INSP-Final Inspection | 3/19/2020 | 3/23/2020 | 3/23/2020 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled. Phone #: ###-#### Inspection requested via web by Connie Danes
|
INSP-Final Inspection | 3/17/2020 | 3/18/2020 | 3/18/2020 | A | FAIL |
Troy Cobbley
|
|
|
No access due to sign on the door. Phone #: ###-#### Inspection requested via web by Connie Danes
|
INSP-Final Inspection | 2/13/2020 | 2/18/2020 | 2/18/2020 | A | FAIL |
Troy Cobbley
|
|
|
There is still exposed cpvc piping.
Phone #: ###-#### Inspection requested via web by Jim Danes
|
INSP-Final Inspection | 1/17/2020 | 1/22/2020 | 1/22/2020 | P | FAIL |
Troy Cobbley
|
|
|
To final permit all of the CPVC piping needs to be covered/protected per the UL listing as discussed. The interconnection with the fire alarm panel has been tested. The riser room needs to be one hour and verified by the building inspector.
Phone #: ###-#### Inspection requested via web by Connie Danes
|
INSP-Sprinkler Rough-in/Hydro | 1/7/2020 | 1/8/2020 | 1/8/2020 | A | DONE |
Jim Page
|
|
|
Hydrostatic test witnessed for overhead fire sprinkler piping, no pressure loss observed.
overhead hydro 1st and 2nd floor Phone #: ###-#### Inspection requested via web by Connie Danes
|
INSP-Sprinkler Rough-in/Hydro | 12/6/2019 | 12/9/2019 | 12/9/2019 | P | CANC |
Troy Cobbley
|
|
|
Needed flush not rough-in.
Barry is ready for you. Phone #: ###-#### Inspection requested via web by Connie Danes
|
INSP-Supply line flush | 12/9/2019 | 12/9/2019 | 12/9/2019 | P | PASS |
Troy Cobbley
|
|
|
Underground flush witnessed.
Barry is ready for you. Phone #: ###-#### Inspection requested via web by Connie Danes
|
INSP-Sprinkler Rough-in | 11/26/2019 | 11/27/2019 | 11/27/2019 | A | PASS |
Troy Cobbley
|
|
|
The underground supply piping is ok for cover. Phone #: ###-#### Inspection requested via web by Connie Danes
|
INSP-Sprinkler Rough-in | 11/14/2019 | 11/14/2019 | 11/14/2019 | P | PASS |
Troy Cobbley
|
|
|
The tenting is approved on the second floor only as per the email/letter from American Fire taking responcibility for the the tenting installation. Phone #: ###-#### Inspection requested via web by Connie Danes
|
INSP-Sprinkler Rough-in | 10/17/2019 | 10/21/2019 | 10/21/2019 | A | FAIL |
Troy Cobbley
|
|
|
Not enough access provided to verify tenting. Provide additional access and a letter as discussed for owner to take responcibility for work performed on the tenting as discussed. Phone #: ###-#### Inspection requested via web by Connie Danes
|
INSP-Sprinkler Rough-in | 10/17/2019 | 10/18/2019 | 10/17/2019 | A | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Connie Danes Inspection cancelled from web by: Connie Danes
|
INSP-Sprinkler Rough-in | 10/10/2019 | 10/11/2019 | 10/11/2019 | P | FAIL |
Troy Cobbley
|
|
|
No access to the single level and tenting is not correct for the two level area. Phone #: ###-#### Inspection requested via web by Connie Danes
|
INSP-Sprinkler Rough-in | 9/26/2019 | 9/27/2019 | 9/27/2019 | P | PART |
Troy Cobbley
|
|
|
Tenting failed for all areas. No piping to be covered. Rough-in passed for the single level area of work but again no piping can be covered. Also prior to a final inspection R38 insulation value will need to be provided.
Phone #: ###-#### Inspection requested via web by Connie Danes
|
INSP-Sprinkler Rough-in/Hydro | 5/21/2019 | 5/22/2019 | 5/22/2019 | P | PART |
Troy Cobbley
|
|
|
Rough-in passed for the two story section of the project, this includes first and second floor. The opening made to install the piping can be repaired. Another rough-in inspection will be requried to verify that the existing blow-in insulation has been removed from below the new piping and adequate tenting has been provided over the new piping. This inspection needs to happen before the new blow-in insulation is installed. A partial hydro test was witnessed for this two story area and no loss on the second floor but a visible loss for the first floor. The single level area of the project is not ready for inspection yet.
Phone #: ###-#### Inspection requested via web by Connie Danes
|