Permit Information
Permit NumberESC18-01168
StatusIssued
Name SID BARZEE
Site Address 330 N 2ND ST
Project NameSt. Lukes shipping/receiving
Customer Number 
ePlanReviewNo
Description
This project is for the shoring and excavation for the Shipping/Receiving building. Refer to the St. Luke's Masterplan for more information. Single master SWPPP created for both the shipping/receiving building and the NW Parking Garage. See ESC18-01167 for parking gararge. BMPs include pollution prevention practices in staging areas and impervious areas, sediment protection on a receiving storm drains. If any dewatering is required, a dewatering plan must be submitted to ESC division for review and inspection. Site preparation /pre-construction conference is required.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
General Inspection7/17/20207/17/20207/22/2020PPASS
DetailsAndy J. Long
Vertical construction in progress. No trackout or discharges from site. No fugitive dust observed. Perimeter is clean and has sediment controls installed. No corrections at this time.
General Inspection6/19/20206/19/20206/22/2020 PASS
DetailsMichael Zawacki
WIP on vertical steel and masonary. 2nd is closed, surrounded by fence and contained. No issues.
General Inspection4/29/20205/4/20205/4/2020PPASS
DetailsAndy J. Long
1 PM with Charlie ###-####

BMPs implemented on site

- stormwater controls to direct stormwater from perimeter to within site for retention and limit offsite discharge.
- access points are swept at minimum once per week. No trackout or dirty surfaces observed at site access points.
- concrete washout pans located in multiple locations on site and being serviced at time of inspection
- secondary containment for mixers at the shipping and receiving site
- working on removing dirt and debris in gutters in areas where fencing is tight and difficult for cleaning. On 2nd street will contain both ends of gutter with sand or rock bags
- suggested installing a gatorguard wattle at Bannock that can contain the dirt at the access area but also be driven over by trucks (should be removed for heavy use or tracked equipment)
- suggested installing secondary contaiment for dumpsters or cover to prevent waste mingling with stormwater or leakage

Correction request:
- reinstall wattle along north side of garage on State Street to be staked every 4-5' and be plush to ground with 2" trench.

- work with St. Luke's to prevent compactor leak from their facility from comingling with stormwater from the construction site.
BMP Violation4/29/20204/30/20205/1/2020PPASS
DetailsAndy J. Long
Corrections completed as requested. Follow up walk through inspection of full perimeter scheduled
BMP Violation4/27/20204/28/20204/29/2020PFAIL
DetailsAndy J. Long
No corrections were made as requested.

RP did call back and stated they would address the issues this afternoon
BMP Violation4/21/20204/22/20204/27/2020PPEND
DetailsAndy J. Long
follow up on corrections
General Inspection4/15/20204/16/20204/21/2020PFAIL
DetailsAndy J. Long
Corrections needed:

- sweep Bannock between 1st & 2nd
- install perimter sediment control around stockpile on north side of road; or relocate away from gutter
- install storm drain sediment bag on 2nd street, east side of street, between Bannock and Idaho.

Follow up scheduled
-
General Inspection4/10/20204/10/20204/15/2020 PASS
DetailsAndy J. Long
WIP. Temporary stockpile in road on Bannock. In process of being removed.

No discharges observed

May request sediment protection on 2nd south of site.
General Inspection2/24/20202/24/20203/2/2020 PASS
DetailsAndy J. Long
No significant trackout. Permeter is clean. Receiving storm drains have sediment controls installed.
General Inspection1/8/20201/8/20201/8/2020PPASS
DetailsAndy J. Long
1 pm with Charlie ###-####

- No significant trackout from site access points at 1st & State and 2nd & Bannock. Runoff from disturbed areas flows into sites tunnel excavation area (minimizes potential offsite discharges)
- site is using Ecopan service for concrete washout
- trash is well managed, no loose trash laying around site
- site has sweeping unit working at access points. Active haul off occuring at Jefferson




Corrections requests:
- install gravel bag gutter check dam bags on Jefferson where CUP excavation & haul off is occuring to contain material in gutters close to site for easy manual clean-up
- check with St. Luke's facilty management regarding putting spill absorbent tubes or secondary containment around the trash compactors (due to leaks and oil drips)
- check that SWPPP has completed operator certfication paperwork complete.
- Inspection reports should be placed in SWPPP binder no longer than after 14 days of the date of inspection
- request during site training or employee meetings that offsite smokers do not throw cigarette butts on the ground but into a trash container or ash tray

- Install stabilized access to the Ecopan’s located on 1st street on east side of garage structure, scoop/contain mud along the curb
General Inspection12/4/201912/4/201912/5/2019 PASS
DetailsAndy J. Long
see ESC18-01167
Conference10/17/201910/18/201910/18/2019APASS
DetailsAndy J. Long
11 am charlie

No trackout, discharges, or other violations observed. SWPPP onsite and site inspections are every 2 weeks and after rain events.

Site walk around and inspection with SWPPP coordinator Charlie of the 3 St. Luke's project. Site stormwater is retained on site, existing DIs are disconnected and or flow into the excavation of the site. Ecopan concrete washouts are utilizied and in good condition.

Jefferson Street to the north of project will soon be demolished/excavated. Streets directs stormwater into site.

Corrections:
- install gravel/road mix on loading areas and temporary parking spots around perimeter (bannock & 2nd)
- re-grade corner access and stabilize
- need to reinstall wattle along the stockpile/backfill piled up along Bannock. Wattle should be installed at toe of slope, be trenched in 2-3" and staked every 4-5 ft.
- make sure inspection records are up to date. An inspection form should be in binder within 1 week of the inspection date.

Notified Charlie of requests.

General Inspection10/17/201910/17/201910/17/2019PPART
DetailsAndy J. Long
correction request to provide stabilized parking or prohibit parking in the dirt entrances to the project.
General Inspection9/9/20199/9/20199/9/2019 PASS
DetailsMichael Zawacki
Wip on footings, 30' or so below grade. Ecopan on site, no issues.
General Inspection7/25/20197/25/20197/25/2019PPASS
DetailsMichael Zawacki
Working below grade, no ESC issues.
General Inspection7/3/20197/3/20197/3/2019 PASS
DetailsMichael Zawacki
Area is excavated and wall has been shored. Dirt ramp leading down site. No activity at time of inspection.
General Inspection5/17/20195/17/20195/17/2019PPASS
DetailsAndy J. Long
WIP on excavation. No discharges or trackout. No corrections requested.
Tracking Control4/8/20194/9/20194/10/2019PFAIL
DetailsAndy J. Long
No stabilized access installed as requested. Mud on apron and trackout in street. Workers and vehicle parked in the mud.
Tracking Control4/8/20194/8/20194/8/2019PFAIL
DetailsAndy J. Long
Mud and dirt on the existing asphalt site entrance. Muddy zone beyond the entrance is being driven through by workers and equipment.

Request to clean up and install stabilizaed access or close off area.
Permit Ready to Issue  1/3/2019 DONE
Issue & PRINT permit COM  1/3/2019 DONE
Routing - Erosion and Sediment11/30/2018 11/30/2018 DONE
DetailsAndy J. Long
revised ESC sheets uploaded. New SWPPP plan details and map of MS4 outfalls for project included. Approved. Site preparation inspection is REQUIRED
Routing - Erosion and Sediment9/17/2018 9/17/2018 PASS
DetailsAndy J. Long
SWPPP narrative and site map approved. Need to designate ESC Responsible Person(s) for SLHS and construction operator. Site preparation/pre-construction conference is required.
Application received  8/10/2018 DONE
Application submitted via PDS Online on Aug 10 2018 5:10PM