Permit Information
Permit NumberFIR18-00673
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION
Site Address 4455 E WARM SPRINGS AVE
Project NameAspen Valley Senior Living
Customer Number 
ePlanReviewYes
Description
[Aspen Valley Senior Living]
The fire sprinkler scope of work consists of new assisted living facility with one wet system and three dry systems. CPVC piping, attic sprinklers and residential sprinklers will be utilized. The 8” underground supplies a 6” backflow preventer and 6” headers. There are two 6” dry systems and one 4”. There is one 4” wet system.

The underground piping is under permit FIR18-00322.

[BLD18-00494]
The fire sprinkler system is used for building area increase and for occupancy. The footings, foundations, under slab plumbing, and concrete slab on grade were done early start permit BLD18-01504. To construct a 47,379 square foot, one story building (33,224 square feet West “building” and 14,155 square feet East “building” separated by a 2-hr fire wall) to be used as an assisted living facility (50 units) and as a memory care facility (16 units having a total floor area of about 6,853 square feet). Within the assisted living facilities, occupants are expected to be able to respond to an emergency situation without assistance. Within the memory care facility, occupants are expected to need assistance to respond to an emergency situation. In both facilities, the need for bed movement is not expected within or between smoke compartments (i.e. no one is confined to their bed). Work is to include concrete footings, concrete stem walls, concrete pedestals, concrete slab on grade with thickened sections to support interior bearing walls, exterior and interior wood stud walls, exterior and interior wood stud bearing walls with headers at openings, exterior and interior wood stud shear walls with hold downs, wood beams and columns, wood trussed roof system with girder trusses, wood roof sheathing, exterior windows, exterior doors, board and batten siding, lap siding, manufactured stone wainscot, wood trellis accent awnings, metal accent awnings, corrugated metal siding, asphalt shingles, standing seam metal roofing, a 6 foot tall masonry screen wall, a 6 foot tall masonry trash enclosure, and a Porte cohere. Special Inspection is required for soils, concrete, shear walls, and roof diaphragms. The design for roof trusses is a deferred submittal item. Other work includes 22 “Unit A” assisted living units each having a toilet/shower room (375 sq. ft. each), 26 “Unit B” assisted living units each having a toilet/shower room (467 sq. feet each), 1 “Unit D” assisted living unit having a toilet/shower room (600 sq. ft.), 1 “Unit E” assisted living unit having a toilet/shower room (467 sq. ft.), and 16 “Unit C” memory care sleeping units each having a toilet room (208 sq. ft. each), a Men’s multi-user toilet room accessible to the disabled, a Women’s multi-user toilet room accessible to the disabled, two single-user toilet rooms accessible to the disabled, a commercial kitchen, a Type I grease hood and duct system, a Type II dishwasher hood and duct system, make-up air, exterior grease trap, a 2-hr fire wall to create separate buildings for building area, 1-hr smoke barrier walls to create smoke compartments, millwork, and interior finishes. At least 2 of the assisted living units are required to comply as “accessible units”. The rest are required to comply as “Type B dwelling units”. All of the memory care units will comply as “accessible units”. A separate permit is required for the future gazebo and trellis. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**


Alternative Materials and Methods:
This project includes approved code alternates to the following fire protection systems and/or buildin
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/9/20195/10/20195/10/2019APASS
DetailsMark Scharfen
Corrections have been made. Eschuchons, heads fixed and signs placed. Passed

Todd Phone #: ###-####
INSP-Final Inspection5/8/20195/8/20195/8/2019AFAIL
DetailsMark Stumbaugh
Escustechons missing or sprinklers low in rooms 109, 310, 120, 119, 110, 111. Tested interconnect with fire alarm panel-reports correctly. Forward flush is at 783 gallons.

Please call when in route Phone #: ###-#### >> Inspection requested via web by Kristin Dolan
INSP-Final Inspection4/29/20194/29/20194/29/2019PCANC
DetailsTroy Cobbley
The project related fire alarm permit is still in Ready To Issue status. No inspection was performed. Will need to reschedule when ready. Please call ahead Phone #: ###-#### Inspection requested via web by Gary Gambino
INSP-Final Inspection4/24/20194/26/20194/26/2019AFAIL
DetailsJim Page
Fire alarm system permit still in review, no device testing performed.

Todd Phone #: ###-####
INSP-Alarm Testing4/24/20194/26/20194/26/2019ACANC
DetailsJim Page
Fire alarm devices under a seperate permit, this request is cancelled.

Todd Phone #: ###-####
INSP-Alarm Testing4/24/20194/25/20194/25/2019ACANC
DetailsJim Page
Fire alarm devices under a seperate permit, this request is cancelled.

Todd Phone #: ###-####
INSP-Final Inspection4/24/20194/25/20194/25/2019APART
DetailsJim Page
Partial final inspection for overhead fire sprinklers complete, escutcheons are in place, no testing of fire alarm associated items due to fire alarm permit still in reviewed status.

Todd Phone #: ###-####
INSP-Final Inspection4/24/20194/24/20194/24/2019PCANC
DetailsJim Page
Rescheduled for 25APR2019 per conversation with point of contact, this request is cancelled.

Todd Phone #: ###-####
INSP-Final Inspection4/9/20194/11/20194/11/2019PPART
DetailsJim Page
Time requirements for dry system trip (3 systems total) test complete. Need as-builts submitted boefore final inspection.

Please call Todd Woods prior to arrival to coordinate inspection. Phone #: ###-#### Inspection requested via web by Kristin Dolan
INSP-Sprinkler Rough-in3/28/20193/29/20193/29/2019APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover. All rough in inspections for project complete.

Todd Phone #: ###-####
INSP-Sprinkler Rough-in2/20/20192/21/20192/21/2019PPASS
DetailsJim Page
Rough to cover inspection for reamining pipe in main entry hallway complete, approved for cover.

hallway // Todd Phone #: ###-####
INSP-Sprinkler Rough-in2/14/20192/15/20192/15/2019APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping above hardlids in corridor complete, corridors approved for cover.hallway // Todd Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro1/29/20191/31/20191/31/2019PDONE
DetailsJim Page
Hydrostatic test for all overehad fire sprinkler piping witnessed, no pressure loss observed.

Phone #: ###-#### Inspection requested via web by Shane Lesteberg
INSP-Sprinkler Rough-in/Hydro1/26/20191/30/20191/30/2019ADONE
DetailsJim Page
24 hour air test on the 3 dry systems complete.

Phone #: ###-#### Inspection requested via web by Shane Lesteberg
INSP-Sprinkler Rough-in/Hydro1/29/20191/29/20191/29/2019AFAIL
DetailsJim Page
Hydrostatic test for wet system lost 4 psi during test, te-hydro is required.

INSP-Sprinkler Rough-in/Hydro1/26/20191/29/20191/29/2019APART
DetailsJim Page
24 hour ait test started at 10AM with 40 psi on all three dry systems.

Phone #: ###-#### Inspection requested via web by Shane Lesteberg
INSP-Sprinkler Rough-in/Hydro1/26/20191/28/20191/28/2019PCANC
DetailsJim Page
Cancelled per conversation with point of contact, inspection request will be rescheduled by contractor.

Phone #: ###-#### Inspection requested via web by Shane Lesteberg
INSP-Sprinkler Rough-in/Hydro1/24/20191/28/20191/26/2019ACANC
DetailsJim Page
Dry system air test Phone #: ###-#### >> Inspection requested via web by Shane Lesteberg Inspection cancelled from web by: Shane Lesteberg
INSP-Sprinkler Rough-in/Hydro1/24/20191/25/20191/25/2019PPART
DetailsJim Page
Rough to cover inspection for east side area B complete, area inspected approved for cover.

Phone #: ###-#### Inspection requested via web by Shane Lesteberg
INSP-Sprinkler Rough-in/Hydro1/23/20191/25/20191/24/2019ACANC
DetailsJim Page
Phone #: ###-#### >> Inspection requested via web by Shane Lesteberg Inspection cancelled from web by: Shane Lesteberg
INSP-Sprinkler Rough-in1/18/20191/22/20191/22/2019APART
DetailsJim Page
Rough to cover inspection for east side area B complete, area inspected approved for cover.

Cover inspection. Contact Nick Smith with time. Thanks! Phone #: ###-#### Inspection requested via web by Shane Lesteberg
INSP-Sprinkler Rough-in1/2/20191/3/20191/3/2019APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping/tenting for remaining section of area C complete, approved for cover.

Todd Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro12/26/201812/27/201812/27/2018ACANC
DetailsJim Page
Tenting has not been installed for area requested for cover, inspection cancelled per point of contact.

Todd Phone #: ###-####
INSP-Sprinkler Rough-in12/12/201812/13/201812/13/2018APART
DetailsJim Page
Previously noted items for area C complete, area C on the fire sprinkler drawings approved for cover.

Site Contact - Nathan Phone #: ###-#### Inspection requested via web by Shane Lesteberg
INSP-Sprinkler Rough-in/Hydro12/6/201812/10/201812/10/2018AFAIL
DetailsJim Page
Numerous heads throughout attic space are blocked, correct blockage issue. Numerous areas in attic space has no sprinkler protection. Sway bracing attached to truss webbing needs to be relocated to top cord, bottom cord or verticals. Need access to overbuilds to verify upright protection. Correct hangers on CPVC armovers that are over 6 inches.

CI sprinkler foreman - Nathan Gregory Phone #: ###-#### Inspection requested via web by Shane Lesteberg
INSP-Sprinkler Rough-in11/26/201811/27/201811/27/2018APART
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping located in west wing complete (from fire doors west), area inspected approved for cover for both wet and dry system. Noted that hydrostatic tests can only be completed if the inside building temperature is maintained at 40 degrees or above with an un-interruptable heat source. If temperature cannot be maintained above 40 degress at all times then antifreeze will be required for hydros. If heat is shut off to building and the pipe is exposed to below 40 degrees after a hydro is completed then a new hydro will be required to verify intregrity of the system.

Phone #: ###-#### Inspection requested via web by Shane Lesteberg
INSP-Sprinkler Rough-in/Hydro11/16/201811/19/201811/19/2018AFAIL
DetailsJim Page
Sway bracing attachments need to be a minimum of a 4X, attachments for attic mains are attached to 2X4, not a 4X4 or larger. Fix blocked head as noted. Move hangers that are to close to the attic heads.

Phone #: ###-#### Inspection requested via web by Shane Lesteberg
INSP-Sprinkler Rough-in/Hydro11/14/201811/15/201811/15/2018PFAIL
DetailsJim Page
No stamped city approved drawings on site, need city approved drawings to be onsite at all times.

Contact Pablo at ###-#### Phone #: ###-#### Inspection requested via web by Shane Lesteberg
INSP-Sprinkler Rough-in11/14/201811/15/201811/15/2018PFAIL
DetailsJim Page
No stamped city approved drawings on site, need city approved drawings to be onsite at all times.

Contact Pablo at ###-#### Phone #: ###-#### Inspection requested via web by Shane Lesteberg