DOC - Permit Finaled | | | 9/12/2019 | | DONE |
|
|
|
Per passing final INSP-Final Inspection on 9/11/19 by MS
|
INSP-Final Inspection | 9/10/2019 | 9/11/2019 | 9/11/2019 | A | PASS |
Mark Scharfen
|
|
|
Tested tampers and flow switch interface with fire alarm system. Checked escutcheons. Outside bell functions. Passed. Thank-you!
Please Txt Tyler Loomis ###-#### 30 min prior to Final Insp start if you can not txt him please call Ken Orahood ###-#### and he will contact Tyler.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank
|
INSP-Final Inspection | 9/5/2019 | 9/6/2019 | 9/6/2019 | A | PART |
Jim Page
|
|
|
Partial final inspection for overhead fire sprinklers complete, fire panel is new so tampers and flow switch need to be coordinated with the fire alarm vendor to inspect/verify monitoring.
Contact Tyler Loomis ###-#### pleae Text or email tylerloomis50@gmail.com 30 min prior to Final Insp please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Final Inspection | 8/23/2019 | 8/27/2019 | 8/27/2019 | A | CANC |
Jim Page
|
|
|
Contact Tyler Loomis ###-#### 30 min prior to Final Insp start please.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
INSP-Final Inspection | 8/22/2019 | 8/23/2019 | 8/23/2019 | A | CANC |
Jim Page
|
|
|
Contact Tyler Loomis ###-#### 30 Min prior to Final Insp start please
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
INSP-Sprinkler Rough-in | 8/7/2019 | 8/8/2019 | 8/8/2019 | A | PASS |
Jim Page
|
|
|
Previously noted items have been repaired for rough to cover in basement area, basement area approved for cover.
Contact Tyler Loomis ###-#### 30 min prior to RTC Insp Start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in/Hydro | 8/6/2019 | 8/6/2019 | 8/6/2019 | P | FAIL |
Jim Page
|
|
|
Fire sprinkler upright in mech room is 8 foot off of the wall, correct overspace issue. Install correct type hanger where grid wire is holding up the pipe. Correct areas where sammy type hangers are not installed correctly, refer to manufactures documents for listed install for sammy type hanger attatchment. Relocate sidewall head that is blocked when door is open.
Contact Tyler Loomis ###-#### 30 min prior to RTC/Hydro Insp start please..Tyler has a Dr Appt. and would like to do this around 1:30 pm if at all possible please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in/Hydro | 8/6/2019 | 8/6/2019 | 8/6/2019 | P | CANC |
Jim Page
|
|
|
Contact Tyler Loomis 208-859--6589 30 min prior to RTC/Hydro Insp start please.
Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
|
INSP-Sprinkler Rough-in | 8/1/2019 | 8/5/2019 | 8/5/2019 | A | FAIL |
Jim Page
|
|
|
Called point of contact 3 times over a 30 minute time span, all calls went straight to voicemail, mailbox was not set up so message could not be left, inspection will need to be rescheduled.
Contact Tyler Loomis - ###-#### 30 Min Prior to RTC nsp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
Plan Modification Accepted | | | 7/11/2019 | | DONE |
|
|
|
Terry requested the workflow to be uploaded up for a plan mod
|
Plan assigned to (Stumbaugh) | 7/11/2019 | | 7/11/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 7/11/2019 | | 7/11/2019 | | FAIL |
Mark Stumbaugh
|
|
|
|
Plan resubmittals received | | | 7/11/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 7/11/2019 | | 7/11/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/11/2019 | | DONE |
Mark Stumbaugh
|
|
|
Plan Mod Fee $150.00
|
Permit Ready to Issue | | | 7/11/2019 | | DONE |
|
|
|
plan mod pleae do not re issue
|
CHANGE STATUS TO (ISS) | | | 7/11/2019 | | DONE |
|
|
|
plan mod
|
INSP-Sprinkler Rough-in | 7/1/2019 | 7/1/2019 | 7/1/2019 | P | PART |
Troy Cobbley
|
|
|
See the city approved plans for rooms marked "ok" where piping can be covered. Not all areas were available for inspection due to flooring installation. Also some rooms did not have the wips installed and have been circled with a question mark. I also noted two heads too close to one another and two heads 16' apart. They have been marked on the plans.
Contact Tyler Loomis - ###-#### 30 min prior to insp start please, he would like to schedule for around noon-ish if possible.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in | 5/21/2019 | 5/22/2019 | 5/22/2019 | A | PART |
Jim Page
|
|
|
Rough in inspection for overhead fire sprinkler piping complete, a follow up inspection will be required after flex heads are installed the grid before all cover can be approved. Hardlids in throughout level 1 approved for cover.
Contact Tyler Loomis ###-#### 30 Min prior to RTC Insp start please, he''s requesting an mid morning /10AM inspection time if possible.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
INSP-Sprinkler Rough-in/Hydro | 5/21/2019 | 5/22/2019 | 5/22/2019 | A | DONE |
Jim Page
|
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Contact Tyler Loomis ###-#### 30min prior to RTC /Hydro Insp start please. He''s requesting a 10 AM insp time if at all possible.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
Plan resubmittals received | | | 4/17/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 4/17/2019 | | 4/17/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 4/17/2019 | | 4/17/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/17/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Permit Ready to Issue | | | 4/17/2019 | | DONE |
|
|
|
met
|
Issue and Print Permit | | | 4/17/2019 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/9/2019 | | 4/10/2019 | | FAIL |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/10/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Sprinkler Plan Check | 4/3/2019 | | 4/9/2019 | | FAIL |
Mark Stumbaugh
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/9/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Plan resubmittals received | | | 4/9/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 4/9/2019 | | 4/9/2019 | | DONE |
Mark Stumbaugh
|
|
|
|
Application received | | | 4/3/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Apr 3 2019 3:15PM
|
Intake Approval | | | 4/3/2019 | | PASS |
Mark Stumbaugh
|
|
|
|
Plan assigned to (Stumbaugh) | 4/3/2019 | | 4/3/2019 | | DONE |
Mark Stumbaugh
|
|
|
|