INSP-Final Inspection | 8/14/2015 | 8/14/2015 | 8/14/2015 | P | PASS |
Thomas Walsh
|
|
|
Hydrostatic pressure test of the FS U/G supply line from the city connection to the A/S riser manilfold (200 psi @ 2hrs) PASSED Also hydrotested the bulk supply line to all of the building standpipe risers (200 psi @ hours) - PASSED.
|
INSP-Sprinkler Rough-in/Hydro | 8/12/2015 | 8/13/2015 | 8/13/2015 | A | CANC |
Thomas Walsh
|
|
|
Not ready for FS U/G test today - Will reschedule for tomorrow. NOTE: This test will also hydrotest all of the standpipe risers in the building.
|
INSP-Supply line flush | 7/1/2015 | 7/2/2015 | 7/1/2015 | A | PASS |
Thomas Walsh
|
|
|
FS U/G supply line flush test. Flushed clear after 2 attempts. NOTE: FS U/G still requires hydrostatic pressure test.
|
INSP-Sprinkler Rough-in | 5/27/2015 | 5/28/2015 | 5/28/2015 | A | PART |
Thomas Walsh
|
|
|
Second floor west unit soffits inspections, including units 221, 222, 223, 224, 229, 233,. Also fourth floor west units - all units on this side. Also inspected trash rooms on the 2nd and 3rd floors - east and west sides for rough in of trash chute interior sprinklers. Several hangers needed work/replacement and all were repaired/replaced prior to the end of the inspection.
|
INSP-Sprinkler Rough-in | 4/17/2015 | 4/20/2015 | 4/20/2015 | A | CANC |
Katie Marron
|
|
|
Wrong permit number for intended inspection. Inspection for 3rd floor east wing not underground. Inspection completed under correct permit number.
|
INSP-Sprinkler Rough-in/Hydro | 4/16/2015 | 4/20/2015 | 4/20/2015 | A | CANC |
Katie Marron
|
|
|
Wrong permit number for intended inspection. Cancelled per conversation with contractor.
|
INSP-Sprinkler Rough-in | 4/16/2015 | 4/17/2015 | 4/17/2015 | A | CANC |
Katie Marron
|
|
|
Wrong permit number requested for inspection. Inspection intended for overhead work not underground.
|
INSP-Conference | 4/13/2015 | 4/13/2015 | 4/13/2015 | P | DONE |
Katie Marron
|
|
|
Phone conversation regarding concealed spaces.
|
INSP-Sprinkler Rough-in | 11/10/2014 | 11/12/2014 | 11/12/2014 | A | PART |
Forrest France
|
|
|
UG fire supply line from the point of connection to the ductile riser completed. *NOTE- contractor has installed retainer in place of thrust blocking at the 90.
|
Plan assigned to (Tim) | 9/3/2014 | | 9/3/2014 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 9/3/2014 | | 9/3/2014 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
|
1st review completed | | | 9/3/2014 | | PASS |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/3/2014 | | DONE |
Tim Frost
|
|
|
|
Permit Ready to Issue | | | 9/3/2014 | | DONE |
|
|
|
|
Issue and Print Permit | | | 9/3/2014 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/3/2014 | | 9/3/2014 | | DONE |
Kristal Soland
|
|
|
|
Application received | | | 8/29/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 29 2014 10:05AM
|