Permit Information
Permit NumberBLD17-01088
StatusFinaled
Name THE ROBINS & MORTON GROUP
Site Address 8800 W EMERALD ST
Project NameTreasure Valley Hospital - TI
Customer Number 
ePlanReviewYes
Description
(TREASURE VALLEY HOSPITAL – PHASE 2 OF ADDITION – INTERIOR FINISH) (DRH16-00514 MODIFICATION TO DRH13-00075) (CUP16-00094) The fire sprinkler system is used for Occupancy and for building area increase. The building shell of the 13,921 square foot addition and the 3-hr fire wall to separate Type I-B construction from V-B construction was constructed under permit BLD17-00359. Interior demolition work within selective existing areas is also covered under this permit. To construct interior improvements within a new building shell addition and to remodel other selective areas of both existing buildings. Work is to include 1-hr smoke barrier walls to create smoke compartments, smoke partitions to create care suites, smoke partitions to create I-2 rated corridors, 1-hr fire barrier walls to separate incidental use areas from the rest of the building, interior nonbearing walls, suspended acoustical ceilings, gypsum board ceilings, a new exterior trash enclosure, exterior brick veneer, EIFS, a grease trap, medical gas piping system, etc. Two new operating rooms, 13 new extended stay private recovery rooms with toilet/shower rooms (two of which are accessible to the disabled) within the addition, 2 new extended stay private recovery rooms with toilet rooms that are not accessible to the disabled within the existing hospital, 9 single user toilet rooms accessible to the disabled, a multi-user Men’s restroom and a multi-user Women’s toilet room accessible to the disabled, a new sterile processing area, a kitchen with a Type I grease hood and duct system, an A-2 Occupancy dining room, laundry facilities, enlarged staff locker rooms, storage areas, etc. will be created. Special Inspection is required for fire stopping, EIFS, and for spray applied fire proofing. This permit is intended to establish a Certificate of Occupancy for the 13,921 square foot hospital expansion area, the 10,694 square foot area in the South office building (the existing 2,806 square foot tenant space is not part of this project), and various remodeled areas within the existing hospital. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 (including quick response sprinkler heads where required) and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Telephone call  8/6/2019 DONE
called-transfered to Michelle-asked about when we could expect payment-she asked me to email her the fees due and she'll check into it
Print Statement  8/6/2019 DONE
Michelle and Robins Morton asked me to email her the statement
Print Statement  7/25/2019 DONE
sent 3rd late notice
Print Statement  6/18/2019 DONE
sent 2nd late notice
Print Statement  4/19/2019 DONE
sent 1st late notice
Print Statement  2/1/2019 DONE
correct updated values
Telephone call  1/23/2019 DONE
Spoke with Justin Free. Justin stated the plumbing inspector said he would split out the plm permit from phase one (bld17-00359) so that is showed work done on phase two (bld17-01088). in formed justin that our inspections are unable to do that and their plumbing company would need to pull a second permit. as of now it looks like no plumbing permit/work was done for phase two
Print Statement  1/17/2019 DONE
Second Notice 12/24/20181/8/2019 DONE
mailed 1-11-19
First Notice 11/11/201812/14/2018 DONE
mailed 12-17
Permanent Occupancy  11/1/2018 DONE
BLD-Final10/30/201810/31/201810/31/2018APASS
DetailsMike Jordan
Charles Phone #: ###-####. Ok for perm occ.
FIRE-Final Inspection10/30/201810/30/201810/30/2018PPASS
DetailsTroy Cobbley
life safety passed

Charles Phone #: ###-####
Zoning Approval10/3/201810/3/201810/3/2018 PASS
DetailsKatelyn Menuge
PubWorks Occupancy Approval8/31/20188/31/20188/31/2018 DONE
DetailsTiffany Lowery
PubWorks Occupancy Approval8/31/20188/31/20188/31/2018 DONE
DetailsTiffany Lowery
Received engineer letter and release letter from Owner of Treasure Valley Hospital.
FIRE-Final Inspection7/20/20187/23/20187/23/2018AFAIL
DetailsTroy Cobbley
Life safety will be ok to pass when the project related fire alarm permit is finaled.

Barry Phone #: ###-####
BLD-Final7/20/20187/20/20187/20/2018PPEND
DetailsMike Jordan
Phase 3 will be ok as soon as fire/life/safety has signed off.
BLD-Final7/20/20187/23/20187/20/2018ACANC
DetailsMike Jordan
Barry Phone #: ###-####
FIRE-Final Inspection7/19/20187/20/20187/20/2018AFAIL
DetailsTroy Cobbley
Need project related fire alarm permit finaled and an exit sign added in new corridor.


Barry Phone #: ###-####
BLD-Conference7/20/20187/20/20187/20/2018PCANC
DetailsMike Jordan
Barry Phone #: ###-####
Print Occupancy Form  7/20/2018 DONE
BLD-Ceiling Grid Inspection7/13/20187/13/20187/13/2018PPASS
DetailsMike Jordan
Charles Phone #: ###-####. phase 3 above ceiling and ceiling grid ok.
BLD-Ceiling Grid Inspection7/10/20187/11/20187/11/2018PPASS
DetailsMike Jordan
Barry Phone #: ###-####. Break room, equipment room and sub sterile passage coridor ok.
BLD-Ceiling Grid Inspection7/10/20187/10/20187/10/2018PPASS
DetailsMike Jordan
Charles Phone #: ###-####. Ceiling grid and fire stopping above grid at mens and womens loker rooms, new phamacy rooms and two closets next to pharmacy.
BLD-Framing/Rough-in6/18/20186/19/20186/19/2018APASS
DetailsMike Jordan
Barry Phone #: ###-####. fire proofing has been patched on tube steel columns. !hr. assembly above grid complete. Aslo inspected shaft board liner on interior side of 1hr. wall in anesthesia work room.
BLD-Framing/Rough-in6/13/20186/14/20186/14/2018APART
DetailsMike Jordan
Berry Phone #: ###-####. Interior steel stud framed walls for new pre op bed aditions. Needs to hand patch fire proofing back on tube stell columns and complete 1hr. fire wall envelope aboce grid.
BLD-Framing/Rough-in5/24/20185/24/20185/24/2018PPASS
DetailsMike Jordan
Max Phone #: ###-####. Prerock on 1hr. wall at anesthesia work room behind bump out wall on patient side.
BLD-Framing/Rough-in5/18/20185/21/20185/21/2018APART
DetailsMike Jordan
Barry Phone #: ###-####. Inteior steel stud framed walls for anesthesia work room.
BLD-Framing/Rough-in5/9/20185/9/20185/10/2018PCANC
DetailsMike Jordan
Barry Phone #: ###-####
BLD-Framing/Rough-in5/9/20185/10/20185/10/2018APASS
DetailsMike Jordan
Barry Phone #: ###-####. INterior steel stud framed walls for pharmacy, breakroom, New O.R. and substerilr rooms ok.
BLD-Final4/17/20184/18/20184/18/2018PPART
DetailsMike Jordan
Charles Phone #: ###-####. Vending room 118 only ok to occupy..
FIRE-Final Inspection4/17/20184/18/20184/18/2018APART
DetailsTroy Cobbley
Vending Room 118 life safety is passed. Will need an additional notification device before project final due to the office being utilized by more than one person.

Charles Phone #: ###-####
BLD-Ceiling Grid Inspection4/13/20184/16/20184/16/2018PPASS
DetailsMike Jordan
Jeff Phone #: ###-####. Room #119.
BLD-Final4/2/20184/2/20184/3/2018PPART
DetailsMike Jordan
Barry Phone #: ###-####. Purchasing room 119 only ok to occupy.
BLD-Ceiling Grid Inspection3/27/20183/28/20183/28/2018APASS
DetailsMike Jordan
Charles Phone #: ###-####
BLD-Final3/13/20183/14/20183/14/2018APART
DetailsMike Jordan
Charles Phone #: ###-####. Ok to occupy new addition. Verified all trades.
FIRE-Final Inspection3/13/20183/14/20183/14/2018APART
DetailsTroy Cobbley
Life safety for Passage 115 will be passed when ceiling tile has been installed.

Charles Phone #: ###-####
FIRE-Final Inspection3/12/20183/13/20183/13/2018APART
DetailsTroy Cobbley
Life safety in new addition passed. Passage 115 was not complete yet.

Charles Phone #: ###-####
BLD-Ceiling Grid Inspection2/13/20182/14/20182/14/2018PPART
DetailsMike Jordan
Jeff Phone #: ###-####. Addition portion.
BLD-Framing/Rough-in2/1/20182/1/20182/1/2018PPASS
DetailsMike Jordan
Blow patches on existing exterior wall at passage #115 behind furred wall.
BLD-Framing/Rough-in1/31/20182/1/20182/1/2018ANR
DetailsMike Jordan
Charles Phone #: ###-####. Moved to pm. inspection.
BLD-Framing/Rough-in1/30/20181/31/20181/31/2018APASS
DetailsMike Jordan
Charles Phone #: ###-####. interior steel stud framed walls at rooms 117,118,119, 146 and 147. Furred walls on passage 115.
BLD-Energy code compliance1/3/20181/4/20181/4/2018APASS
DetailsMike Jordan
Jeff Phone #: ###-####
BLD-Framing/Rough-in12/21/201712/21/201712/21/2017PPASS
DetailsMike Jordan
Charles Phone #: ###-#### Remainder of framing in addition ok.
BLD-Final12/13/201712/13/201712/13/2017PCANC
DetailsMike Jordan
Charles Phone #: ###-####
BLD-Final12/12/201712/13/201712/13/2017APART
DetailsMike Jordan
Ok to occupy M.O.B building south of gridline N6.5 and corridor149 and 156 ( link from existing hospital to M.O.B.) only.
FIRE-Final Inspection12/12/201712/13/201712/13/2017APART
DetailsTroy Cobbley
Life safety for the MOB portion of the project is passed. The connecting corridor from the new MOB to the existing hospital is ok on life safety as well.

Charles Phone #: ###-####
BLD-Final12/7/201712/12/201712/12/2017PCANC
DetailsMike Jordan
Charles Phone #: ###-####
FIRE-Final Inspection12/12/201712/12/201712/12/2017PFAIL
DetailsTroy Cobbley
Life safety in the MOB tenant improvement will be ok to pass when the sprinkler system in the connecting corridor between the MOB and the existing hospitol has been activated..
BLD-Ceiling Grid Inspection12/7/201712/7/201712/7/2017PPART
DetailsMike Jordan
Charles-above ceiling Phone #: ###-####. Corridor only between existing hospital and new cafeteria. Needs to complete fire stopping at #hr. wall and 1hr. wall above grid.
BLD-Ceiling Grid Inspection12/5/201712/6/201712/6/2017APASS
DetailsMike Jordan
Charles Phone #: ###-####. Ceiling grid at main corridor between b occupancy and 3hr. fire wall ok. Also did courtesey walk through on B occupancy portion of building.
BLD-Final11/22/201711/27/201711/27/2017APART
DetailsMike Jordan
Charles Phone #: ###-####. Ok to occupy rooms 111 and 112 only next to pharmacy. Verified all other trades sign offs.
FIRE-Final Inspection11/22/201711/27/201711/27/2017APART
DetailsTroy Cobbley
Life safety is passed in the two new Pharmacy Rooms in the existing hospital area. Fire alarm and fire sprinkler work is complete.

Charles Phone #: ###-####
FIRE-Final Inspection11/16/201711/17/201711/17/2017AFAIL
DetailsTroy Cobbley
Todays inspection was for the Pharmacy Room. Life safety will be ok in this room when the fier alarm devices have been tested.

Charles Phone #: ###-####
BLD-Ceiling Grid Inspection11/14/201711/15/201711/15/2017PPASS
DetailsMike Jordan
Charles Phone #: ###-####. All grid south of corridor 198 in the B occupancy portion of building.
BLD-Framing/Rough-in11/14/201711/15/201711/15/2017PPASS
DetailsMike Jordan
Charles Phone #: ###-####. Interior steel stud framed walls at rooms 151/150/152/148 and corridors 149 and 156.
BLD-Energy code compliance11/8/201711/8/201711/8/2017PPASS
DetailsMike Jordan
East and south walls of new building ok.
BLD-Energy code compliance11/7/201711/8/201711/8/2017ANR
DetailsMike Jordan
Charles Phone #: ###-####. Inspection moved to today in the pm.
BLD-Framing/Rough-in11/6/201711/7/201711/7/2017APASS
DetailsMike Jordan
Charles Phone #: ###-####. Soffit framing in new dinning room. Interior steel stud framed walls fro new cooridor from ramp at new dinning room to existing dinning room.
BLD-Framing/Rough-in11/1/201711/2/201711/2/2017APASS
DetailsMike Jordan
Charles Phone #: ###-####. Interior steel stud framed wals in east/west corridor, 3hr. fire wall and soffit in new cafetria. Noted will need engineering showing that bottom chord of roof trusses will support new soffit.
BLD-Framing/Rough-in10/19/201710/19/201710/19/2017PCANC
DetailsMike Jordan
Completed inspection in the a.m.
BLD-Framing/Rough-in10/18/201710/19/201710/19/2017APASS
DetailsMike Jordan
Charles Phone #: ###-####. Exterkior curtain walls ok
BLD-Final10/5/201710/6/201710/6/2017PPART
DetailsMike Jordan
late as possible // Charles Miller Phone #: ###-####. Ok to occupy O.R. #141 only. Noted all other trades signed off.
FIRE-Final Inspection10/5/201710/6/201710/5/2017PPART
DetailsTroy Cobbley
O.R. 141 life safety is passed. Sprinkler and alarm work is complete

Charles Miller Phone #: ###-####
FIRE-Final Inspection10/4/201710/5/201710/5/2017ACANC
DetailsTroy Cobbley
Charlies Phone #: ###-#### cancel per Cindy with The Robins & Morton Group
BLD-Final10/4/201710/5/201710/5/2017PCANC
DetailsMike Jordan
Charlies Phone #: ###-#### cancel per Cindy with The Robins & Morton Group
BLD-Framing/Rough-in9/22/20179/25/20179/25/2017APASS
DetailsJim Storey
Charlies Phone #: ###-#### noted on plan set sheer wall/ hard ceilling/ two locations
BLD-Framing/Rough-in9/19/20179/20/20179/20/2017PPASS
DetailsMike Jordan
Charles Phone #: ###-####. Interior steel stud framed walls , remainderof framing west of engineering room and south of corridor.
BLD-Framing/Rough-in9/8/20179/11/20179/12/2017APART
DetailsDave Hannah
Charles Phone #: ###-#### fire caulking inter shaft wall ok to cover ext
BLD-Ceiling Grid Inspection9/7/20179/8/20179/8/2017APASS
DetailsMike Jordan
Charles Phone #: ###-####. Hardlid ok in OR 141.
BLD-Framing/Rough-in8/16/20178/17/20178/17/2017APASS
DetailsMike Jordan
Charles Phone #: ###-####. Interior stel stud framed walls for hood room and anti room. OR #141 and corridor at sterile passage#126. Corridor wallsat corridor 199, and all walls to the east of corridor 199.Also purchaseing office 215 and office 214. All areas marked on approved plans.
OVERRIDE  8/14/2017  
Plan assigned to (CJW)5/9/20175/9/20178/14/2017 PASS
DetailsCarl Westfall
(2nd done) (May 26 - 15 days) (188 sheets) Treasure valley TI
Issue PAID IN FULL permit  8/14/2017 DONE
Routing - PLAN CHECK8/11/2017 8/14/2017 PASS
DetailsCarl Westfall
Drawings approved after the revisions were reviewed. No need to route the drawings to any other agency.
PLANS/APPL TAKEN TO FRONT DESK  8/14/2017 DONE
Permit Ready to Issue  8/14/2017 DONE
Permit has never been issued
Routing - FIRE8/7/20178/7/20178/11/2017 PASS
DetailsScott Arellano
Attached revised comments to plans.
Plan resubmittals requested  8/11/2017 DONE
The Architect wanted to upload drawings after making the changes that were redlined on the drawings. Even though all agencies had approved the drawings, I complied with the Architect's desire and sent the workflow back to her.
Plan resubmittals received  8/11/2017 DONE
Routing - PLUMBING8/8/2017 8/9/2017 PASS
DetailsBill VanDegrift
Please transfer your notes to the most recent version
per plan and ISPC.
Routing - MECHANICAL8/8/2017 8/9/2017 PASS
DetailsTroy James
Please transfer your notes to the most recent version.
Routing - PLAN CHECK8/3/2017 8/8/2017 PASS
DetailsCarl Westfall
Routing for the 2nd review was delayed because the assigned Plans Examiner was gone on vacation and because ePlanReview was not available because of an upgrade when he came back. He was gone on Aug 2, 3, and 4 (Wed, Thurs, Fri) but was back on Aug. 5 (Saturday). He could have routed the drawings on Saturday had ePlanReview been available.
Plan resubmittals received  8/3/2017 DONE
Route to Impact Fee Review7/21/20177/24/20178/1/2017 PASS
DetailsMarissa Taylor
Review requested for Commercial Permit
1st review completed  7/21/2017 DONE
Plan resubmittals requested  7/21/2017 DONE
Routing - PLAN CHECK5/9/2017 7/21/2017 FAIL
DetailsCarl Westfall
1st review completed
Routing Off Site - C.D.H5/9/2017 7/17/2017 PASS
DetailsCarl Westfall
(7-17-17) Talked to Natasha Ferney on the phone. She said that just today she received what she needs to complete her review. She completed it later the same day.
Routing - PLANNING Land Div5/9/2017 5/12/2017 PASS
DetailsTodd Tucker
Routing - MECHANICAL5/9/2017 5/12/2017 PASS
DetailsTroy James
Routing PW Environmental5/9/2017 5/12/2017 PASS
DetailsRick Christenson
Routing - FIRE5/9/20175/9/20175/11/2017 FAIL
DetailsKatie Marron
Report attached to case and emailed to architect.
Routing - PLUMBING5/9/2017 5/11/2017 PASS
DetailsBill VanDegrift
Per plans and ISPC
Routing PW Solid Waste5/9/2017 5/10/2017 PASS
DetailsEvan Carpenter
Solid waste is OK as planned.
Routing - Erosion and Sediment5/9/2017 5/10/2017 PASS
DetailsAndy J. Long
ESC plan approved. Need to designate Responsible Person. Site preparation inspeciton is required.
Intake Approval  5/9/2017 PASS
Routing - Addressing5/9/2017 5/9/2017 PASS
DetailsLaura Hunter
Routing - PUBLIC WORKS5/9/2017 5/9/2017 PASS
DetailsRachael Beierle
SWR17-00226 IS ATTACHED TO 1ST PHASE.
Routing PW Drainage5/9/2017 5/9/2017 PASS
DetailsBrian Murphy
Routing - PLANNING5/9/2017 5/9/2017 PASS
DetailsCody Riddle
No review required. Approved by DRH16-00514.
Routing - Design Review5/9/2017 5/9/2017 PASS
DetailsKatelyn Menuge
per DRH16-00514 and BLD17-00359
Routing - PLANNING5/9/2017 5/9/2017 PASS
DetailsCeline Acord
per approval of CUP16-00094 (and BLD17-00359)
Intake Approval  4/25/2017 FAIL
DetailsJavier Guzman
Please provide the following items, Incomplete submittals will not be accepted. Applicants with incomplete submittals must upload additional documents:
• Please provide a filled out #502 checklist as this is a new addition to the existing building and does not fall under the #520 checklist that was uploaded. The #502 checklist can be found at http://pds.cityofboise.org/media/43820/502-new-commercial-building-additions-submittal-checklist_7-5-16.pdf
• Please provide Structural calculations stamped and signed by an Idaho licensed engineer.
• Please provide a Soils and geotech report for support of the structure stamped and signed by an Idaho licensed engineer or declare on plans the default seismic site class & soil bearing per IBC
• Please provide a Soils and geotech report for infiltration systems stamped and signed by an Idaho licensed civil engineer, geologist, or soil scientist
• Please provide a Verification of Legal Lot or Parcel form signed and approved by PDS Subdivision Staff found at our website at https://pds.cityofboise.org/media/134120/211_verificationlegallot_application.pdf
• The new plan sheets show a kitchen please provide completed Food Establishment License application and Food Establishment Plan Review and Approval form for any building where food is prepared, manufactured or stored. Forms are available at: www.cdhd.idaho.gov/EH/food/forms.htm.
• Please provide Form #310 – Statement of Special Inspections must be completed by the design engineer. Form can be found at our web site at http://pds.cityofboise.org/media/104147/final310_special_inspections.pdf
• Please provide if any Shallow Injection Well Inventory form Drainage plans with seepage beds must submit a “Shallow Injection Well Inventory” form from the Idaho Department of Water Resources available at: http://www.idwr.idaho.gov/wells/shallow-injection-wells.html
• Please provide Site Drainage Report stamped and signed by an Idaho licensed design professional including descriptive narrative and calculations
• Please provide a Drainage System Operation & Maintenance Plan stamped and signed by Idaho licensed design professional
• Please check off new checklist box for the required Permanent Operation & Maintenance Agreement form stating you have mailed in or dropped off the original signed and notarized document from the landowner to the Public Works Drainage Coordinator. Form can be found in Appendix J of the Boise City Stormwater Design Manual and at this link: http://publicworks.cityofboise.org/services/drainage-control/
• Please provide Site & Landscape Plans
• Please provide Erosion & Sediment Control, Grading/Drainage Plans
• Please provide structural plans stamped and signed by an Idaho licensed engineer to include design loads and material specifications, identify required special inspections, Foundation plans & details, wall framing & bracing details, Structural building sections, Floor framing plans & details and Roof framing plans & details.
• Please provide an Idaho licensed architects stamp/signature on EQ plan sheets
• Please provide any additional items I forgot to mention or missed from the #502 Checklist
Application received  4/18/2017 DONE
Application submitted via PDS Online on Apr 18 2017 1:13PM