Information based on query as of Saturday, May 4, 2024.
Permit Information
Permit NumberMEC19-01679
StatusFinaled
Name HOBSON FABRICATING CORP
Site Address 3500 N CABARTON LN
Project Name 
Customer NumberH9709
ePlanReviewNo
Description
New: HVAC for MOUNTAIN VIEW ELEMENTARY
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/3/20204/3/20204/3/2020PPASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- final ok- card signed
Final3/31/20203/31/20203/31/2020PPART
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- Walked job with Levi- need all operational equipment installed under class 1 hood- missing 1 warmer- talked with GC about this- temp occupancy ok- rest of job ok- air balance ok
Final2/25/20202/26/20202/26/2020APART
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- temp occupancy ok-
1- need uv protection on mini split arma flex and seal penetration thru roof weather tight
2- need air balance report sent to me
3- need all equipment set and opertrational under class 1 and 2 hoods
4- RFI on smoke dectectors for RTU 25 a and b and 26 a and b still needs addressed and approved

call in final when ready
Rough-in2/11/20202/12/20202/12/2020PPASS
DetailsBrian Scoles
cover in the Kitchen Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- flex insulation and registers ok in rooms gym D 100 halway, 112A 116 cafeteria and kictchen ok for cover- all areas ok
Rough-in1/28/20201/29/20201/29/2020PPASS
DetailsBrian Scoles
Kitchen Phone #: ###-#### Inspection requested via web by Amanda Farnsworth-R/I on rooms 112 kitchen, 112a 113 116 and 117 seal on duct ok- dishwasher exhaust seal ok- ok for ceiling grid
Rough-in1/10/20201/13/20201/13/2020PPART
DetailsBrian Scoles
Area C for cover Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- area D rooms 106, 109, and 100 hallway ok for ceiling tiles
area C 106, 107, 108, 109, 110, 111, 112, 113 and 114 ok for ceiling tiles
area C 104 and 105 media center ok for ceiling tiles
2nd layer firewrap on grease duct ok- all grease duct done
Rough-in1/8/20201/9/20201/9/2020APART
DetailsBrian Scoles
light test inspection on grease duct Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- RTU 25 A and B ducting on roof ok- media center seal ok partially insulated waiting on approved flex duct to tie in registers on order- grease duct light test on 2 taps tied into 1 24" round to hood ok- ok for firewrap- grease duct light test all completed
Rough-in12/31/20191/3/20201/3/2020APART
DetailsBrian Scoles
cover and grease duct
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- 1st and 2nd layer firewrap ok- excluding hood connections- area A B and C corridirs ok for ceiling tiles- area A rms 111 110 109 ok for cover
Rough-in12/23/201912/24/201912/24/2019APASS
DetailsJack Reynolds
Grease duct Phone #: ###-#### Inspection requested via web by Amanda Farnsworth
- light test on field weld at drop to 90 and square/round ok marked prints
- small amount of duct seal in corridor ok for insulation marked prints
Rough-in12/17/201912/19/201912/19/2019APART
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- grease duct light test on round main 1 weld ok in ceiling- light test on drop and 90 degree with square to round on floor ok- still couple more to verify when installed- area A excluding rooms A111, 110 and 109 at later date- corridors in area A B C D needs inspected when ready
Rough-in12/5/201912/6/201912/6/2019PPART
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- area DS rooms 101 102 103 104 107 107a seal and registerts ok- ok for hard lids- area D 2 fire smoke damper framing ok- ok to sheetrock- will look at clearances next inspection
Rough-in11/26/201911/27/201911/27/2019PPART
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- area D rms D109 and D105 seal on duct ok- ok for insulation- area B classrooms only and rms B112 and B113 ok for ceiling tile cover- 2 fire/smoke dampers need framing and sheetrock clearances per installation instructions- framing missing on sides- access doors need installed on 2 fire/smoke damper above hard lids- call in for inspection when ready
Rough-in11/20/201911/21/201911/21/2019PPART
DetailsChad Schwendiman
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth - Signed okay to cover some hard lids on the mechanical plans
Conference10/16/201910/17/201910/17/2019APASS
DetailsBrian Scoles
Light test on grease duct- ###-####- 2- 16 feet 24 inch round lengths with 3 square accees ports light test ok
Rough-in10/15/201910/16/201910/16/2019PPART
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- all area c seal on duct ok- ok for insulation
Rough-in10/2/201910/3/201910/3/2019PPART
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- All area A seal on duct ok- ok to insulate excluding drops from RTU have not been installed will look at seal on grid inspection
Rough-in9/4/20199/5/20199/5/2019APASS
DetailsBrian Scoles
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- Area B only 6 class rooms seal ok- ok for insulation all 6 classrooms area B only- approved drawings onsite