201911/19/201911/19/2019AFAIL
DetailsJim Page
Tenting not installed correctly in numerous places, blow in insulation will get inot required pocket between sheetrock and piping. Sidewall heads in the in-law suite are more than 36 inches down from the peak. Freeze protection for vertical pipe in attic spaces is not adequate, relocate piping for correct freeze protection as discussed or provide heat calculations for install to meet the minimum requirement. No cover is approved.

Contact Perly Daniel ###-#### 30 min prior to RTC insp start please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
INSP-Sprinkler Rough-in11/6/201911/6/201911/6/2019PFAIL
DetailsJim Page
Install piping in wall cavities as discussed instaed of vertical in the attic space. Relocate hangers/straps that are attached to the webbing of the trusses or get documentation from the truss manufacturer showing that the webbing is approved to attach too. Sprinkler heads need to be added in storage area located in the in-law suite, no tenting installed at time of inspection, no cover is approved.

Contact Noemi Carrero ###-#### 30 min prior to RTC Insp start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank