Permit Information
Permit NumberFIR11-00296
StatusIssued
Name ALARMCO
Site Address 11818 W JOPLIN RD
Project NameW. BOISE WASTEWATER TREATMENT
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to install an AES radio to replace the existing DACT in the FACP. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIR-Aging Inspection9/26/20189/26/20189/28/2018 NR
DetailsTroy Cobbley
Tried to contact Bill Benko to see when they would proceed with their plan to seperate out buildings for central station monitoring. Email was rejected. It looks like Bill is no longer a city employee. No other known cite contact at this time.
FIR-Aging Inspection2/12/20182/12/20182/16/2018 NR
DetailsTroy Cobbley
Waiting on the city of boise.
FIR-Aging Inspection9/11/20179/11/20179/12/2017 NR
DetailsTroy Cobbley
waiting on the city of boise
FIR-Aging Inspection5/2/20175/2/20175/8/2017 NR
DetailsTroy Cobbley
Waiting on city of boise
FIR-Aging Inspection12/19/201612/19/201612/22/2016 NR
DetailsTroy Cobbley
FIR-Aging Inspection8/31/20168/31/20168/31/2016 NR
DetailsTroy Cobbley
FIR-Aging Inspection2/19/20162/19/20162/24/2016 NR
DetailsTroy Cobbley
Per Scott the city of boise is working toward a resolution on the separate address monitoring
FIR-Aging Inspection7/28/20157/28/20157/28/2015 NR
DetailsTroy Cobbley
Per Scott the city of boise is working toward a resolution on the separate address monitoring
FIR-Aging Inspection4/28/20154/28/20154/28/2015 NR
DetailsTroy Cobbley
Per Scott the city of boise is working toward a resolution on the separate address monitoring.
FIR-Aging Inspection6/4/20136/4/20136/5/2013 NR
DetailsTroy Cobbley
I spoke to Rick Phone #: ###-#### with Public Works, and he said different options are being investigated for a solution.
FIR-Aging Inspection10/5/201210/5/201210/8/2012 NR
DetailsTroy Cobbley
Mark is working on this permit. An email has been sent to Scoot by Mark requiesting furhter action.
FIR-Aging Inspection3/20/20123/20/20123/20/2012 NR
DetailsTroy Cobbley
I spoke to Mark with Alarmco and he stated that he would follow up.
Telephone call  10/5/2011  
Telephone call  10/5/2011 DONE
Spoke with Mark at Alarmco. He asked if they could use an IntelliPro device instead of an IntelliTap device with the AES. I let him know that for this particular fire alarm panel, it is approved to use the AES-7794 IntelliPRO PROVIDED only the CID/Pulse format be used. I also requested that he please provide this information to the inspector for field verification.
INSP-Final Inspection9/15/20119/16/20119/16/2011AFAIL
DetailsTroy Cobbley
Alarm, trouble and supervisory signals were tested through the AES but only a single address/building location is set up for the facility which includes multiple buildings and alarm systems. The monitoring company needs to receive specific addresses/locations for each of the reporting fire alarm panels.
Plan assigned to (Stephanie)6/22/2011 7/1/2011 DONE
DetailsStephanie L. Cobbley
1st review completed  7/1/2011 DONE
Alarm Plan Check7/1/2011 7/1/2011 PASS
DetailsStephanie L. Cobbley
Plans approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  7/1/2011 DONE
Approved redlined plans available at front counter.
Inspection Record Card- Fire7/1/2011 7/1/2011 DONE
DetailsPatricia Smith
Telephone call  7/1/2011 DONE
t/c w terri - permit ready and fees given
Permit Ready to Issue  7/1/2011 DONE
Details
Issue and Print Permit  7/1/2011 DONE
Application received  6/22/2011  
FIR-Aging Inspection8/12/20208/12/2020   
DetailsTroy Cobbley