Information based on query as of Wednesday, May 15, 2024.
Permit Information
Permit NumberELE19-00602
StatusIssued
Name R M E INC
Site Address 502 W FRONT ST
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Install lights, outlets and electrical service for new parking garage.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/6/20203/6/20203/6/2020PPART
DetailsRock A. Hudson
Changing out the exits today. Please come as late as possible or call 1/2 prior to arrival. Danny is the contact. Thanks Phone #: ###-#### Inspection requested via web by Buster Bowen Card signed. TCO OK
Final3/5/20203/5/20203/5/2020PFAIL
DetailsRock A. Hudson
Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen 110.3(B)- Exit lights shall have an operating temp for the environment for which it is installed. 0 degrees celcius to 50 degrees celcius,
32 degrees F to 104 degrees F installed.
-40 degrees C to 50 degrees C on order.
110.26(D)- Illumination around electrical service and panel boards shall not be controlled by automatic means.
Fire alarm circuit breaker is located in a hotel electrical room which is under construction, illumination required.
Conference2/24/20202/24/20202/24/2020PPASS
DetailsRock A. Hudson
Pre TCO walk thru-
- Fire pump replacement being installed due to manufacturing issues.
- Must complete panel schedules.
- Level 2 12"x12" junction has low volt cables not rated for other voltages present in box.
- Elevator yet to complete and inspect.
- Damp location rated receptacles and cover thru out parking garage.
- Exposed wiring for signs shall be terminated in boxes with covers.
- Commissioning report required for generator and lighting systems.
- Label all disconnecting means as to each purpose. 2 located level 6 to 7 on stair tower.
- Ticket stations not in as of 2/24/2020 4pm.
- Stairways have not officially been inspected but appear to have all lighting complete.
Electrical Rough-In2/3/20202/5/20202/4/2020ACANC
DetailsRock A. Hudson
Underground cover for 5th street side historic pole lights. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Duplicate request.
Electrical Rough-In2/4/20202/4/20202/4/2020PPASS
DetailsRock A. Hudson
Underground cover 5th street side. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
2 east pole bases and underground for poles and extend to south rough in ok cover.
Electrical Rough-In2/3/20202/4/20202/3/2020ACANC
DetailsRock A. Hudson
Underground cover. 5th street side for historic street lights. Phone #: ###-#### >> Inspection requested via web by Buster Bowen Inspection cancelled from web by: Buster Bowen
Electrical Rough-In1/27/20201/27/20201/27/2020PPASS
DetailsRock A. Hudson
Garage Soffit cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Garage interior soffits rough in ok cover
Conference1/17/20201/17/20201/17/2020PDONE
DetailsRock A. Hudson
Discussed the occupancy of parking garage in 30 days. General contractor will meet with city officials to determine a completion plan.
BLD18-01831 states several subs will finish on hotel phase including electrical lighting and emergency lighting, generator back up, elevators, egress paths ect.
Completion plan will determine what systems must be complete.
Permanent Service1/1/20201/2/20201/2/2020APASS
DetailsRock A. Hudson
Permanent service. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Main service and fire pump service ok
p/s u/g n ok
Electrical Rough-In12/23/201912/23/201912/23/2019PPASS
DetailsEric Story
Pole Base pour. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
7th floor pole bases ok to cover
Electrical Rough-In12/13/201912/16/201912/16/2019PPASS
DetailsRock A. Hudson
7th floor PT deck cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Last pour noted rough in ok cover
Electrical Rough-In12/11/201912/11/201912/11/2019PPASS
DetailsEric Story
6th floor Stair Tower. After 2pm if possible. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
6th floor elevator shaft ok to cover
Electrical Rough-In12/5/201912/5/201912/5/2019PPASS
DetailsRock A. Hudson
7th Floor NW stair tower. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Discussed running service entrance conductors assciated with fire pump on interior of building. Shall comply with 230.6.
Level 7 area noted rough in ok cover
Electrical Rough-In11/22/201911/25/201911/25/2019PPASS
DetailsRock A. Hudson
6th floor east PT deck cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Pour noted rough in ok cover
Electrical Rough-In11/20/201911/20/201911/20/2019PPASS
DetailsRock A. Hudson
NW Stair Tower cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Level 6 N.W. stair pour rough in ok cover
Electrical Rough-In11/14/201911/14/201911/14/2019PPASS
DetailsRock A. Hudson
6th floor west PT deck cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Level 5 to 6 north and west pour rough in ok cover
Electrical Rough-In11/11/201911/12/201911/12/2019APASS
DetailsRock A. Hudson
SE Stair tower in garage. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Stairway noted pour rough in ok cover
Electrical Rough-In11/1/201911/1/201911/1/2019PPASS
DetailsRock A. Hudson
5th floor PT deck cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Level 5 south and east PT deck pour rough in ok cover.
Electrical Rough-In10/25/201910/25/201910/25/2019PPASS
DetailsRock A. Hudson
Cover for 5th floor NW stair tower. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Area noted rough in ok cover
Electrical Rough-In10/21/201910/21/201910/21/2019PPASS
DetailsRock A. Hudson
5th Floor PT deck cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Level noted on north and west sides pour rough in ok cover.
Electrical Rough-In10/16/201910/16/201910/16/2019PPASS
DetailsRock A. Hudson
Cover for SE stairwell in garage. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Level 4 S.E. stairwell rough in ok cover
Electrical Rough-In10/3/201910/7/201910/7/2019PPASS
DetailsRock A. Hudson
4th floor PT deck pour. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Level 4 ramp and around east side pour rough in ok cover
Electrical Rough-In10/1/201910/2/201910/2/2019APASS
DetailsRock A. Hudson
4th floor NW Stairwell cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Level noted stair walls rough in ok cover
Electrical Rough-In9/25/20199/25/20199/25/2019PPASS
DetailsRock A. Hudson
Shear wall cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Shear wall level 2 south east corner rough in ok cover
Electrical Rough-In9/23/20199/23/20199/23/2019PPASS
DetailsRock A. Hudson
PT deck concrete pour. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
PT deck ramp from level 3 to 4 and around to south on west side pour rough in ok cover.
Electrical Rough-In9/16/20199/16/20199/16/2019PPASS
DetailsRock A. Hudson
Garage stairwell. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Levels 3 to 4 South East stair wall rough in ok cover
Electrical Rough-In9/6/20199/9/20199/9/2019PPASS
DetailsEric Story
Garage PT deck pour. Buster is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
3rd floor PT deck ok to pour
Electrical Rough-In8/28/20198/28/20198/28/2019PPASS
DetailsJames Ady
Cover for 3rd floor NW Stairwell. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Walls only area listed ok to cover
Electrical Rough-In8/23/20198/23/20198/23/2019PPASS
DetailsRock A. Hudson
Deck pour cover. Tyson is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Level 2 to 3 ramp and level 3 deck pour rough in ok cover.
Electrical Rough-In8/16/20198/16/20198/16/2019PPASS
DetailsRock A. Hudson
Garage Stairwell cover. Tyson is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
S.E. stair well level 2 walls rough in ok cover
Electrical Rough-In8/7/20198/7/20198/7/2019PPASS
DetailsRock A. Hudson
Wall cover for NW stairwell. Tyson is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Area noted rough in ok cover
Electrical Rough-In8/5/20198/5/20198/5/2019PPASS
DetailsRock A. Hudson
PT deck pour from level 2 to 3 rough in ok cover
Electrical Rough-In8/2/20198/5/20198/5/2019PNH
DetailsRock A. Hudson
Danny PT deck concrete pour at front street garage. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Contact provided is on bereavement leave due to the death of his daughter. Undable ot locate others on site. Provide correct contact number so I do ot have to bother this person again.
Electrical Rough-In7/15/20197/16/20197/16/2019PPASS
DetailsRock A. Hudson
Garage concrete pour cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Report has been given of someone with general contractor removing electrical conduits with out informing electrical contractor.
BCC 4-05-15 It shall be unlawful for any person to engage in electrical work without first having a electrical journeymans license and be employed by an electrical licenced and permitted electrical contractor.
First and only warning, if any electrical wiring , conduit, or equipment is installed or removed without consulting electrical foreman of licensed and permitted electrical contractor a compliance inspector from the State of Idaho will be brought on site to discuss penalties and fines up to $1000 that may be assessed for each infraction. Level 2 west pour as noted on contractor print rough in ok cover
Electrical Rough-In6/18/20196/18/20196/18/2019PPASS
DetailsRock A. Hudson
Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
EMT being used with taped up boxes and fittings as per instructions. Bottom of ramp pour rough in ok cover
Electrical Rough-In5/8/20195/8/20195/8/2019PPASS
DetailsRock A. Hudson
UG inspection. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Garage underground complete, west of line 9 rough in ok cover
Electrical Rough-In5/6/20195/6/20195/6/2019PPASS
DetailsDaryl DeGrange
UG cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Rough-in ok cover between A-D 1 thur 9
Electrical Rough-In4/26/20194/26/20194/26/2019PPASS
DetailsRock A. Hudson
UG inspection. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
East parking garage underground roug in ok cover.
Electrical Rough-In4/17/20194/18/20194/18/2019APASS
DetailsRock A. Hudson
NW Concrete Stairwell rough in. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Area noted pour rough in ok cover
Electrical Rough-In4/8/20194/9/20194/9/2019APASS
DetailsRock A. Hudson
Cover for NE concrete walls. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
N.E. corner wall pour rough in ok cover
Electrical Rough-In4/2/20194/2/20194/2/2019PPASS
DetailsMark Moncarr
Wall rough. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Ok cover conduits SE hotel stairwell.
Electrical Rough-In4/1/20194/1/20194/1/2019PPASS
DetailsRock A. Hudson
Wall rough for garage. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
South East stair wall pour rough in ok cover
Electrical Rough-In2/19/20192/19/20192/19/2019PPASS
DetailsRock A. Hudson
Uffer inspection. Danny is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Concrete encased electode rough in ok cover